Configuration of system texts

Configuration of system texts is performed by means of the process D2000 CNF.

Configuration of system texts

The system texts are divided into the following categories:


The objects, values of which do not contain system texts:

  • I/O tags of AI, AO, CI, CO, TiA, ToA, TiR, ToR, TmRo, TxtI a TxtO types
  • Evaluated tags
  • User variables of Integer, Real, TmA, TmR, Txt types

* Displaying of values of Integer, Real, Absolute time and Time interval types might be controlled by transformation palette.


Boolean values

Label in the system Predefined label Cause
B_False False False value
B_True True True value
B_Oscillate Oscilate Oscillating value (TRUE <-> FALSE).


Di, Do measured values

Label in the system Predefined label Cause
D_False OFF False value
D_True ON True value
D_Oscillate OSCILATE Oscillating value (TRUE <-> FALSE). The system sets the value as the oscillating one according to defined parameters of filtering - Oscillation limits.


Process object values

Label in the system Predefined label Cause>
P_Run Run The process is running.
P_Crash Crash The process is terminated by an error (incorrect termination). If it is possible, D2000 Server will try to start the process again.
P_Stop Stop The process is correctly terminated.
P_WDErr WDErr Error when communicating with D2000 Server - Watch Dog Error (interrupted flow of Watch Dog messages between the client process and D2000 Server).


System alarm values

Label in the system Predefined label Cause
A_Norm Normal The condition to raise the alarm is not met.
A_Alarm Alarm The condition to raise the alarm is met.
A_Kvit Kvit The alarm is acknowledged by operator.
A_Block Block The alarm is blocked by operator, or at the alarm configuration is enabled Blocked alarm option.
A_UnBlock UnBlock The process D2000 Alarm is not running and operator unblocks the given alarm in Blocked state.
A_NoKvit NoKvit The condition to finish the acknowledge-required alarm is met before its acknowledgement.


Station values

Label in the system Predefined label Cause
St_On ON The station communicates
St_Off OFF The station does not communicate. The communication is disabled by operator (via the control window in process D2000 HI) or at the station configuration in the process D2000 CNF.
St_CommErr COMERR The occurrence of a "soft" error of the communication. Such error is occurred after an unsuccessful data transmission.
St_HardErr HARDERR The occurrence of "hard" error of the communication. Such error is occurred, if the communication with station is in StCOMERR state within the period given by Time filter parameter. If the station value is StHARDERR, then all the I/O tags of the station will pass to undefined state.
St_Simul SIMUL Communication with the station is simulated.
St_Wait WAIT The station is in AUTO mode. Communication is stopped. The control object value is TRUE. Requests for output are postponed and they will be executed when the control object value will be FALSE.


Qi measured values

Label in the system Predefined label Cause
SwTrans TRANS Change of quadrature value from TRUE into FALSE or vice-versa.
SwOff OFF False value
SwOn ON True value
SwErr ERROR Invalid (illegal) value.
SwOsc OSCILATE Oscillating value (TRUE <-> FALSE). The system sets a value as the oscillating one according to defined parameters of filtering - Oscillation limits.


Process alarms

Label in the system Predefined label Cause
NoAlarm NoAlarm No process alarm is active
ToTrue ToOn Process alarm occurred - change into ON (TRUE) level.
ToFalse ToOff Process alarm occurred - change into OFF (FALSE) level.
True On Process alarm occurred - ON (TRUE) level.
False Off Process alarm occurred - OFF (FALSE) level.
Invalid Err Invalid (illegal) value.
Oscillate Oscillate Oscillating value.
HL HL Process alarm occurred - limit state of HL value.
VHL VHL Process alarm occurred - limit state of VHL value.
LL LL Process alarm occurred - limit state of LL value.
VLL VLL Process alarm occurred limit state of VLL value.
ToHL ToHL Process alarm occurred- value change into HL limit state.
ToVHL ToVHL Process alarm occurred- value change into  VHL limit state.
ToLL ToLL Process alarm occurred - value change into LL limit state.
ToVLL ToVLL Process alarm occurred - value change into  VLL limit state.
SwToTrans SwToTrans Process alarm occurred - change of quadrat value into Q_Trans value.
SwToOff SwToOff Process alarm occurred- change of quadrat value into Q_Off (FALSE) value.
SwToOn SwToOn Process alarm occurred- change quadrat value into Q_On (TRUE) value.
SwToError SwToErr Process alarm occurred - change of quadrat value into Q_Err value.
SwTrans SwTrans Process alarm occurred- quadrat value is Q_Trans.
SwOff SwOff Process alarm occurred - quadrat value is Q_Off.
SwOn SwOn Process alarm occurred - quadrat value is Q_On.
SwError SwErr Process alarm occurred - quadrat value is Q_Err.
ErrorWriteCmd ErrWriteCmd Error at the setting of output tags.
Sw_ErrorCmdOn ErrCmdOn Error during cm_SetSwitchOn command execution.
Sw_ErrorCmdOff ErrCmdOff Error during cm_SetSwitchOff command execution.
Sw_ErrorBkpCmdOff ErrZalCmdOff Error during cm_SetSwitchBkpOff command execution.
Change Change Process alarm occurred - change of integer or analog value.
SysPrAl SysProcAlarm Special type of process alarm used just for two objects of System variable type - SystemError and SystemWarning.


Value limits

Label in the system Predefined label Cause
Is_InLimit InLimit The object value is at once greater or equal to LL and less or equal to HL (LL<=values<=HL).
Is_VL_Limit VL_Limit The object value is less than VLL (value<VLL).
Is_L_Limit L_Limit The object value is at once greater or equal to VLL and less than LL (VLL<=value<LL).
Is_H_Limit H_Limit The object value is at once greater than HL and less than VHL (HL<value<=VHL).
Is_VH_Limit VH_Limit The object value is greater than VHL (VHL<value).
Is_LimitsProblem LimitsProblem In case of dynamic limits, there is the validity mismatch of the conditions: VLL<LL<HL<VHL.


Value states

Label in the system Predefined label Cause
s_val_Invalid Invalid Invalid object value.
s_pa_Alarm ProcAlarm The state is occurred in case that the given object has an active process alarm.
s_pa_NoAck NoAckPAlarm The state is occurred in case that the process alarm is not acknowledged by operator in process D2000 HI.
s_pa_Blocked PrAlSilent The state is occurred in case that the given object has not any active process alarm, or Silent option is enabled at configuration of object process alarms in the process D2000 CNF.
s_val_Weak Weak Weak (suspicious) value is a value not valid in the system, because all the conditions of its validity are not met.
s_val_NoAck NoAckValue The state is occurred in case that the last object value change is not acknowledged by operator in process D2000 HI.
s_val_Transient Transient Transient state of the value is occurred, if the command that sets the object value was executed, but backward reading has not yet verified the value setting.
s_val_Default Default Default state of the object value is occurred, if the I/O tag value gained by the process D2000 KOM is replaced by other value - the control object value, or is manually set by operator in process D2000 HI.
s_val_Manual Manual The object value is in Manual state, if it is manually set by operator in process D2000 HI.
s_pa_Critical PrAlCrit The status is occurred in case that the process alarm is defined as critical one in the process D2000 CNF.
s_pa_Unknown Unknown  


Operator commands

Label in the system Predefined label Cause
cm_SetDefautManual SetDefMan Manual setting of the object default value.
cm_SetDefautAuto SetDefAuto Activation of the automatic mode of the object default value control. The default value in this mode will be copied the control object value.
cm_SetManual SetManual Manual setting of output object value.
cm_SetAuto SetAuto Activation of the automatic mode of the output object value control. The object value in this mode copies the control object value.
cm_SetDefaultOff SetDefOff Cancel the validity of the object default value.
cm_SetSwitchBlockAOn SetBlockAOn Activation of blockade A of the switch.
cm_SetSwitchBlockAOff SetBlockAOff Deactivation of blockade A of the switch.
cm_SetSwitchOn SetSwitchOn Switch on the switch.
cm_SetSwitchOff SetSwitchOff Switch off the switch.
cm_SetSwitchBkpOff SetSwitchBkpOff Backup switch off the switch.
cm_SetSwitchBlockBOn SetBlockBOn Activation of blockade B of the switch.
cm_SetSwitchBlockBOff SetBlockBOff Deactivation of blockade B of the switch
cm_SetSwitchNormalOff SetSwitchNormalOff Set the switch to the normal state - OFF.
cm_SetSwitchNormalOn SetSwitchNormalOn Set the switch to the normal state - ON.
cm_SetSwitchNormalNone SetSwitchNormalNone Set the switch to the normal state - NONE.


Alarm commands

Label in the system Predefined label Cause
cm_AlarmKvit Kvit The alarm is acknowledged by operator.
cm_AlarmBlock Block The alarm is blocked by operator, or Blocked alarm option is enabled at its configuration in the process D2000 CNF.
cm_AlarmUnblock Unblock The alarm is unblocked by operator.