Circutor CVMk MODBUS communication protocol

Supported device types and versions 
Communication line configuration
Communication station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions

Kotva
typy_verzie
typy_verzie
Supported device types and versions

...

Kotva
komunikacna_stanica
komunikacna_stanica
Communication station configuration

...

  • Communication protocol: MODBUS Circutor CVMk.
  • Station address is a decimal number in the range of 0 up to 255 or a hexadecimal number with a hash at the beginning (e.g. #1A).


Station protocol parameters

There can be defined the following parameters:

Table 1

Key wordFull nameMeaningUnitDefault value
Kotva
rc
rc
RC
Retry CountNumber of retry calls when an error in communication occurs.-2
Kotva
rt
rt
RT
Retry TimeoutDelay between retry calls if an error in communication occurs.ms200 millisec.
Kotva
wft
wft
WFT
Wait First TimeoutFirst waiting on the response after sending a call.ms100 millisec.
Kotva
wt
wt
WT
Wait TimeoutDelay between the readings of a response until it is completed.ms100 millisec.
Kotva
mwr
mwr
MWR
Max Wait RetryNumber of retry response reading until it is completed.-15

...

Kotva
merany_bod
merany_bod
I/O tag configuration

...

I/O tags: Ai

Address – decimal number in the range of 0 to 65535 – number of MODBUS double register, or a hexadecimal number with a hash at the beginning (e.g. #0ABC).

The values are read by 2 registers and interpreted as a 4 byte integer. The addresses of values are described in literature about Circutor.

...