Premex CALMEX II communication protocol

Supported device types and versions 
Communication line configuration
Communication station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions

Supported device types and versions


The protocol allows reading data from multifunctional calorimetric counters of the VKP and VKPs CALMEX II types by means of the M-Bus bus (originally used RS232/M-Bus Premex RS-M convertor, after 15 years replaced by converter RS232toMBus-XL45 from www.prevodniky.sk).

Communication line configuration


  • Communication line category: Serial (both convertors), SerialOverUDP Device Redundant (RS232toMBus-XL45 only).
  • Mode 1: Baud rate 300, 8 bit, 1 stop bit, even parity, RTS=1, DTR=1 (RTS and DTR signals are not used by RS232toMBus-XL45).

Communication station configuration


  • Communication protocol: Premex CALMEX II
  • Station address is a decimal number within the range of 1..250 (or a hexadecimal number with a hash at the beginning, e.g. #0A) – it is VKP address. By default, the address is set by the manufacturer according to the serial number (identification number) of the measuring device as the last three digits. If last three digits are greater than 250, the higher digit of them is not taken into account. If the serial number is one of the numbers of 000, 300, 400, 500, 600, 700, 800, 900 then must be changed.
  • Recommended polling parameters: Delay at least 1 minute.


Station protocol parameters

The following station protocol parameters can be defined:

Table 1

KeywordFull nameMeaningUnitDefault value
RC
Retry CountPoll repetition count in case of a communication error.-2 seconds
RT
Retry TimeoutDelay between poll repetition in case of a communication error.ms100 ms
WT
Wait TimeoutDelay between response readings till its finalization.ms500 ms
WFT
Wait First TimeoutFirst waiting for response after sending the poll.ms800 ms
MWR
Max Wait RetryRepetition count of response readings till its finalization.-40
WUL
WakeUp LengthLength (given in characters) of so-called wake-up message sent before each poll.-20
WUD
WakeUp DelayDelay between wake-up message and poll. It is recommended to enable the option WaitTxEMPTY in the line mode configuration.ms400

String containing the protocol parameters is being defined as follows:

Keyword=value;Keyword=value; ...

Example:

RC=1;RT=500;

If there is used a keyword with an invalid value in the initialization string, there will be used corresponding default value according the table 1.

I/O tag configuration


Possible I/O tag types: Ai, Ci, TiA

Address: A number fro the following table must be entered (as a decimal number or as a hexadecimal number with a hash at the beginning, e.g. #0A):

Table 2

AddressMeaningTypeUnits
1Measuring device ID.Ci-
2Access number (measurement number incremented by 1 for each data reading).Ci-
3Status number, bit descriptions see the table 3, individual bits are sent to the value attributes.Ci-
4Heat quantity.AiMJ,GJ,kWh,MWh
5Heat rate.AiW,kW,MW
6Volume overflow.Ail,m3
7Volume flow.Ail/h,m3/h
8Forward temperature.AiºC
9Return temperature.AiºC
10Measuring device date+time.TiA-
11Heat quantity on the 1st date.AiMJ,GJ,kWh,MWh
12Heat quantity on the 2nd date.AiMJ,GJ,kWh,MWh
13Volume overflow on the 1st date.Ail,m3
14Volume overflow on the 2nd date.Ail,m3
151st date of data.TiA-
162nd date of data.TiA-

Values saved on 1st date or 2nd date are sent to the D2000 system with the save time. Measuring unit of individual parameters depends on the measuring device type.

Meaning of status word bits (Ci address - 3)

Table 3

Bit numberMeaningValue attribute
0Always 0.A
10 - current value, 1 - stored value.B
2Low input power.C
3Constant error.D
4Temporary error.E
5Water-meter error.F
6Temperature pickups error.G
7Always 0.H

Literature


-

Changes and modifications


-

Document revisions


  • Ver. 1.0 - March 13th 2001 – document creation.
  • Ver. 1.1 - 7. september 2016 – support for SerialOverUDP Device Redundant line, information about RS232toMBus-XL45 convertor.