VONSCH VQfrem 400 protocol

Supported device types and versions
Communication line configuration
Communication station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions

Supported device types and versions


The protocol is used for communication with vector control frequency converters VQfrem 400 (for 3 x 400 V motors) from VONSCH. Reading values from inverters is supported. Commanding or writing values is not supported.

Communication line configuration


  • Communication line category: Serial, SerialOverUDP Device Redundant (serial communication).
  • Note: serial communication has been tested with a VQfrem 400 with 609h firmware.
    Serial line setting: 19200 baud, 8 bits, no parity, 1 stop bit, RS-485 interface.
    The serial line speed is configurable on the drive (2400 - 19200 baud).

Communication station configuration


  • Communication protocol: VONSCH VQfrem 400.
  • The station address is a 16-bit number (1-32767). It can be entered decimally (e.g. 1 or 1234) or hexadecimally using a hash (e.g. #0001 or #4D2).
    Address 32768 (#8000) serves as a broadcast for commanding - all devices receive it, but none respond to it.

Station protocol parameters


Communication station - configuration dialog box - tab Protocol parameters.
They influence some of the optional parameters. You can set the following station protocol parameters:

Table 1

ParameterMeaningUnitDefault value

Full Debug

Logging of detailed debug information about communication in the line log.-NO

Retry Count

Maximum count of request retries. If no response returns after a request had been sent, the station's status will change to a communication error.-2

Retry Timeout

Timeout before resending a request if no response has been received.ss.ms0.1

Wait First Timeout

The delay after sending the request and before reading the response.ss.ms0.1

Wait Timeout

The delay between the response readings.ss.ms0.1

Max Wait Retry

The maximum number of retries of the response reading.-6

I/O tag configuration


I/O tags: Ai, Ci

I/O tag address

The address of the I/O tag is a 16-bit number (1-65535). It can be entered decimally (e.g. 1 or 1234) or hexadecimally using a hash (e.g. #0001 or #4D2).

Table 2 - quantities available for reading according to the documentation

AddressDescriptionMeaning
#0001Software version609h for ver. 6.09, (402h for ver.4.02, 304h for ver.3.04)

#0004

Voltage range190h for 400V, 191h for 400 ...M, 2b2h for 690V
#0025Freq. INV - the frequency of voltage on converter’s output (stator frequency) +/- XXX,XX Hz
#0026Revolves - output revolutions of the motor+/- XXXX rev/min
#0027Revol/i - evolutions behind gear/transmission+/- XXXX,X rev/min
#0028Freq.RT - rotor frequency (evaluated from speed encoder – IRC)+/- XX,XX Hz
#0029Freq.RF - required converter frequency+/- XX,XX Hz
#002A

MT Curr. - effective current value into the motor

XXX,X A
#002BR.torque - required mechanical motor torque +/- XXX,X Nm
#002CTorque - mechanical motor torque +/- XXX,X Nm
#002DMag. flux - rotor magnetic fluxX,XXX Wb
#002EVolt. MT - momentary motor supply voltage (100.0% responds to 400 V)XXX,X %
#002FVolt. DC - real voltage of converter’s unidirectional DC busXXX V
#0030Inp.pow. - momentary input power into the motorXXX,X kW
#0031

MT power - motor power

XXX,X kW
#0032kW hours - motor energy consumption in kWhXXXX kWh
#0033MW hours - motor energy consumption in MWhXXXX MWh
#0034Teplota chladiča meničaXX,X °C
#0035Temp.INV. - air temperature in the converterXX,X °C
#0036PR ref. - required value of process regulatorXX,X %
#0037PR real - feedback of process regulator (real value)XX,X %
#0038Inp. AIN1 - the value of analogue input AIN1 in % rangeXX,X %
#0039Inp. AIN2 - the value of analogue input AIN2 in % rangeXX,X %
#003AHodnota analógového vstupu 3 v % rozsahuXX,X %
#003B

BIN 1-6 - status of binary inputs BIN 1 - BIN 6 (bits 0-5 from the received value - bit numbering is from 0 to 15). 

0=input is open
1=input is closed
#003C

RELAY 1-2,3 - the status of relay inputs RELAY 1 - RELAY 4  (bits 8-10 from the received value - bit numbering is from 0 to 15). 

0=relay is open
1=relay is closed
#003DHours INV - converter operating time counterXXXX h
#003EHours MT - motor operating time counterXXXX h
#003FPos.ref. - required position in a case of „position“ variable+/- XXXX,X cm
#0040Position - real position+/- XXXX,X cm
#0041Pos. TSW2 - the trajectory for running down when Terminal switch TSW2 is on+/- XXXX cm
#0042Deviation from zero position when calibrating the ARC position sensorXXXX d
#0043cos(fi ) - momentary value of motor power factor+/- X,XX
#0044See Warnings register 2-
#0045See Warnings register 1-
#0046

See Faults register

-
#0048Okamžitá hodnota preťaženiaXXX.X %
#0049Servisná zobrazovaná veličina Slave+/- XXXX d
#004aServisná zobrazovaná veličina Master

+/- XXXX d

Všetky hodnoty sú prenášané ako 16-bitové čisla. KOM proces ich interpretuje ako znamienkové alebo kladné podľa adresy (znamienkové sú #0025-#0027, #002B, #002C, #003F - #0041, #0043, #0049 - #004a).

Pokiaľ je číslo desatinné, treba v konfigurácii meraného bodu v záložke Prevod zadať príslušný lineárny prevod (napr. koeficient A=0.1 pre #0030, A=0.01 pre #0028).


Tab. č. 3 - register porúch (hodnoty bodu s adresou #0046). Ak je ľubovoľný bit nastavený na log.1, potom v meniči vznikla príslušná porucha

BitVýznam
0Nadprúd meniča
1Preťaženie meniča
2Podpätie meniča
3Prepätie meniča
4Tepelný integrál motora
5Teplota chladiča
6

Nekorektné parametre prúdov, konštánt motora alebo rýchlosti

7Chyba regulácie
8Chyba identifikácie
9Skrat výstupov
10Chyba snímača IRC (ARC), RM-ARC
11

Prerušenie vstupnej alebo výstupnej fázy meniča

12Externá porucha
13Teplota v meniči
14Prerušenie AIN1, AIN2 alebo AIN3
15

rezervované


Tab. č. 4 - register varovaní 1 (hodnoty bodu s adresou #0045). Ak je ľubovoľný bit nastavený na hodnotu 1, menič generuje príslušné varovanie

BitVýznam
0

niektoré z varovaní W1-W5:
W1 - Menič znižuje magnetický tok motora pre dosiahnutie nadsynchrónnych otáčok
W2 - Počas odbudzovania klesol magn. tok na minimálnu hodnotu
W3 - Regulátor magnetického toku je v nasýtení (len vo vektorovom režime)
W4 - Regulátor momentu motora je v nasýtení (len vo vektorovom režime)
W5 - Regulátor rýchlosti je v nasýtení (len vo vektorovom režime)

1W6 - Chladič meniča má zvýšenú teplotu (viac ako 75 °C).
Pri typoch VQFREM 400 005, 007 a 011 je teplota modulu vyššia ako 90 °C
2W7 - Menič sa prepol do skalárneho režimu pri výpadku IRC,ARC
3W8 - Signalizácia opačného napojenia IRC alebo ARC
4F7 - Pred ďalším štartom ešte neuplynul čas potrebný pre odbudenie motora
5W12 - Procesný regulátor je v nasýtení; frekvencia meniča je na maximálnej hodnote
6

F9 - Prebieha kalibrácia polohy od povelu 9.4.3 alebo sa kalibruje IRC (ARC) snímač na synchrónnom motore

F10 -Prebieha hľadanie nulového impulzu IRC na synchrónnom motore po zapnutí meniča na sieť a povele ŠTART

7F11 - Rýchlosť bola znížená na nulu aktivovaním softvérového koncového spínača
8F8 - Prudký pokles rýchlosti aktivoval funkciu dynamický dobeh
9W16 - Snímaná teplota v motore dosiahla nepovolenú hodnotu
10W17 - Ak je EOPN panel aktívny (2.4.1), a prerušilo sa spojenie s meničom
11

F2 - Aktivuje sa regulátor max. prúdu (par.13.3.1) a obmedzuje prúd na hodnotu par. 9.10.1

12F3 - Menič je v režime kinetického zálohovania po výpadku elektrickej energie
13F4 - Prebieha nafázovanie meniča na roztočený motor
14F5 - Prebieha parkovanie procesného regulátora
15

F6 - Brzdný modul je aktívny

Tab. č. 5 - register varovaní 2 (hodnoty bodu s adresou #0044). Ak je ľubovoľný bit nastavený na hodnotu 1, menič generuje príslušné varovanie

BitVýznam
0W23 - Pri povele ŠTART menič zistil neprítomnosť záťaže na výstupných svorkách U,V,W
1F12 - Je zopnutý koncový spínač 1 alebo koncový spínač 2
2F13 - Funkcia „brzdenie tokom“ zvyšuje budenie motora úmerne rozdielu UDC-UDCnom
3W9 - Prerušenie vstupnej fázy meniča
4rezervované
5F14 - Prebieha OFF-LINE identifikácia niektorého z parametrov motora (Rs, Ls+Lm, Upoč)
6

W25 - Teplota vzduchu v meniči je vyššia ako 70 °C

7rezervované
8W18 - Nastala chyba pri komunikácii po sériovej linke RS232 ( RS485)
9F16 - Signalizuje, že Relé s funkciou „vypne, preťaženie“ práve rozoplo


Literature


www.vonsch.sk - A web site of vector frequency converter manufacturer

Manuál for VQfrem 400 vector frequency converter

Changes and modifications


  • 21.1.2000 – Testing the communication

Document revisions


  • Ver. 1.0 – March 16, 2018 - the creation of a document