Note: Single bits of the byte, which informs us on quality (SIQ for ASDU 1,2,30; DIQ for ASDU 3,4,31; QDS for 5..14,20,32..36) are mapped into the FLA A (0.bit), FLB B (1.bit) .. FLH H (7.bit) flags except  except the bits that are directly set by the value of the variable ( SCO bit 0, DCO and RCS bits 0-1). After receiving the answer (a positive/negative one), the FLAA .. FLH H flags are  are set according to bits of "status" byte.

For example:
for ASDU 4: FLAA=DPI bit 0, FLBB=DPI bit 1, FLCC=0, FLDD=0, FLEE=BL bit, FLFF=SB bit, FLGG=NT bit, FLHH=IV bit.
for ASDU 16: FLAA .. FLE E Sequence number bits 0..4, FLFF=CY bit, FLGG=CA bit, FLHH=IV bit.

Moreover:

  • if a bit is set to IV (Invalid), the value state will be Invalid
  • if some of the bits are set to NT (Not topical), SB (Substituted), BL (Blocked), OV (Overflow), CA (Counter adjusted), CY (Counter overflow) for corresponding ASDU types, the value state will be Weak.

...

Kotva
pozn1
pozn1
* - T-bit of the value of these ASDU types is in the FI I flag, a number within -64 .. +63 is in a variable of Ci/Ai type.
Kotva
pozn2
pozn2
** - ASDU 17 and 38: SEP byte is in the flags FLA  A (0.bit), FLB B (1.bit) .. FLH H (7.bit), the following 2 bytes (CP16Time2a) are in a variable of Ci/Ai type as a positive number (0-60 000) or they are in a variable of TiR type as a relative time (0-60 seconds).

Kotva
pozn3
pozn3
*** - ASDU 18, 39 and 40: SPE(ASDU 18,39) byte respectively OCI (ASDU 40) byte is in the flags FLI  I (0.bit), FLJ J (1.bit) .. FLP P (7.bit), QDP byte is in the the flags FLA A (0.bit), FLB B (1.bit) .. .FLH H (7.bit), the following 2 bytes (CP16Time2a) are in a variable of Ci/Ai type as a positive number (0-60 000) or they are in a variable of TiR type as a relative time.

...

To set the bits of "status" byte (SCO for ASDU 45,58; DCO for ASDU 46,59; RCO for ASDU 47,60; QOS for ASDU 48..50,61..63), the flags FLA  A (0.bit), FLB B (1.bit) .. FLH H (7.bit) are used, except the bits, which are directly set by the variable value (SCO bit 0, DCO and RCS bits 0-1). Having received a response (positive/negative), the FLAA .. FLH H flags are  are set according to the bits of the "status" byte.

When sending commands (ASDU 45-64), the value of 6 [Activation] is sent as a CauseOfTransmission. The expected response from the controlled station depends on the Command Confirm parameter. There are the following possibilities:
- writing is successful if the packet with RSN confirming the SSN packet with the write command
- writing is finished, if there is a response with CauseOfTransmission=7 [Activation Confirmation] and/or with 10 [Activation Termination]. Success/failure depends on the setting of the P/N bit in CauseOfTransmission.

...

Note 3: Starting with D2000 version 7.02.004 if a TCP Redundant line category is used, the FLC C and FLD D flags are used in the value of communication stations for an indication of the functionality of primary (FLCC) and secondary (FLDD) communication path. If these flags are set, the respective communication path is non-functional. For example, if the value of the communication station is StON and FLC C flag is  is set it means that only the secondary communication path is functional.
For lower versions of D2000 only partial detection of a broken communication path is available when using the Strict Redundancy Connection Signalisation parameter.

...

Full nameMeaningUnitDefault value
Kotva
armp
armp
Asymmetric Redundancy Mode Periodicity
The parameter can be used for a TCP Redundant line with defined backup servers (see the parameters AS1, AP1, BS1, BP1 ..). The non-zero value of ARMP parameter means that if this number of ASDUs is received (after a successful reconnect), both connections are checked whether they're not going through the same network (IPs and ports defined in the line settings or ASx:APx and BSx:BPx). If they do, the connection to the standby server (see the Asymmetric Redundancy Mode Slave Detection parameter) will be closed and an attempt to establish a connection through another network will be made. If unsuccessful, the next IP address will be tried (i.e. Alternate Server 1, Alternate Server 2, line IP, Alternate Server 1, etc).
Note: When the parameter Asymmetric Redundancy Mode Periodicity is enabled, the second connection is established to "B-Alternate Server 1":"B-Alternate Port 1" and not to the IP address and port defined for the line after running the D2000 KOM process (so that it wouldn't be immediately closed).
-0
Kotva
armsd
armsd
Asymmetric Redundancy Mode Slave Detection
The detection method of standby server for Asymmetric Redundancy Mode Periodicity:
  • 0 - no detection: the first connection, that detects it is working via the same network, is to be disconnected
  • 1 - if ASDU contains the bit 0 of the 3rd Control Field byte set to 1
  • 2 - if ASDU in CauseOfTransmission contains the bit 7 set to 1
-0
Kotva
an
an
Alternate Server 1/
Alternate Port 1/
Alternate Server 2/
Alternate Port 2/
Extension for redundant systems: besides the IP address defined in the configuration of the Line, it is possible to define 2 alternative IP addresses. In case of a connection failure, the D2000 KOM process is attempting to connect to the next address in the list.
Note 1: All IP addresses and ports must be defined gradually for one station (i.e. at first "Alternate Server 1", "Alternate Port 1" and then "Alternate Server 2", "Alternate Port 2").
Note 2: These parameters are obsolete since it's possible to define several IP addresses in the configuration of the line (separated by comma or semicolon, e.g. 10.0.0.1;10.0.0.2).
--
Kotva
bn
bn
B-Alternate Server 1/
B-Alternate Port 1/
B-Alternate Server 2/
B-Alternate Port 2/
Can be used when the protocol IEC 870-5-104 is configured for a TCP redundant line. The meaning of the parameters is the same as for the primary connection, but they are valid for the backup connection.
Note 1: All IP addresses must be defined stepwise for one station (i.e. at first "Alternate Server 1", "Alternate Port 1" and then "Alternate Server 2", "Alternate Port 2").
Note 2: These parameters are obsolete since it's possible to define several IP addresses in the configuration of the line (separated by comma or semicolon, e.g. 10.0.0.1;10.0.0.2).
--
Kotva
cmdc
cmdc
Command Confirm
Confirmation of control ASDU.
If Command Confirm=0, the D2000 KOM process is not waiting for confirmation of control ASDU from the partner station using a reply ASDU with a different CauseOfTransmission. ASDU is considered to be confirmed when a packet containing the corresponding ReceiveSequenceNumber is received.
If Command Confirm=1, the D2000 KOM process is waiting for confirmation with CauseOfTransmission=7 (Activation Confirmation).
If Command Confirm=2, the D2000 KOM process is waiting for confirmation with CauseOfTransmission=10 (Activation Termination).
If Command Confirm=3, the D2000 KOM process waiting for confirmation with CauseOfTransmission=7 or 10 (if both of them are received, only the first of them is taken into account).
Having received corresponding confirmation means that writing is finished (the Transient attribute of written value is cleared and the "Wait Timeout Tn" timeout stops elapsing).
If a confirmation with a CauseOfTransmission different from the one the D2000 KOM process expects, is received, it will be ignored.
Writing is successful if the received ASDU contains the P/N bit set to 0. Otherwise, writing is unsuccessful.
Value from received ASDU is written back into a particular I/O tag and is sent to the system. E.g. if an ASDU of type 50 (short floating point) with the value of 1200.0 is sent and the partner station sends an ASDU of type 50 as a reply, P/N bit=0, the value of 999.0 (e.g. due to physical limitations of the given parameter) as a response, then the value will be sent to the D2000 system by the D2000 KOM process.
-1

Kotva
d2cls
d2cls
These parameters are intended for the configuration of a communication station for communication between two D2000 systems using ASDU 252 - D2000 Unival (Ipesoft's implementation). more ...

Kotva
dbgi
dbgi
Debug Input
A mask for debug levels of input data. The meaning of bits is as follows:
  • 0.bit - displays a number of incoming values during General Interrogation
  • 1.bit - displays all incoming values
  • 2.bit - balanced mode: requesting Interrogation command was received
-0
Kotva
dbgo
dbgo
Debug Output
A mask for debug levels of output data. The meaning of bits is as follows:
  • 0.bit - balanced mode: displays a number of outgoing values during General Interrogation
  • 1.bit - displays all outgoing values
-0
Kotva
eoi
eoi
End of initialization
Extension for ABB MicroScada: If End of initialization=1, having received ASDU 70 (End of initialisation) resends Interrogation Command and/or Counter Interrogation Command.-0
Kotva
fmt
fmt
Force Master Time
If Force Master Time=True, then the D2000 KOM process will accept ASDU 103 (Clock synchronisation command) with CauseOfTransmission=6 [Activation] or 3 [Spontaneous] from the server and it will save the time difference between the server's time and its time. If CauseOfTransmission=6, it replies with CauseOfTransmission=7 [Activation Confirmation].
Then the time of all values, which are received with timestamps, is decreased by this difference, i.e. a correction to the time of D2000 is made.
The parameter allows solving the problem when some values from the server are received with the timestamps and others without timestamps and times from D2000 and server differ. In this case, without parameter Force Master Time=True the values received without timestamps are tagged by D2000 time and the values with the timestamps are tagged by the server time. With parameter Force Master Time=True the time, sent by the server, is corrected to D2000 time using the time difference, which is computed from the received ASDU 103 (Clock synchronisation command).
-False
Kotva
fst
fst
Force Slave Time
Extension for ABB MicroScada: If Force Slave Time=True, then the D2000 KOM process will accept ASDU 103 (Clock synchronisation command) with CauseOfTransmission=6 [Activation] or 3 [Spontaneous] from the server and saves the time difference between server time and its time. If CauseOfTransmission=6, it replies with CauseOfTransmission=7 [Activation Confirmation].
Then all values, which are received with no timestamps, are to be marked by the current time plus time difference (if the station is not configured to use the communication computer time).
The Force Slave Time parameter allows solving the problem, that after receiving ASDU 100 or 101, the ABB MicroScada sends "interrogated" values without timestamps. However, during the communication, the values are sent with the timestamps - which may cause problems if the times of the MicroScada and the D2000 system are not synchronized.
-False
Kotva
icci
icci
GI Send New
If GI Send New=True, then the D2000 KOM process, after receiving the General Interrogation command, sends also values with more recent times than the time when the command was received. The value of the GI Send New parameter must be True to send values with future times as a reply to the General Interrogation command.-False
Kotva
icf3
icf3
Ignore Control Field 3 bit 0
Determines behavior, when ASDU contains Control Field with the lowest bit (0) of the 3rd-byte set to 1.
  • if Ignore Control Field 3 bit 0=False (default), ASDU content is to be processed
  • if Ignore Control Field 3 bit 0=True, ASDU content is to be ignored
The feature can be used when creating a redundant TCP connection (TCP Redundant line + IEC 870-5-104 protocol). The active server should send ASDU with the lowest bit of the 3rd Control Field byte set to 0, the passive server should send ASDU with the lowest bit of the 3rd Control Field byte set to 1.
-False
Kotva
iii
iii
Ignore Invalids on Interrogation
Balanced mode: if this parameter is set on a station, the D2000 KOM process will not send as a reply for ASDU 100 and 101 (Interrogation / Counter interrogation command) values of I/O tags which are Invalid or Unknown. The parameter can be used e.g. when controlling if sending Invalid values causes a breakdown of control.-False
Kotva
it
it
Ignore Tests
Determines behavior, when ASDU contains the highest 7th bit (Test) set in CauseOfTransmission.
  • if Ignore Tests=0 (default), ASDU content is to be processed
  • if Ignore Tests=1, ASDU content is to be ignored
  • if Ignore Tests=2, a Weak attribute is to be set
The feature can be used for creating a redundant TCP connection (TCP Redundant line + IEC 870-5-104 protocol). An active server should send ASDU with the Test bit=0, a passive server should send ASDU with the Test bit=1.
-0
Kotva
iua
iua
Ignore Unknown Addresses
If Ignore Unknown Addresses=TRUE, the D2000 KOM process will not show an error on its console or write it into log files in case that incoming value has the address not matching any of the addresses of I/O tags defined in the D2000 system.-False
Kotva
ii
ii
Implicit Interrogation
Balanced mode: After connecting to the IEC104 server, the D2000 KOM process sends the values of all variables without waiting for ASDU 100 or 101 [Interrogation/Counter Interrogation Command] requests.-False
Kotva
icci
icci
Interrogation Covers Counter Interrogation
Balanced mode: As a reply to Interrogation, also values of I/O tags configured as ASDU 15, 16, 37 (Integrated Totals) are sent. (They are normally requested by ASDU 101 [Counter Interrogation].)-False
Kotva
iwot
iwot
Interrogation WithOut Timestamps
If Interrogation WithOut Timestamps=True, then values sent as a response to ASDU 100 [Interrogation Command] in balanced mode will be sent as ASDUs without timestamps.
For example instead of ASDU 2 (Single-point information with time tag) or ASDU 30 (Single-point information with time tag CP56Time2a) ASDU 1 (Single-point information) will be sent.
This behavior is suitable in the situation when the values have been invalidated as a result of communication error and after the communication is reestablished the values come with old timestamps which causes problems in the archive (if the values change only rarely, calculated archives depending on them will be also invalid till a new value arrives). At the same time, this behavior is strictly according to the IEC standard, which says that the response to Interrogation should not use ASDUs with time stamps.
-False
Kotva
k
k
K
Sending window size i.e. number of I-frames sent by the D2000 KOM process without receiving a confirmation (S-frame or I-frame). According to the standard, the default value is 12.-12
Kotva
lh
lh
LFC History

The parameter may be used to read historical values for communication with LFC terminals or other devices that support ASDU 250 defined by Ipesoft.

Unlike the primary use of ASDU 250, the LFC terminal can only transmit one value for interval begin time, while the end time is ignored. The value will not be received as ASDU 251 but as one of the standard ASDU with a timestamp. Moreover, the values (with the same timestamp) of other tags may be received along with the value of the required tag. LFC terminal does not send ASDU 250 (with CauseOfTransmission=7, 10) as part of the response to ASDU 250 and the D2000 KOM process considers the reading done as soon as it gets the value of the required I/O tag. If the value is not received within the time defined by the Wait Timeout T1 parameter, the reading of historical value is considered unsuccessful, however, the connection to the LFC terminal is not closed.

If the values of other I/O tags are received along with the value of the required I/O tag, they must be received before the value of the required tag is received, otherwise, they are not considered as historical values (because reading is considered to be done after the value of required I/O tag is received).
Example: After the request for the values of I/O tags with the addresses of 1,2..16, the LFC terminal always sends the values of all the tags in the order of 1,2..16, therefore we must ask for the value of the I/O tag with the address of 16.

If the parameter is not defined or LFC History=0, reading of historical data is defined by Ipesoft (D2000 IEC104 Server partner is assumed).

If LFC History=1, then the value is considered to be historical (it will go to the archive but not to the I/O tag, etc.) if its timestamp belongs to the time interval specified by the GETOLDVAL action (and is received as ASDU 250).

If LFC History=2 then the behavior is as for LFC History=1 except if the timestamp of the received value is newer than the timestamp of the current value of the I/O tag, the received value will be sent into the D2000 Server process as a new one and not as a historical one.

Note: When reading historical data of the LFC terminal, the GETOLDVAL action may not contain the station name (the statIdent parameter) but the I/O tag name. If the action contains a station name, ASDU 250 will be sent for one I/O tag only.

-0
Kotva
mtd
mtd
Maximum Time Difference
Maximum acceptable time difference (in hours) between the time of received data and the time of the D2000 KOM process. If the partner station sends a value with a timestamp older or later than MDT hours, the value will be ignored and an error log will be written into the line's trace file. If the Maximum Time Difference parameter is a negative value (e.g. Maximum Time Difference=-5), its absolute value is used and the system alarm SystemError will be generated as well. If the parameter's value is zero, the time difference will not be checked.hrs0
Kotva
nf
nf
No Flags

If the parameter is True, then the status byte of incoming ASDUs is ignored and not saved into the

FA

A ..

.FH

H flags. Flags of output I/O tags are also ignored and they are not written to the status byte.

-False
Kotva
oic
oic
Order of IC
Order of sending ASDU 100 [Interrogation Command] during connection initialization. If Order of IC < Order of Counter IC, ASDU 100 will be sent before ASDU 101. If Order of IC=0, ASDU 100 will not be sent. The parameter can be set extra for each station.-1
Kotva
ocic
ocic
Order of Counter IC
Order of sending ASDU 101 [Counter Interrogation Command] during connection initialization. If Order of Counter IC < Order of IC, ASDU 101 will be sent before ASDU 100. If Order of Counter IC=0, ASDU 101 will not be sent. The parameter can be set extra for each station.-2
Kotva
pcnt
pcnt
Ping Count
The number of repetitions, after which the IP address not responding to the ping is considered non-functional.
See the Ping TimeOut parameter.
-3
Kotva
pto
pto
Ping TimeOut
If the parameter is non-zero, it defines the timeout (in milliseconds) of server response for ping (ICMP echo) packet. In the background, the D2000 KOM process sends ping packets to all defined IPs - Line IP address and Alternate Server 1, Alternate Server 2, B-Alternate Server 1, B-Alternate Server 2. If some of the addresses do not respond Ping Count-times, it is designated as non-functional. If the line is connected to this IP address, the connection is terminated. A new connection is established only to a functional IP address. If the parameter Ping TimeOut=0, sending the ping packet to IP addresses is disabled.ms0
Kotva
psd
psd
Post start delay
A delay between receiving StartDT Con response and sending Interrogation Command and/or Counter Interrogation Command in the initialization phase.ms0
Kotva
prd
prd
Pre Reconnect Delay
A delay before connecting or reconnecting (after starting the D2000 KOM process and after communication break-up).ms0
Kotva
ssn
ssn
Send sequence number
Initial The initial Send sequence number after the TCP connection is established. According to the standard, having established the connection the Send sequence number is set to 0, other than zero could be appropriate e.g. for testing.-0
Kotva
srmin
srmin
Smart Redundancy Minimum
The number of values that must be identical in the Smart Redundancy Minimum mode to consider the connections synchronized. The following parameters are taken into account:
  • I/O tag and station addresses
  • value
  • time
  • flags (FAA .. FHH)
-5
Kotva
srm
srm
Smart Redundancy Mode
Can be used for TCP Redundant line as an alternative to Ignore Tests=1 or Ignore Control Field 3 bit 0=1. The D2000 KOM process assumes that identical values go via the both connection of the TCP Redundant line in the same order. The D2000 KOM process is attempting to synchronize the connections. If a number of identical values defined by the Smart Redundancy Minimum parameter are received, data are synchronized. After synchronization is done, the value that comes earlier is taken into account, the same value via the other connection is ignored.
When the TCP connection is broken or two different values come, the synchronization is broken.
Compared to the detection of active/passive partner by means of "Ignore Tests"/"Ignore Control Field 3 bit 0", an advantage is that after communication failure with the active server, there is no data loss because the communication is still working with the passive partner and the D2000 KOM process is attempting to recover the connection with the active server.
Having recovered the connection (if the second connection is working), there are ignored the values which are acquired by the command General Interrogation.
-False
Kotva
sko
sko
Standby Keep Open
If True, after changing the status of the D2000 Server process (the D2000 KOM process is connected to) from Hot into Standby state (in a redundant system), connection with the IEC104 server will not be closed.-False
Kotva
sscf3
sscf3
Standby Set Control Field
If TRUE, after changing the status of the D2000 Server process (the D2000 KOM process is connected to) from Hot to Standby state (in a redundant system), the lowest bit of the 3rd Control Field byte of information APDUs (APDU containing data or commands) will be set to 1 instead of the standard value of 0. The behavior does not strictly follow the standard and we recommend using the Standby Set Test Bit parameter instead of this parameter if it is possible.-False
Kotva
sstb
sstb
Standby Set Test Bit
If True, the Cause Of Transmission will have a Test bit set if the D2000 KOM process is connected to the Standby server (in a redundant system) or is a passive instance.-False
Kotva
swv
swv
Standby Write Values
If True, after changing the status of the D2000 Server process (the D2000 KOM process is connected to) from Hot into Standby state (in a redundant system), the new values will be sent to the IEC104 server.-False
Kotva
st_ce
st_ce
Station Communication Error
The number of unsuccessful connection attempts after the communication failure after which the station status is changed to St_CommErr. For redundant lines, the communication must be either failed on both TCP connections or only a TCP connection to a passive server is established (see the parameters Ignore Control Field 3 bit 0 and Ignore Tests), i.e. data from such a server are ignored.-2
Kotva
st_he
st_he
Station Hard Error
The status of all stations on the line is changed into the St_HardErr state if the following conditions are met:
  • number of unsuccessful connection attempts reaches the value of Station Hard Error or higher,
  • an attempt to restore the communication lasts at least the time defined by the Time filter parameter (maximum value of all stations on the line is taken into account),
  • for redundant lines, the communication must be either failed for both TCP connections or only a TCP connection to a passive server is established (see the parameters Ignore Control Field 3 bit 0 and Ignore Tests), i.e. data from such a server are ignored.
-5
Kotva
stdci
stdci
Stop Data Confirm Ignored
Workaround for the MetsoDNA server error: after connecting to the IEC870-5-104 server from the Metso company, the server sends a StopDT Con U-frame (thereby confirming the end of sending data). If the Stop Data Confirm Ignored parameter is True, this frame will be ignored and the communication will continue. Without the Stop Data Confirm Ignored parameter set, the connection will be aborted.-False
Kotva
srcs
srcs
Strict Redundancy Connection Signalisation
Determines behavior, when the protocol is used for TCP Redundant line
  • if Strict Redundancy Connection Signalisation=False, the line is ok (TRUE), if at least 1 connection is working
  • if Strict Redundancy Connection Signalisation=True, the line is in error state (FALSE), if both connections are working
-False
Kotva
tki
tki
Tcp Keep Init
The parameter is implemented for use on OpenVMS platforms only. If it is other than zero, then defines the timeout (in seconds) for opening a new connection to the IEC104 server. For OpenVMS, the default value is 75 seconds, for Windows, it is 20 seconds. When the timeout expires, the connect procedure returns an error.-0
Kotva
tnd
tnd
Tcp No Delay
Setting Tcp No Delay parameter causes low-level socket option TCP_NODELAY being set, thus turning off the default packet coalesce feature.-False
Kotva
w
w
W
The number of received I-frames, after which the D2000 KOM process sends an S-frame confirmation. According to the standard, the default value is 8. The relation W < K must be true, the standard recommends W = 2/3 * K.-8
Kotva
wt1
wt1
Wait Timeout T1
Timeout for receiving the confirmation of a sent I-frame (either confirmation within the I-frame or the S-frame itself) or a U-frame. If the D2000 KOM process does not receive the confirmation within Wait Timeout T1 time, it closes the TCP connection. According to the standard, the Wait Timeout T1 default value is 15000 ms.ms15 000
Kotva
wt2
wt2
Wait Timeout T2
Timeout for sending the confirmation of a received I-frame. Wait Timeout T2 < Wait Timeout T1. If another I-frame (which confirms the received I-frame) is not sent within Wait Timeout T2 time since the I-frame was received, the D2000 KOM process sends an S-frame confirming the received I-frame to the partner. According to the standard, the Wait Timeout T2 default value is 10000 ms.ms10 000
Kotva
wt3
wt3
Wait Timeout T3
Timeout for sending test frames ( TEST ACT U-frame). If no data are sent in any direction for a long time, a TEST ACT U-frame will be sent after the expiration of the Wait Timeout T3 time by the D2000 KOM process, and a TEST CON U-frame is expected (within Wait Timeout T1 time after sending). If the Wait Timeout T3 on the partner side is set to a lower value, it sends the test frames, and the D2000 KOM process replies to them. According to the standard, the Wait Timeout T2 default value is 20000 ms.
Setting the value to 0 disables sending test frames.
ms20 000
Kotva
wtn
wtn
Wait Timeout No answer
Timeout for receiving the confirmation of a sent value. Receiving e.g. S-frame with RSN (Receive Sequence Number) confirming, that the other party received the previous I-frame doesn't mean, that the I-frame was processed. Within the Wait Timeout No answer time interval, the D2000 KOM process waits for receiving the response (e.g. after sending ASDU with TypeIdentificator=45 [Single Command] with CauseOfTransmission=6 [Activation], the receiving of Single Command with CauseOfTransmission=7 [Activation Confirmation] is expected.
After the expiration of the Wait Timeout Tn, the D2000 KOM process closes the TCP connection.
ms60 000

...