Forced sending of Interrogation Command and/or Counter Interrogation Command: If a station is in the simulation mode and the communication is not stopped for it (the Parameters tab of Station type object), the D2000 KOM process sends Interrogation Command and/or Counter Interrogation Command (see the parameters Order of IC, Order of Counter IC).

The D2000 system also supports the a balanced mode. In the mode, the task of controlled and control stations is changed. In this mode, the D2000 system receives commands and confirms them. The balanced mode may be used only when it is supported by the partner station. An advantage is that the D2000 system sends the current status of output I/O tags (defined as ASDU 1-40) as a reply to ASDU 100 [Interrogation Command] and 101 [Counter Interrogation Command] requests. It is still suitable to configure single-shot commands as ASDU 45 - 64; they are not repeated after re-establishing the connection.
As the protocol supports the balanced mode (partly it is a server), the rules of server protocols apply to it.
The output tags, which are configured as ASDU 1-40, do not go through the Transient status (i.e. they are considered as if in the configuration of I/O tag, Output control tab, the I/O tag output mode is set to Command). The writing is considered to be successful if there is the a connection with the server at the time of writing, otherwise, the writing is unsuccessful.

...

  • Communication line category: TCP/IP-TCP or TCP/IP-TCP Redundant.
  • TCP parameters - server parameters are mandatory:
    • Host: string containing at most 80 characters – server name in form of INET (name or numerical address a.b.c.d). In the case of redundant systems, multiple names/addresses separated by commas can be entered.
    • Port: TCP port number (0..65535)
    • Line number: is to be used as the Originator ASDU address (1 byte, 0-255)

...

Note 3: Starting with D2000 version 7.02.004 if a TCP Redundant line category is used, the FLC and FLD flags are used in the value of communication stations for an indication of the functionality of primary (FLC) and secondary (FLD) communication path. If these flags are set, the respective communication path is non-functional. For example, if the value of the communication station is StON and FLC flag is set it means that only the secondary communication path is functional.
For lower versions of D2000 only partial detection of a broken communication path is available when using the Strict Redundancy Connection Signalisation parameter.

...

Full nameMeaningUnitDefault value
Kotva
armp
armp
Asymmetric Redundancy Mode Periodicity
The parameter can be used for a TCP Redundant line with defined backup servers (see the parameters AS1, AP1, BS1, BP1 ..). The non-zero value of ARMP parameter means that if this number of ASDUs is received (after a successful reconnect), both connections are checked whether they're not going through the same network (IPs and ports defined in the line settings or ASx:APx and BSx:BPx). If they do, the connection to the standby server (see the Asymmetric Redundancy Mode Slave Detection parameter) will be closed and an attempt to establish a connection through another network will be made. If unsuccessful, the next IP address will be tried (i.e. Alternate Server 1, Alternate Server 2, line IP, Alternate Server 1, etc).
Note: When the parameter Asymmetric Redundancy Mode Periodicity is enabled, the second connection is established to "B-Alternate Server 1":"B-Alternate Port 1" and not to the IP address and port defined for the line after running the D2000 KOM process (so that it wouldn't be immediately closed).
-0
Kotva
armsd
armsd
Asymmetric Redundancy Mode Slave Detection
The detection method of standby server for Asymmetric Redundancy Mode Periodicity:
  • 0 - no detection: the first connection, that detects it is working via the same network, is to be disconnected
  • 1 - if ASDU contains the least significant bit of the 3rd Control Field byte set to 1
  • 2 - if ASDU in CauseOfTransmission contains a bit set to 8
-0
Kotva
an
an
Alternate Server 1/
Alternate Port 1/
Alternate Server 2/
Alternate Port 2/
Extension for redundant systems: besides the IP address defined in the configuration of the Line, it is possible to define 2 alternative IP addresses. In case of a connection failure, the D2000 KOM process is attempting to connect to the next address in the list.
Note 1: All IP addresses and ports must be defined gradually for one station (i.e. at first "Alternate Server 1", "Alternate Port 1" and then "Alternate Server 2", "Alternate Port 2").
Note 2: These parameters are obsolete since it's possible to define several IP addresses in the configuration of the line (separated by comma or semicolon, e.g. 10.0.0.1;10.0.0.2).
--
Kotva
bn
bn
B-Alternate Server 1/
B-Alternate Port 1/
B-Alternate Server 2/
B-Alternate Port 2/
Can be used when the protocol IEC 870-5-104 is configured for a TCP redundant line. The meaning of the parameters is the same as for the primary connection, but they are valid for the backup connection.
Note 1: All IP addresses must be defined stepwise for one station (i.e. at first "Alternate Server 1", "Alternate Port 1" and then "Alternate Server 2", "Alternate Port 2").
Note 2: These parameters are obsolete since it's possible to define several IP addresses in the configuration of the line (separated by comma or semicolon, e.g. 10.0.0.1;10.0.0.2).
--
Kotva
cmdc
cmdc
Command Confirm
Confirmation of control ASDU.
If Command Confirm=0, the D2000 KOM process is not waiting for confirmation of control ASDU from the partner station using a reply ASDU with a different CauseOfTransmission. ASDU is considered to be confirmed when a packet containing the corresponding ReceiveSequenceNumber is received.
If Command Confirm=1, the D2000 KOM process is waiting for confirmation with CauseOfTransmission=7 (Activation Confirmation).
If Command Confirm=2, the D2000 KOM process is waiting for confirmation with CauseOfTransmission=10 (Activation Termination).
If Command Confirm=3, the D2000 KOM process waiting for confirmation with CauseOfTransmission=7 or 10 (if both of them are received, only the first of them is taken into account).
Having received corresponding confirmation means that writing is finished (the Transient attribute of written value is cleared and the "Wait Timeout Tn" timeout stops elapsing).
If a confirmation with a CauseOfTransmission different from the one the D2000 KOM process expects, is received, it will be ignored.
Writing is successful if the received ASDU contains the P/N bit set to 0. Otherwise, writing is unsuccessful.
Value from received ASDU is written back into a particular I/O tag and is sent to the system. E.g. if an ASDU of type 50 (short floating point) with the value of 1200.0 is sent and the partner station sends an ASDU of type 50 as a reply, P/N bit=0, the value of 999.0 (e.g. due to physical limitations of the given parameter) as a response, then the value will be sent to the D2000 system by the D2000 KOM process.
-1

Kotva
d2cls
d2cls
These parameters are intended for the configuration of a communication station for communication between two D2000 systems using ASDU 252 - D2000 Unival (Ipesoft's implementation). more ...

Kotva
dbgi
dbgi
Debug Input
A mask for debug levels of input data. The meaning of bits is as follows:
  • 1.bit - displays a number of incoming values during General Interrogation
  • 2.bit - displays all incoming values
  • 3.bit - balanced mode: requesting Interrogation command was received
-0
Kotva
dbgo
dbgo
Debug Output
A mask for debug levels of output data. The meaning of bits is as follows:
  • 1.bit - balanced mode: displays a number of outgoing values during General Interrogation
  • 2.bit - displays all outgoing values
-0
Kotva
eoi
eoi
End of initialization
Extension for ABB MicroScada: If End of initialization=1, having received ASDU 70 (End of initialisation) resends Interrogation Command and/or Counter Interrogation Command.-0
Kotva
fmt
fmt
Force Master Time
If Force Master Time=True, then the D2000 KOM process will accept ASDU 103 (Clock synchronisation command) with CauseOfTransmission=6 [Activation] or 3 [Spontaneous] from the server and it will save the time difference between the server's time and its time. If CauseOfTransmission=6, it replies with CauseOfTransmission=7 [Activation Confirmation].
Then the time of all values, which are received with timestamps, is decreased by this difference, i.e. a correction to the time of D2000 is made.
The parameter allows solving the problem when some values from the server are received with the timestamps and others without timestamps and times from D2000 and server differ. In this case, without parameter Force Master Time=True the values received without timestamps are tagged by D2000 time and the values with the timestamps are tagged by the server time. With parameter Force Master Time=True the time, sent by the server, is corrected to D2000 time using the time difference, which is computed from the received ASDU 103 (Clock synchronisation command).
-False
Kotva
fst
fst
Force Slave Time
Extension for ABB MicroScada: If Force Slave Time=True, then the D2000 KOM process will accept ASDU 103 (Clock synchronisation command) with CauseOfTransmission=6 [Activation] or 3 [Spontaneous] from the server and saves the time difference between server time and its time. If CauseOfTransmission=6, it replies with CauseOfTransmission=7 [Activation Confirmation].
Then all values, which are received with no timestamps, are to be marked by the current time plus time difference (if the station is not configured to use the communication computer time).
The Force Slave Time parameter allows solving the problem, that after receiving ASDU 100 or 101, the ABB MicroScada sends "interrogated" values without timestamps. However, during the communication, the values are sent with the timestamps - which may cause problems if the times of the MicroScada and the D2000 system are not synchronized.
-False
Kotva
icci
icci
GI Send New
If GI Send New=True, then the D2000 KOM process, after receiving the General Interrogation command, sends also values with more recent times than the time when the command was received. The value of the GI Send New parameter must be True to send values with future times as a reply to the General Interrogation command.-False
Kotva
icf3
icf3
Ignore Control Field 3 bit 0
Determines behavior, when ASDU contains Control Field with the lowest bit (1) of the 3rd-byte set.
  • if Ignore Control Field 3 bit 0=False (default), ASDU content is to be processed
  • if Ignore Control Field 3 bit 0=True, ASDU content is to be ignored
The feature can be used when creating a redundant TCP connection (TCP Redundant line + IEC 870-5-104 protocol). The active server should send ASDU with the lowest bit of the 3rd Control Field byte set to 0, the passive server should send ASDU with the lowest bit of the 3rd Control Field byte set to 1.
-False
Kotva
iii
iii
Ignore Invalids on Interrogation
Balanced mode: if this parameter is set on a station, the D2000 KOM process will not send as a reply for ASDU 100 and 101 (Interrogation / Counter interrogation command) values of I/O tags which are Invalid or Unknown. The parameter can be used e.g. when controlling if sending Invalid values causes a breakdown of control.-False
Kotva
it
it
Ignore Tests
Determines behavior, when ASDU contains bit 8 (test) set in CauseOfTransmission.
  • if Ignore Tests=0 (default), ASDU content is to be processed
  • if Ignore Tests=1, ASDU content is to be ignored
  • if Ignore Tests=2, a Weak attribute is to be set
The feature can be used for creating a redundant TCP connection (TCP Redundant line + IEC 870-5-104 protocol). An active server should send ASDU with the Test bit=0, a passive server should send ASDU with the Test bit=1.
-0
Kotva
iua
iua
Ignore Unknown Addresses
If Ignore Unknown Addresses=TRUE, the D2000 KOM process will not show an error on its console or write it into log files in case that incoming value has the address not matching any of the addresses of I/O tags defined in the D2000 system.-False
Kotva
ii
ii
Implicit Interrogation
Balanced mode: After connecting to the IEC104 server, the D2000 KOM process sends the values of all variables without waiting for ASDU 100 or 101 [Interrogation/Counter Interrogation Command] requests.-False
Kotva
icci
icci
Interrogation Covers Counter Interrogation
Balanced mode: As a reply to Interrogation, also values of I/O tags configured as ASDU 15, 16, 37 (Integrated Totals) are sent. (They are normally requested by ASDU 101 [Counter Interrogation].)-False
Kotva
iwot
iwot
Interrogation WithOut Timestamps
If Interrogation WithOut Timestamps=True, then values sent as a response to ASDU 100 [Interrogation Command] in balanced mode will be sent as ASDUs without timestamps.
For example instead of ASDU 2 (Single-point information with time tag) or ASDU 30 (Single-point information with time tag CP56Time2a) ASDU 1 (Single-point information) will be sent.
This behavior is suitable in the situation when the values have been invalidated as a result of communication error and after the communication is reestablished the values come with old timestamps which causes problems in the archive (if the values change only rarely, calculated archives depending on them will be also invalid till a new value arrives). At the same time, this behavior is strictly according to the IEC standard, which says that the response to Interrogation should not use ASDUs with time stamps.
-False
Kotva
k
k
K
Sending window size i.e. number of I-frames sent by the D2000 KOM process without receiving a confirmation (S-frame or I-frame). According to the standard, the default value is 12.-12
Kotva
lh
lh
LFC History

The parameter may be used to read historical values for communication with LFC terminals or other devices that support ASDU 250 defined by Ipesoft.

Unlike the primary use of ASDU 250, the LFC terminal can only transmit one value for interval begin time, while the end time is ignored. The value will not be received as ASDU 251 but as one of the standard ASDU with a timestamp. Moreover, the values (with the same timestamp) of other tags may be received along with the value of the required tag. LFC terminal does not send ASDU 250 (with CauseOfTransmission=7, 10) as part of the response to ASDU 250 and the D2000 KOM process considers the reading done as soon as it gets the value of the required I/O tag. If the value is not received within the time defined by the Wait Timeout T1 parameter, the reading of historical value is considered unsuccessful, however, the connection to the LFC terminal is not closed.

If the values of other I/O tags are received along with the value of the required I/O tag, they must be received before the value of the required tag is received, otherwise, they are not considered as historical values (because reading is considered to be done after the value of required I/O tag is received).
Example: After the request for the values of I/O tags with the addresses of 1,2..16, the LFC terminal always sends the values of all the tags in the order of 1,2..16, therefore we must ask for the value of the I/O tag with the address of 16.

If the parameter is not defined or LFC History=0, reading of historical data is defined by Ipesoft (D2000 IEC104 Server partner is assumed).

If LFC History=1, then the value is considered to be historical (it will go to the archive but not to the I/O tag, etc.) if its timestamp belongs to the time interval specified by the GETOLDVAL action (and is received as ASDU 250).

If LFC History=2 then the behavior is as for LFC History=1 except if the timestamp of the received value is newer than the timestamp of the current value of the I/O tag, the received value will be sent into the D2000 Server process as a new one and not as a historical one.

Note: When reading historical data of the LFC terminal, thethe GETOLDVAL action may not contain the station name (thethe statIdent parameter) but the I/O tag name. If the action contains a station name, ASDU 250 will be sent for one I/O tag only.

-0
Kotva
mtd
mtd
Maximum Time Difference
Maximum acceptable time difference (in hours) between the time of received data and the time of the D2000 KOM process. If the partner station sends a value with a timestamp older or later than MDT hours, the value will be ignored and an error log will be written into the line's trace file. If the Maximum Time Difference parameter is a negative value (e.g. Maximum Time Difference=-5), its absolute value is used and the system alarm SystemError will be generated as well. If the parameter's value is zero, the time difference will not be checked.hrs0
Kotva
nf
nf
No Flags
If the parameter is True, then the status byte of incoming ASDUs is ignored and not saved into the FA...FH flags. Flags of output I/O tags are also ignored and they are not written to the status byte.-False
Kotva
oic
oic
Order of IC
Order of sending ASDU 100 [Interrogation Command] during connection initialization. If Order of IC < Order of Counter IC, ASDU 100 will be sent before ASDU 101. If Order of IC=0, ASDU 100 will not be sent. The parameter can be set extra for each station.-1
Kotva
ocic
ocic
Order of Counter IC
Order of sending ASDU 101 [Counter Interrogation Command] during connection initialization. If Order of Counter IC < Order of IC, ASDU 101 will be sent before ASDU 100. If Order of Counter IC=0, ASDU 101 will not be sent. The parameter can be set extra for each station.-2
Kotva
pcnt
pcnt
Ping Count
The number of repetitions, after which the IP address not responding to the ping is considered non-functional.
See the parameter the Ping TimeOut parameter.
-3
Kotva
pto
pto
Ping TimeOut
If the parameter is non-zero, it defines the timeout (in milliseconds) of server response for ping (ICMP echo) packet. In the background, the D2000 KOM process sends ping packets to all defined IPs - Line IP address and Alternate Server 1, Alternate Server 2, B-Alternate Server 1, B-Alternate Server 2. If some of the addresses do not respond Ping Count-times, it is designated as non-functional. If the line is connected to this IP address, the connection is terminated. A new connection is established only to a functional IP address. If the parameter Ping TimeOut=0, sending the ping packet to IP addresses is disabled.ms0
Kotva
psd
psd
Post start delay
A delay between receiving StartDT Con response and sending Interrogation Command and/or Counter Interrogation Command in the initialization phase.ms0
Kotva
prd
prd
Pre Reconnect Delay
A delay before connecting and or reconnecting (after starting the D2000 KOM process and after communication break-up).ms0
Kotva
ssn
ssn
Send sequence number
Initial Send sequence number after the TCP connection is established. According to the standard, having established the connection the Send sequence number is set to 0, other than zero could be appropriate e.g. for testing.-0
Kotva
srmin
srmin
Smart Redundancy Minimum
The number of values that must be identical in the Smart Redundancy Minimum mode to consider the connections synchronized. The following parameters are taken into account:
  • I/O tag and station addresses
  • value
  • time
  • flags (FA..FH)
-5
Kotva
srm
srm
Smart Redundancy Mode
Can be used for TCP Redundant line as an alternative to Ignore Tests=1 or Ignore Control Field 3 bit 0=1. The D2000 KOM process assumes that identical values go via the both connection of the TCP Redundant line in the same order. The D2000 KOM process is attempting to synchronize the connections. If the D2000 KOM process receives a number of identical values defined by the Smart Redundancy Minimum parameter are received, data are synchronized. After synchronization is done, the value that comes earlier is taken into account, the same value via the other connection is ignored.
When the TCP connection is broken or two different values come, the synchronization is broken.
Compared to the detection of active/passive partner by means of "Ignore Tests"/"Ignore Control Field 3 bit 0", an advantage is that after communication failure with the active server, there is no data loss because the communication is still working with the passive partner and the D2000 KOM process is attempting to recover the connection with the active server.
Having recovered the connection (if the second connection is working), there are ignored the values which are acquired by the command General Interrogation.
-False
Kotva
sko
sko
Standby Keep Open
If True, after changing the status of the D2000 Server process (the D2000 KOM process is connected to) from Hot into Standby state (in a redundant system), connection with the IEC104 server will not be closed.-False
Kotva
sscf3
sscf3
Standby Set Control Field
If TRUE, after changing the status of the D2000 Server process (the D2000 KOM process is connected to) from Hot to Standby state (in a redundant system), the lowest bit of the 3rd Control Field byte of information APDUs (APDU containing data or commands) will be set to 1 instead of the standard value of 0. The behavior does not strictly follow the standard and we recommend using the Standby Set Test Bit parameter instead of this parameter if it is possible.-False
Kotva
sstb
sstb
Standby Set Test Bit
If True, the Cause Of Transmission will have a Test bit set if the D2000 KOM process is connected to the Standby server (in a redundant system) or is a passive instance.-False
Kotva
swv
swv
Standby Write Values
If True, after changing the status of the D2000 Server process (the D2000 KOM process is connected to) from Hot into Standby state (in a redundant system), the new values will be sent to the IEC104 server.-False
Kotva
st_ce
st_ce
Station Communication Error
The number of unsuccessful connection attempts after the communication failure after which the station status is changed to St_CommErr. For redundant lines, the communication must be either failed on both TCP connections or only a TCP connection to a passive server is established (see the parameters Ignore Control Field 3 bit 0 and Ignore Tests), i.e. data from such a server are ignored.-2
Kotva
st_he
st_he
Station Hard Error
The status of all stations on the line is changed into the St_HardErr state if the following conditions are met:
  • number of unsuccessful connection attempts reaches the value of Station Hard Error or higher,
  • an attempt to restore the communication lasts at least the time defined by the Time filter parameter (maximum value of all stations on the line is taken into account),
  • for redundant lines, the communication must be either failed for both TCP connections or only a TCP connection to a passive server is established (see the parameters Ignore Control Field 3 bit 0 and Ignore Tests), i.e. data from such a server are ignored.
-5
Kotva
stdci
stdci
Stop Data Confirm Ignored
Workaround for the MetsoDNA server error: after connecting to the IEC870-5-104 server from the Metso company, the server sends a StopDT Con U-frame (thereby confirming the end of sending data). If the Stop Data Confirm Ignored parameter is True, this frame will be ignored and the communication will continue. Without the Stop Data Confirm Ignored parameter set, the connection will be aborted.-False
Kotva
srcs
srcs
Strict Redundancy Connection Signalisation
Determines behavior, when the protocol is used for TCP Redundant line
  • if Strict Redundancy Connection Signalisation=False, the line is ok (TRUE), if at least 1 connection is working
  • if Strict Redundancy Connection Signalisation=True, the line is in error state (FALSE), if both connections are working
-False
Kotva
tki
tki
Tcp Keep Init
The parameter is implemented for use on OpenVMS platforms only. If it is other than zero, then defines the timeout (in seconds) for opening a new connection to the IEC104 server. For OpenVMS, the default value is 75 seconds, for Windows, it is 20 seconds. When the timeout expires, the connect procedure returns an error.-0
Kotva
tnd
tnd
Tcp No Delay
Setting Tcp No Delay parameter causes low-level socket option TCP_NODELAY being set, thus turning off the default packet coalesce feature.-False
Kotva
w
w
W
The number of received I-frames, after which the D2000 KOM process sends an S-frame confirmation. According to the standard, the default value is 8. The relation W < K must be true, the standard recommends W = 2/3 * K.-8
Kotva
wt1
wt1
Wait Timeout T1
Timeout for receiving the confirmation of a sent I-frame (either confirmation within the I-frame or the S-frame itself) or a U-frame. If the D2000 KOM process does not receive the confirmation within Wait Timeout T1 time, it closes the TCP connection. According to the standard, the Wait Timeout T1 default value is 15000 ms.ms15 000
Kotva
wt2
wt2
Wait Timeout T2
Timeout for sending the confirmation of a received I-frame. Wait Timeout T2 < Wait Timeout T2. If another I-frame (which confirms the received I-frame) is not sent within Wait Timeout T2 time since the I-frame was received, the D2000 KOM process sends an S-frame confirming the received I-frame to the partner. According to the standard, the Wait Timeout T2 default value is 10000 ms.ms10 000
Kotva
wt3
wt3
Wait Timeout T3
Timeout for sending test frames ( TEST ACT U-frame). If no data are sent in any direction for a long time, a TEST ACT U-frame will be sent after the expiration of the Wait Timeout T3 time by the D2000 KOM process, and a TEST CON U-frame is expected (within Wait Timeout T1 time after sending). If the Wait Timeout T3 on the partner side is set to a lower value, it sends the test frames, and the D2000 KOM process replies to them. According to the standard, the Wait Timeout T2 default value is 20000 ms.
Setting the value to 0 disables sending test frames.
ms20 000
Kotva
wtn
wtn
Wait Timeout No answer
Timeout for receiving the confirmation of a sent value. Receiving e.g. S-frame with RSN (Receive Sequence Number) confirming, that the other party received the previous I-frame doesn't mean, that the I-frame was processed. Within the Wait Timeout Tn time interval, the D2000 KOM process waits for receiving the response (e.g. after sending ASDU with TypeIdentificator=45 [Single Command] with CauseOfTransmission=6 [Activation], the receiving of Single Command with CauseOfTransmission=7 [Activation Confirmation] is expected.
After the expiration of the Wait Timeout Tn, the D2000 KOM process closes the TCP connection.
ms60 000

...

Examples of configurations

...

Example 1: Client communicating with the server SrvA

...

on a redundant network.

Server settings

  • line: TCP/IP-TCP(Host ALL, port 2404)
  • protocol: IEC 870-5-104 Server
  • parameters: none

Client settings

  • line: TCP (Host IPA1, IPA2, port 2404)
  • protocol: IEC 870-5-104
  • parameters: none

If a communication segment drops out (e.g. IPA1 failure) the client establishes a connection with the server SrvA using the address IPA2.

...

The client communicates both with the hot server and with the standby active and passive server, connection with the standby passive server continues to be open, but new values are send sent by the hot active server only.
Note: If a symbolic name myName is used in the configuration of the IEC104 Server, it should be defined as IPA in the hosts file of the 1-st server and as IPA and IPB in the hosts file of the 2-nd server as IPB.


Example 3: Client communicating with the redundant servers SrvA, SrvB

...

on a redundant network.

Servers' settings

  • line: TCP/IP-TCP(Host ALL, port 2404)
  • protocol: IEC 870-5-104 Server
  • parameters: SKO=True; SWV=False;SSCF3=True;

Client settings

  • line: TCP/IP-TCP Redundant (Primary host IPA1, IPA2, Secondary host IPB1, IPB2, both ports 2404)
  • protocol: IEC 870-5-104
  • parameters: ICF3=True

The client communicates with both the servers. If one network segment drops out (e.g. IPA1 failure), the client establishes a connection with the SrvA server SrvA using the IPA2 address IPA2.


Example 4: The redundant clients ClientC, ClientD communicating with the redundant servers SrvA,

...

SrvB on a redundant network.

Servers' settings

  • line: TCP/IP-TCP(Host ALL, port 2404)
  • protocol: IEC 870-5-104 Server
  • parameters: SKO=True; SWV=False;SSCF3=True;

Clients' settings

  • line: TCP/IP-TCP Redundant (Primary host IPA1, IPA2, Secondary host IPB1, IPB2, both ports 2404)
  • protocol: IEC870-5-104
  • parameters: SKO=True; SWV=False;ICF3=True

The clients communicate with both the servers. If one network segment drops out (e.g. IPA1 failure), the clients establish a connection with the SrvA server SrvA using the IPA2 address IPA2. After switching the hotactive/standby passive statuses of the clients ClientC and ClientD clients, they keep communicating with the servers, but however, only the active client only sends commands. New values are sent by the active server.

...

  • I/O tag address is mapped on the Information object address, i.e. it has 3 bytes and must within the range of 0..16777215.
  • Input tags must be of particular types (Ai, Ci, Di, Qi) for received ASDU, see the see table 1 and also the table 2 in the balanced mode.
  • For a particular type of output tag (Ao, Dout, Co) it is necessary to set a an ASDU type, that has to be used, see the see table 2.
  • Archive for providing historical values: if the client asks for historical values through ASDU 250, the server sends:
    1. the values of the historical value specified by this input entry field,
    2. if the input entry field is not filled, then the values of the historical value that archives the I/O tag,
    3. if given the specified historical value does not exist, then the values of the I/O tag that archives the control object of given the specified I/O tag,
    4. if the control object does not exist (or the archive is not available), the server returns an error.
    Specification of a historical value allows user to set configuring e.g. sending 10-minutes averages instead of sending all changes of given I/O tag.

Kotva
literatura
literatura
Literature

...



Info
titleBlogs

You can read blogs about the IEC 870-5-104 protocol (for now, in Slovak language only): 


Kotva
revizie
revizie
Document revisions

...

  • Ver. 1.0 – July 30th, 2003
  • Ver. 1.1 – November 19th, 2003: extension of supported ASDU, new parameters
  • Ver. 1.2 – March 20th, 2004: added ASDU for reading archive data
  • Ver. 1.3 – June 20th, 2004: extension - redundancy support
  • Ver. 1.4 – December 1st, 2004: extension - support of balanced mode
  • Ver. 1.5 - December 12th, 2012 - updating, tell commands
Info
titleRelated pages:

Communication protocols

IEC 870-5-104 communication protocol

Supported device types and versions
Communication partners
Communication line configuration
Communication station configuration
Tell commands
I/O tag configuration
Literature
Document revisions

...

The protocol allows reading and writing data, operating on the basis of TCP network communication. Implementation is, according to the IEC870-5-104 standard, as follows:

  • Originator ASDU address is 1 byte, it is defined as the line number.
  • ASDU address is 2 bytes, it is defines as the station address. ASDU addresses of all stations on one line must be different.
  • Cause of transmission is 2 bytes (contains also Originator ASDU address).
  • Information object address is 3 bytes, it is defined as an I/O tag address.
  • The following ASDU types are implemented in the monitoring course (from controlled station to the D2000 system and also vice-versa in balanced mode):

...

Moreover:

  • if a bit is set to IV (Invalid), the value state will be Invalid
  • if some of the bits are set to NT (Not topical), SB (Substituted), BL (Blocked), OV (Overflow), CA (Counter adjusted), CY (Counter overflow) for corresponding ASDU types, the value state will be Weak.

...

The following ASDU types are implemented in the control course (from D2000 system to controlled station and also vice-versa in balanced mode):

...

  • TELL commands

...

  • 0 - the successful start of reading the history
  • 1 - the history for the required tag doesn't exist
  • 2 - the history for the required tag is not available (the archive does not run)

Further follows (is the return code was 00) ASDU 251 with archive data and the termination ASDU 250 with CauseOfTransmission=10.

Establishing a connection:

The D2000 KOM process is connecting to the specified TCP port and sends StartDT Act U-frame, StartDT Con is expected as a reply.

For all the stations with a defined synchronization (see the article below), ASDU type 103 [Clock synchronisation command] is sent with CauseOfTransmission=6 [Activation], and a reply is expected (depending on the Command Confirm parameter).

Then a sequence of 0 up to N I-frames with ASDU 100 [Interrogation Command] and ASDU 101 [Counter Interrogation Command] is sent, both with CauseOfTransmission=6 [Activation]. The I-frames are sent for each station with at least one input I/O tag (i.e. Ai, Di, Qi, Ci). An expected response is (in any order):

  • reception of frames with ASDU 100 [Interrogation Command] and with CauseOfTransmission=7 or 10 (depends on Command Confirm)
  • reception of frames with ASDU 101 [Counter Interrogation Command] and with CauseOfTransmission=7 or 10 (depends on Command Confirm)
  • reception of current values of all I/O tags.

The other party can also send frames with ASDU TypeIdentificator=100 and CauseOfTransmission=10 [Activation Termination], but the D2000 KOM process does not consider it to be an error if such frames are not received. The order of sending ASDU 100 and 101 as well as disabling their sending is defined by the Order of IC and Order of Counter IC parameters.

Clock synchronization: Sending ASDU type 103 [Clock synchronisation command] is performed during initialization (after sending StartDT and before sending Interrogation Command). The synchronization is sent for the stations, with the checked parameter Enable synchronization in the Time parameters tab. ASDU type 103 is sent regularly with a defined period.

Forced disconnection: If all stations on the line are in the simulation mode or the communication is stopped for them, the line will be disconnected (communication socket will be closed). If the simulation is disabled for at least one station and the communication is not stopped for it (the Parameters tab of Station type object), the line will be connected again (and Interrogation Command and/or Counter Interrogation Command will be sent to the active station). After enabling communication for further stations, Interrogation Command and/or Counter Interrogation Command will be sent to these stations - see the next paragraph.

Forced sending of Interrogation Command and/or Counter Interrogation Command: If a station is in the simulation mode and the communication is not stopped for it (the Parameters tab of Station type object), the D2000 KOM process sends Interrogation Command and/or Counter Interrogation Command (see the Order of IC and Order of Counter IC parameters).

The D2000 system also supports a balanced mode. In the mode, the task of controlled and control stations is symmetrical. That means, the D2000 system receives commands and confirms them. The balanced mode may be used only when it is supported by the partner station. An advantage is that D2000 system sends the current values of output I/O tags (defined as ASDUs 1-40) as a reply to ASDU 100 [Interrogation Command] and 101 [Counter Interrogation Command] requests. It is still suitable to configure single-shot commands as ASDUs 45 - 64; they are not repeated after re-establishing the connection.
As the protocol supports the balanced mode (partly it is a server protocol), the rules of server protocols apply.
The output tags, which are configured as ASDUs 1-40, do not go through Transient status (i.e. they are considered as if in the configuration of I/O tag, Output control tab, the I/O tag output mode is set to Command). The writing is considered to be successful if a connection with the server is established at the time of writing, otherwise, the writing is unsuccessful.

...

  • ABB MicroScada. Note: The value of the parameter Maximum message length in the ABB MicroScada settings must be changed from 253 similar to 230 (+/- a few bytes). The default value of the parameter causes rewriting the communication buffer and it is expressed by sending a corrupted message.
  • PLC Bernecker & Rainer, protocol implementation: URAP-AUTOMATIZÁCIA s.r.o. (Ltd.)
  • LFC terminals of Slovenské Elektrárne, a.s. (Inc.), protocol implementation: Energodata/ABB
  • RS Unicon 4, UniControls

...

  • Communication line category: TCP/IP-TCP or TCP/IP-TCP Redundant.
  • TCP parameters - server parameters are mandatory:
    • Host: string containing at most 80 characters – server name in form of INET (name or numerical address a.b.c.d). In the case of redundant systems, multiple names/addresses separated by commas can be entered.
    • Port: TCP port number (0..65535)
    • Line number: is to be used as the Originator ASDU address (1 byte, 0-255)

...

  • Communication protocol: IEC870-TCP.
  • Station address a decimal number within the range of 0..65535, defines the ASDU address.

Note 1: After saving a station in process D2000 CNF, the process D2000 KOM automatically sends ASDU 100 and ASDU 101 (Interrogation and Counter Interrogation Commands) to this station, if enabled.

Note 2: The protocol supports sending long time stamps (CP56Time2a tag) in local time or UTC time with defined offset (see the parameter Use monotonic UTC time +).

Note 3: Starting with D2000 version 7.02.004 if a TCP Redundant line category is used, the FLC and FLD flags are used in the value of communication stations for the indication of the functionality of primary (FLC) and secondary (FLD) communication path. If these flags are set, the respective communication path is non-functional. For example, if the value of the communication station is StON and FLC flag is set, it means that only the secondary communication path is functional.
For lower versions of D2000, only partial detection of the broken communication path is available when using the Strict Redundancy Connection Signalisation parameter.

Station protocol parameters

Table 3

...

  • 0 - no detection: the first connection, that detects it is working via the same network, is to be disconnected
  • 1 - if ASDU contains the least significant bit of the 3rd Control Field byte set to 1
  • 2 - if ASDU in CauseOfTransmission contains a bit 8 set to 1

...

Confirmation of control ASDU.
If Command Confirm=0, the D2000 KOM process is not waiting for confirmation of control ASDU from the partner station using a return ASDU with a different CauseOfTransmission. ASDU is considered to be confirmed when a packet containing a corresponding ReceiveSequenceNumber is received.
If Command Confirm=1, the D2000 KOM process is waiting for confirmation with CauseOfTransmission=7 (Activation Confirmation).
If Command Confirm=2, the D2000 KOM process is waiting for confirmation with CauseOfTransmission=10 (Activation Termination).
If Command Confirm=3, the D2000 KOM process waiting for confirmation with CauseOfTransmission=7 or 10 (if both of them are received, only the first of them is taken into account).
Having received corresponding confirmation means that writing is finished (the Transient attribute of written value is evaluated and the "Wait Timeout Tn" timeout stops elapsing).
If there is received confirmation with a different CauseOfTransmission than the D2000 KOM process expects, it will be ignored.
Writing is successful if the received ASDU contains the P/N bit set to 0. Otherwise, writing is unsuccessful.
Value from received ASDU is written back into a particular I/O tag and is sent to the system. E.g. if an ASDU of type 50 (short floating point) with the value of 1200.0 is sent and the partner station sends an ASDU of type 50 as a reply, P/N bit=0, the value of 999.0 (e.g. due to physical limitations of the given parameter) as a response, then the value will be sent to the D2000 system by the D2000 KOM process.

...

  • 1.bit - displays a number of incoming values during General Interrogation
  • 2.bit - displays all incoming values
  • 3.bit - balanced mode: requesting Interrogation command was received

...

  • 1.bit - balanced mode: displays a number of outgoing values during General Interrogation
  • 2.bit - displays all outgoing values

...

  • if Ignore Control Field 3 bit 0=False (default), ASDU content is to be processed
  • if Ignore Control Field 3 bit 0=True, ASDU content is to be ignored

...

  • if Ignore Tests=0 (default), ASDU content is to be processed
  • if Ignore Tests=1, ASDU content is to be ignored
  • if Ignore Tests=2, weak attribute is to be set

...

If the parameter is True, then the process D2000 KOM sends ASDU 100 [Interrogation Command] resp. ASDU 101 [Counter Interrogation Command] during connection initialisation to a single station with ASDU address 0xFFFF (decimally 65535). 
Otherwise, it sends these ASDUs to all stations on the line that have input I/O tags and are not turned off. The order of ASDU 100 and ASDU 101 and whether they are sent at all depends on the "Order of IC" and "Order of Counter IC" parameters.

...

The parameter may be used to read archive values for communication with LFC terminals or other devices that support ASDU 250 defined by Ipesoft.

Unlike the primary use of ASDU 250, LFC terminal can only transmit one value for interval begin time, while the end time is ignored. The value is not to be received as ASDU 251 but as one of the standard ASDU with time stamp. What is more, the values (with the same time stamp) of other tags may be received along with the value of required tag. LFC terminal does not ASDU 250 (with CauseOfTransmission=7, 10) as part of the response and the process D2000 KOM treats the reading as done as soon as gets the value of the required IO/ tag. Reading archive values is considered as unsuccessful but connection to LFC terminal is not closed until the value is not received in the time defined by the parameter Wait Timeout T1.

If the values of other I/O tags are received along with the value of required I/O tag, they must be received before the value of required tag is received, otherwise they are not considered as archive values (because reading is consider to be done after the value of required I/O tag is done).
Example: After the request for the values of I/O tags with the addresses of 1,2..16, LFC terminal always sends the values of all the tags in the order of 1,2..16, therefore we must require for the value of the I/O tag with the address of 16.

If the parameter is not defined or LFC History=0, reading archive data are defined by Ipesoft (D2000 IEC104 Server partner is assumed).

If LFC History=1, then the value the time of which belongs into the time interval specified by the action GETOLDVAL (and transferred through ASDU 250) is considered to be historical one (it is to be stored in the archive and not I/O tag, etc.).

If LFC History=2 then see the description above for LFC History=1 except if the time of received value is later than the current value of the I/O tag, the received value is to be sent into the process D2000 Server as new one and not as historical one.

Note: When reading archive data of LFC terminal, the action GETOLDVAL may not contain station name (the parameter statIdent) but the I/O tag name. If the action contains a station name, ASDU 250 is to be sent for one I/O tag only.

...

  • I/O tag and station addresses
  • value
  • time
  • flags (FA..FH)

...

  • number of unsuccessful connection attempts reaches the value of ST_HE or higher,
  • an attempt to restore the communication lasts at least the time defined by the parameter Time filter (maximum value of all stations on line is taken into account),
  • for redundant lines, the communication must be either failed for both TCP connections or there is a working TCP connection only to a standby-server (see the parameters Ignore Control Field 3 bit 0 and Ignore Tests), i.e. the data from the server are ignored.

...

  • if Strict Redundancy Connection Signalisation=False, the line is in order (TRUE), if at least 1 connection is working
  • if Strict Redundancy Connection Signalisation=True, the line is in error state (FALSE), if both connections are working

...

Defined parameters, except for Order of IC, Order of Counter IC and Force Slave Time, are valid for the entire line - i.e. it is enough to define them for one station on the line.

...

Table 4

...

Examples of configurations

Example 1: Client communicating with the server SrvA on redundant networks.

Image Removed

Server settings

...

Client settings

  • line: TCP (Host IPA1,IPA2, port 2404)
  • protocol: IEC 870-5-104
  • parameters: none

If a communication segment drops out (e.g. IPA1 failure) the client establishes connection with the server SrvA using the address IPA2.

Example 2: Client communicating with the redundant servers SrvA, SrvB.

Image Removed

...

Servers' settings

  • line: TCP/IP-TCP (Host myName or ALL, port 2404)
  • protocol: IEC 870-5-104 Server
  • parameters: SKO=TRUE; SWV=False; SSCF3=True;

...

Client settings

  • line: TCP/IP-TCP Redundant (Primary host IPA, Secondary host IPB, both ports 2404)
  • protocol: IEC 870-5-104
  • parameters: SKO=True;ICF3=True;

The client communicates both with the hot server and with the standby server, connection with the standby server continues to be open, but new values are send by the hot server.
Note: If symbolic myName is used, it should be defined in hosts file of 1-st server as IPA and in hosts file of 2-nd server as IPB.

Example 3: Client communicating with the redundant servers SrvA, SrvB on redundant networks.

Image Removed

Servers' settings

...

Client settings

  • line: TCP/IP-TCP Redundant (Primary host IPA1,IPA2, Secondary host IPB1,IPB2, both ports 2404)
  • protocol: IEC 870-5-104
  • parameters: ICF3=True

The client communicates with both the servers. If one network segment drops out (e.g. IPA1 failure), the client establishes connection with the server SrvA using the address IPA2.

Example 4: The redundant clients ClientC, ClientD communicating with the redundant servers SrvA, SrvB on redundant networks.

Image Removed

Servers' settings

...

Clients' settings

  • line: TCP/IP-TCP Redundant (Primary host IPA1,IPA2, Secondary host IPB1,IPB2, both ports 2404)
  • protocol: IEC870-5-104
  • parameters: SKO=True; SWV=False;ICF3=True

The clients communicate with both the servers. If one network segment drops out (e.g. IPA1 failure), the clients establish connection with the server SrvA using the address IPA2. After switching the hot/standby statuses of the clients ClientC and ClientD, they keep communicating with the servers, but the active client only sends commands. New values are sent by the active server.

...

Possible I/O tag types: Ai, Ao, Ci, Co, Di, Dout, Qi

  • I/O tag address is mapped on Information object address, i.e. it has 3 bytes and must within the range of 0..16777215.
  • Input tags must be particular types (Ai, Ci, Di, Qi) for received ASDU, see the table 1 and also the table 2 in the balanced mode.
  • For particular type of output tag (Ao, Dout, Co) it is necessary to set a ASDU type, that has to be used, see the table 2.
  • Archive for providing historical values: if client asks for historical values through ASDU 250, the server sends:
    1. the values of the historical value specified by this input entry field,
    2. if the input entry field is not filled, then the values of the historical value that archives the I/O tag,
    3. if given historical value does not exist, then the values of the I/O tag that archives the control object of given I/O tag,
    4. if the control object does not exist (or the archive is not available), the server returns an error.
    Specification of a historical value allows user to set e.g. sending 10-minutes averages instead of sending all changes of given I/O tag.

Browse

For the I/O tags, it is possible to discover the list of objects, as long as the KOM process is running and communication with a station is established.
Clicking the Browse button opens the IEC870-5-104 Item Browser window and displays a list of objects that have been read so far. The object list is created dynamically as a result of received messages.

The list of objects is dynamic, i.e. when a new value arrives in the KOM process, it is updated. Filtering in individual columns is also supported, asterisks can be used in the mask (e.g. *Short*).

Double-clicking on a particular line will cause the Address parameter to be inserted into the configuration of I/O tag from which the IEC870-5-104 Item Browser window was opened.

The Refresh button clears the list of values in both the CNF and the KOM process.

The Value column contains the received value.

Image Removed

...

-

Info
titleBlogs

You can read blogs about  IEC 870-5-104 protocol (for now, in Slovak language only): 

...

  • Ver. 1.0 – July 30th, 2003
  • Ver. 1.1 – November 19th, 2003: extension of supported ASDU, new parameters
  • Ver. 1.2 – March 20th 2004: added ASDU for reading archive data
  • Ver. 1.3 – June 20th, 2004: extension - redundancy support
  • Ver. 1.4 – December 1st, 2004: extension - support of balanced mode
  • Ver. 1.5 - December 12th, 2012 - updating, tell commands
  • Ver. 1.6 – June 15th, 2020: browsing support