Porovnávané verzie

Kľúč

  • Tento riadok sa pridal
  • Riadok je odstránený.
  • Formátovanie sa zmenilo.

...

ASDU typeI/O tag type
1 - Single-point informationDi, Qi (On/Off), Ai, Ci
2 - Single-point information with time tagDi, Qi (On/Off), Ai, Ci
3 - Double-point informationQi, Ai, Ci
4 - Double-point information with time tagQi, Ai, Ci
5 - Step position informationCi, Ai *
6 - Step position information with time tagCi, Ai *
7 - Bitstring of 32 bitsCi, Ai
8 - Bitstring of 32 bits with time tagCi, Ai
9 - Measured value, normalized valueAi
10 - Measured value, normalized value with time tagAi
11 - Measured value, scaled valueCi, Ai
12 - Measured value, scaled value with time tagCi, Ai
13 - Measured value, short floating-point valueAi
14 - Measured value, short floating-point value with time tagAi
15 - Integrated totalsCi, Ai
16 - Integrated totals with time tagCi, Ai
17 - Event of protection equipment with time tagCi, Ai, TiR **
18 - Packed start events of protection equipment with time tagCi, Ai, TiR ***
20 - Packed single-point information with status change detectionCi, Ai
21 - Measured value, normalized value without quality descriptorAi
30 - Single-point information with time tag CP56Time2aDi, Qi (On/Off), Ai, Ci
31 - Double-point information with CP56Time2a tagQi, Ai, Ci
32 - Step position information with CP56Time2a tagCi, Ai *
33 - Bitstring of 32 bits with CP56Time2a tagCi, Ai
34 - Measured value, normalized value with CP56Time2a tagAi
35 - Measured value, scaled value with CP56Time2a tagCi, Ai
36 - Measured value, short floating-point value with time tag CP56Time2aAi
37 - Integrated totals with time tag CP56Time2aCi, Ai
38 - Event of protection equipment with time tag CP56Time2aCi, Ai, TiR **
39 - Packed start events of protection equipment with time tag CP56Time2aCi, Ai, TiR ***
40 - Packed output circuit information of protection equipment with time tag CP56Time2aCi, Ai, TiR ***
241 - 64-bit floating-point value (Ipesoft & URAP implementation)Ao
243 - 64-bit floating-point value with time tag CP56Time2a (Ipesoft & URAP implementation)Ao
251 - Archive data values (Ipesoft's implementation)none ****
252 - D2000 Unival (Ipesoft's implementation)all (except Qi)

Note: Single bites bits of the byte, which informs us on quality (SIQ for ASDU 1,2,30; DIQ for ASDU 3,4,31; QDS for 5..14,20,32..36) are mapped into the flags FLA (0.bit), FLB (1.bit) ..FLH (7.bit) flags except the bits that are directly set by the value of variable ( SCO bit 0, DCO and RCS bity bits 0-1). After receiving the answer (a positive/negative one), the flags FLA..FLH flags are set according to bits of "status" byte.

For example:
for ASDU 4: FLA=DPI bit 0, FLB=DPI bit 1, FLC=0, FLD=0, FLE=BL bit, FLF=SB bit, FLG=NT bit, FLH=IV bit.
for ASDU 16: FLA..FLE Sequence number bity 0..4, FLF=CY bit, FLG=CA bit, FLH=IV bit.

...

ASDU typeI/O tag type
45 - Single commandDout
46 - Double commandDout
47 - Regulating step commandDout
48 - Set point command, normalised valueAo
49 - Set point command, scaled valueCo
50 - Set point command, short floating-point valueAo
51 - Bitstring of 32 bitCo
58 - Single command with time tag CP56Time2aDout
59 - Double command with time tag CP56Time2aDout, Co
60 - Regulating step command with time tag CP56Time2aDout
61 - Set point command, normalised value with time tag CP56Time2aAo
62 - Set point command, scaled value with time tag CP56Time2aCo
63 - Set point command, short floating-point value with time tag CP56Time2aAo
64 - Bitstring of 32 bit with time tag CP56Time2aCo
250 - Archive data request command (Ipesoft's implementation)none ****
252 - D2000 Unival (Ipesoft's implementation)all

To set the bites bits of "status" byte (SCO for ASDU 45,58; DCO for ASDU 46,59; RCO for ASDU 47,60; QOS for ASDU 48..50,61..63), there are used the flags FLA (0.bit),FLB (1.bit) ..FLH (7.bit) are used, except the bitesbits, which are directly set by the variable value (SCO bit 0, DCO and RCS bites bits 0-1). Having received a response (positive/negative), the flags FLA..FLH are set according to the bites bits of the "status" byte.

When sending commands (ASDU 45-64), the value of 6 [Activation] is send sent as a CauseOfTransmission. Expecting a The expected response from the controlled station depends on the parameter the Command Confirm parameter. There are the following possibilities:
- writing is successful , if the packet with RSN confirming the SSN packet with the logwrite command
- writing is finished, if there is a response with CauseOfTransmission=7 [Activation Confirmation] and/or with 10 [Activation Termination]. Success/Unsuccess failure depends on the setting of the P/N bite in CauseOfTransmission.

Kotva
pozn4
pozn4
**** - ASDU 250 can be used for communication with Ipesoft 870-5-104 Server. The command will ask for historical values (within any specified interval) from the server, which get back will arrive as ASDU 251 (or newer ASDU 249 that use 64-bit values for improved precision, if the protocol parameter D2H64 is enabled on the server). The reading of the archive values can be executed by means of the TELL GETOLDVAL command GETOLDVAL with the parameter containing the name of the I/O tag or station (in this case, there are read the values of all I/O tag in successive stepsare read gradually, i.e. reading another of the next tag starts after termination the reading of currently read current tag is done).
Response for ASDU 250 is again ASDU 250 (with CauseOfTransmission=7) and with the return code:

  • 0 - the successful start of reading the history
  • 1 - the history for the required tag doesn't existsexist
  • 2 - the history for the required tag is not available (the archive does not run)

Further follows Next (is the return code was 00) the ASDU 251 with archive data will be sent and the termination ASDU 250 with CauseOfTransmission=10.

Establishing a connection:

process The D2000 KOM process is connecting to the TCP port and sends a StartDT Act U-frame StartDT Act, then a StartDT Con U-frame is waited expected as a reply.

For all the stations with a defined synchronization (see the article below), there is send an ASDU type 103 [Clock synchronisation command] with CauseOfTransmission=6 [Activation] is sent, there is expected and a reply in dependence (depending on the Command Confirm parameter) is expected.

Then there is sent a sequence of 0 up to N I-frames with ASDU 100 [Interrogation Command] and ASDU 101 [Counter Interrogation Command] is sent, both with CauseOfTransmission=6 [Activation]. The I-frames are sent for each station with at least one input I/O tag (i.e. Ai, Di, Qi, Ci). As a response, there is expected (in any order):

  • receiving reception of frames with ASDU 100 [Interrogation Command] and with CauseOfTransmission=7 or 10 (depends depending on the Command Confirm parameter)
  • receiving reception of frames with ASDU 101 [Counter Interrogation Command] and with CauseOfTransmission=7 or 10 (depends depending on the Command Confirm parameter)
  • receiving reception of current values of all I/O tags.


The other side can also sent send frames with ASDU TypeIdentificator=100 and CauseOfTransmission=10 [Activation Termination]. However, but the process D2000 KOM process does not consider it to be an error , if such no frames will not receive. are received. The order of sending ASDU 100 and 101 sending order as well as disabling their sending is defined by the parameters Order of IC and Order of Counter IC parameters.

Clock synchronisation: Sending ASDU type 103 [Clock synchronisation command] is performed during initialization (after sending StartDT and before sending Interrogation Command). The synchronization is sent for the stations, with the checked parameter Enable in the tab Enable parameter checked in the Time parameters tab. ASDU type 103 is sending sent regularly with a defined period.

Forced disconnection: If all stations on the line are in the simulation mode or the communication is stopped for them, the line will be disconnected (communication socket will be closed). If the simulation is disabled for at least one station and the communication is not stopped for it (the the Parameters tab Parameters of Station type object), the line will be connected again (and there will be sent Interrogation Command and/or Counter Interrogation Command will be sent to the active station). After turning on every next stationenabling communication for further stations, Interrogation Command and/or Counter Interrogation Command will be sent to the stationthese stations, see the next articleparagraph.

Forced sending of Interrogation Command and/or Counter Interrogation Command: If a station is in the simulation mode and the communication is not stopped for it (the the Parameters tab Parameters of Station type object), the process D2000 KOM process sends Interrogation Command and/or Counter Interrogation Command (see the parameters Order of IC, Order of Counter IC).

D2000 system also supports the balanced mode. In the mode, the task of controlled and control stations is changed. That timeIn this mode, the D2000 system receives commands and confirms them. The balanced mode may be used only when it is supported by partner station. An advantage is that D2000 system sends the current status of output I/O tags (defined as ASDU 1-40) as a reply to ASDU 100 [Interrogation Command] and 101 [Counter Interrogation Command] requests. It is still suitable to configure single-shot commands as ASDU 45 - 64; they are not repeated after re-establishing the connection.
As the protocol supports the balanced mode (partly it is a server), there are valid the rules of server protocols apply to it.
The output tags, which are configured as ASDU 1-40, do not switched to go through the Transient status (i.e. they are considered as if in the configuration of I/O tag, tab Output controlcontrol tab, the I/O tag output mode is set on to Command). The record writing is considered to be successful if there is the connection with server at the time of recordwriting, otherwise the record writing is unsuccessful.

Kotva
referencie
referencie
Communication partners

...

  • Communication line category: TCP/IP-TCP or TCP/IP-TCP Redundant.
  • TCP parameters - server parameters are mandatory:
    • Host: string containing at most 80 characters – server name in form of INET (name or numerical address a.b.c.d). In case of redundant systems, multiple names/addresses separated by commas can be entered.
    • Port: TCP port number (0..65535)
    • Line number: is to be used as the Originator ASDU address (1 byte, 0-255)

...

  • Communication protocol: IEC870-TCP.
  • Station address a decimal number within the range of 0..65535 , defines the ASDU address.

...

Note 3: Starting with D2000 version 7.02.004 if a TCP Redundant line category is used, the flags FLC and FLD flags are used in the value of communication stations for indication of functionality of primary (FLC) and secondary (FLD) communication path. If these flags are set, the respective communication path is non-functional. For example, if the value of communication station is StON and FLC flag FLC is set it means that only secondary communication path is functional.
For lower versions of D2000 only partial detection of a broken communication path is available when using the parameter the Strict Redundancy Connection Signalisation parameter.

The Browse button opens a browsing dialog dialogue for the station address. If the communication is functional, a dialog dialogue with the ASDU addresses received so far is displayed. The Refresh button can be used to clear the list of received ASDU addresses.

...

Full nameMeaningUnitDefault value
Kotva
armp
armp
Asymetric Asymmetric Redundancy Mode Periodicity
The parameter can be used for a TCP Redundant line with defined backup servers (see the parameters AS1, AP1, BS1, BP1 ..). Non-zero value of ARMP parameter means that if this number of ASDUs is received (after a successful reconnect), both connection are checked whether they're not going through the same network (IP a ports defined in the line settings or ASx:APx and BSx:BPx). If they do, the connection to the standby server (see the parameter Asymetric Asymmetric Redundancy Mode Slave Detection) will be closed and an attempt to establish a connection through another network will be made. If unsuccessful, the following IP address will be tried (i.e. Alternate Server 1, Alternate Server 2, line IP, Alternate Server 1 etc).
Note: When the parameter Asymetric Asymmetric Redundancy Mode Periodicity is enabled, the second connection is established to "B-Alternate Server 1" : "B-Alternate Port 1" and not to the IP address and port defined for the line after running the process D2000 KOM (so that it wouldn't be immediately closed).
-0
Kotva
armsd
armsd
Asymetric Asymmetric Redundancy Mode Slave Detection
Detection The detection method of standby server for Asymetric Asymmetric Redundancy Mode Periodicity:
  • 0 - no detection: the first connection, that detects it is working via the same network, is to be disconnected
  • 1 - if ASDU contains the least significant bit of the 3rd Control Field byte set to 1
  • 2 - if ASDU in CauseOfTransmission contains a bit set to 8
-0
Kotva
an
an
Alternate Server 1/
Alternate Port 1/
Alternate Server 2/
Alternate Port 2/
Extension for redundant systems: beside besides the IP address defined in the configuration of the Line, it is possible to define 2 alternative IP addresses. In case of a connection failure, the process D2000 KOM process is attempting to connect to the next address in the list.
Note 1: All IP addresses and ports must be defined stepwise gradually for one station (i.e. at first "Alternate Server 1", "Alternate Port 1" and then "Alternate Server 2", "Alternate Port 2").
Note 2: These parameters are obsolete , since it's possible to define several IP addresses in the configuration of the line (separated by comma or semicolon, e.g. 10.0.0.1;10.0.0.2).
--
Kotva
bn
bn
B-Alternate Server 1/
B-Alternate Port 1/
B-Alternate Server 2/
B-Alternate Port 2/
Can be used when the protocol IEC 870-5-104 is configured for a TCP redundant line. The meaning of the parameters is the same as for primary connection, but they are valid for the backup connection.
Note 1: All IP addresses must be defined stepwise for one station (i.e. at first "Alternate Server 1", "Alternate Port 1" and then "Alternate Server 2", "Alternate Port 2").
Note 2: These parameters are obsolete , since it's possible to define several IP addresses in the configuration of the line (separated by comma or semicolon, e.g. 10.0.0.1;10.0.0.2).
--
Kotva
cmdc
cmdc
Command Confirm
Confirmation of control ASDU.
If Command Confirm=0, the process D2000 KOM process is not waiting for confirmation of control ASDU from the partner station using backward sending a reply ASDU with other a different CauseOfTransmission, . ASDU is consider considered to be confirmed , when there is received a packet containing the corresponding ReceiveSequenceNumber is received.
If Command Confirm=1, the process D2000 KOM process is waiting for confirmation with CauseOfTransmission=7 (Activation Confirmation).
If Command Confirm=2, the process D2000 KOM process is waiting for confirmation with CauseOfTransmission=10 (Activation Termination).
If Command Confirm=3, the process D2000 KOM process waiting for confirmation with CauseOfTransmission=7 or 10 (if both of them are received, only the first of them is taken into account).
Having received corresponding confirmation means that writing is finished (the Transient attribute of written value is evaluated cleared and the "Wait Timeout Tn" timeout stops elapsing).
If there is received a confirmation with other CauseOfTransmission, as the process a CauseOfTransmission different from the one the D2000 KOM process expects for, is received, it will be ignored.
Writing is successful , if the received ASDU contains the P/N bit set to 0. Otherwise, writing is unsuccessful.
Value from received ASDU is backwardly written back into a particular I/O tag and is sent to the system. E.g. if an ASDU of type 50 (short floating point) with the value of 1200.0 is sent and the partner station sends an ASDU of type 50 as a reply, P/N bit=0, the value of 999.0 (e.g. due to physical limitations of the given parameter) as a response, then the value is to be send by process D2000 KOM will be sent to the D2000 system by the D2000 KOM process.
-1

Kotva
d2cls
d2cls

The

These parameters are intended for the configuration of a communication station for communication between two D2000 systems

with

using ASDU 252 - D2000 Unival (Ipesoft's implementation). more ...

Kotva
dbgi
dbgi
Debug Input
A mask for debug levels of input data. The meaning of bits is as follows:
  • 1.bit - displays a number of incoming values during General Interrogation
  • 2.bit - displays all incoming values
  • 3.bit - balanced mode: requesting Interrogation command was received
-0
Kotva
dbgo
dbgo
Debug Output
A mask for debug levels of output data. The meaning of bits is as follows:
  • 1.bit - balanced mode: displays a number of outgoing values during General Interrogation
  • 2.bit - displays all outgoing values
-0
Kotva
eoi
eoi
End of initialization
Extension for ABB MicroScada: If End of initialization=1, having received ASDU 70 (End of initialisation) resends Interrogation Command and/or Counter Interrogation Command.-0
Kotva
fmt
fmt
Force Master Time
If Force Master Time=True, then the process D2000 KOM process will accept ASDU 103 (Clock synchronisation command) with CauseOfTransmission=6 [Activation] or 3 [Spontaneous] from the server and saves the time difference between the server's time and its time. If CauseOfTransmission=6, it replies with CauseOfTransmission=7 [Activation Confirmation].
Then time of all values, which are received with timestamps, is decreased by this difference, i.e. a correction to the time of D2000 is made.
The parameter allows to solve solving the problem when some values from the server are received with the timestamps and others without timestamps and times from D2000 and server differ. In this case, without parameter Force Master Time=True the values received without timestamps are specified tagged by D2000 time and the values with the timestamps are specified tagged by the server time. With parameter Force Master Time=True the time, sent by server, is corrected to D2000 time using the time difference, which is computed from the received ASDU 103 (Clock synchronisation command).
-False
Kotva
fst
fst
Force Slave Time
Extension for ABB MicroScada: If Force Slave Time=True, then the process D2000 KOM process will accept ASDU 103 (Clock synchronisation command) with CauseOfTransmission=6 [Activation] or 3 [Spontaneous] from the server and saves the time difference between server time and its time. If CauseOfTransmission=6, it replies with CauseOfTransmission=7 [Activation Confirmation].
Then all values, which are received with no timestamps, are to be marked by the current time plus time difference (if the station is not configured to use the communication computer time).
The parameter Force Slave Time allows to solve the problem, that having sent ASDU 100 or 101 there are sent ABB MicroScada values with no timestamps, but they are sent with the time stamps during the communication - problems can occur, when there are not synchronized the times of the MicroScada and the D2000 system.
-False
Kotva
icci
icci
GI Send New
If GI Send New=True, then the process D2000 KOM after receiving the command General Interrogation sends also values with more recent times than is the time when the command is received. The value of the parameter GI Send New must be True to send values with more recent times using the command General Interrogation.-False
Kotva
icf3
icf3
Ignore Control Field 3 bit 0
Determines behaviourbehavior, when ASDU contains Control Field with the lowest bit (1) of the 3rd-byte set.
  • if Ignore Control Field 3 bit 0=False (default), ASDU content is to be processed
  • if Ignore Control Field 3 bit 0=True, ASDU content is to be ignored
The feature can be used when creating a redundant TCP connection (TCP Redundant line + IEC 870-5-104 protocol). Hot The active server should send ASDU with the lowest bit of the 3rd Control Field byte set to 0, standby the passive server should send ASDU with the lowest bit of the 3rd Control Field byte set to 1.
-False
Kotva
iii
iii
Ignore Invalids on Interrogation
Balanced mode: if this parameter is set on a station, the process D2000 KOM will not send as a reply for ASDU 100 and 101 (Interrogation / Counter interrogation command) values of I/O tags which are Invalid or Unknown. Parameter can be used e.g. when controlling, if sending Invalid values causes breakdown of control.-False
Kotva
it
it
Ignore Tests
Determines behaviour, when ASDU contains bit 8 (test) set in CauseOfTransmission.
  • if Ignore Tests=0 (default), ASDU content is to be processed
  • if Ignore Tests=1, ASDU content is to be ignored
  • if Ignore Tests=2, weak attribute is to be set
The feature can be used for creating a redundant TCP connection (TCP Redundant line + IEC 870-5-104 protocol). Hot server should send ASDU with the Test bit=0, standby server should send ASDU with the Test bit=1.
-0
Kotva
iua
iua
Ignore Unknown Addresses
If Ignore Unknown Addresses=TRUE, the process D2000 KOM will not show an error on its console or write it into log files in case that incoming value has the address not matching any of the addresses of I/O tags defined in the D2000 system.-False
Kotva
ii
ii
Implicit Interrogation
Balanced mode: After connecting to the IEC104 server, the process D2000 KOM sends the values of all variables without waiting for ASDU 100 or 101 [Interrogation/Counter Interrogation Command] requests.-False
Kotva
icci
icci
Interrogation Covers Counter Interrogation
Balanced mode: As a reply to Interrogation, also values of I/O tags configured as ASDU 15, 16, 37 (Integrated Totals) are sent. (They are normally requested by ASDU 101 [Counter Interrogation].)-False
Kotva
iwot
iwot
Interrogation WithOut Timestamps
If Interrogation WithOut Timestamps=True, then values sent as a response to ASDU 100 [Interrogation Command] in balanced mode will be sent as ASDUs without timestamps.
For example instead of ASDU 2 (Single-point information with time tag) or ASDU 30 (Single-point information with time tag CP56Time2a) ASDU 1 (Single-point information) will be sent.
This behaviour is suitable in the situation when the values have been invalidated as a result of communication error and after the communication is reestablished the values come with old timestamps which causes problems in archive (if the values change only rarely, calculated archives depending on them will be also invalid till a new value arrives). At the same time, this behavior is strictly according to the IEC standard, which says that the response to Interrogation should not use ASDUs with time stamps.
-False
Kotva
k
k
K
Sending window size i.e. number of I-frames sent by the process D2000 KOM without receiving a confirmation (S-frame or I-frame). According to the standard, the default value is 12.-12
Kotva
lh
lh
LFC History

The parameter may be used to read archive values for communication with LFC terminals or other devices that support ASDU 250 defined by Ipesoft.

Unlike the primary use of ASDU 250, LFC terminal can only transmit one value for interval begin time, while the end time is ignored. The value is not to be received as ASDU 251 but as one of the standard ASDU with time stamp. What is more, the values (with the same time stamp) of other tags may be received along with the value of required tag. LFC terminal does not ASDU 250 (with CauseOfTransmission=7, 10) as part of the response and the process D2000 KOM treats the reading as done as soon as gets the value of the required IO/ tag. Reading archive values is considered as unsuccessful but connection to LFC terminal is not closed until the value is not received in the time defined by the parameter Wait Timeout T1.

If the values of other I/O tags are received along with the value of required I/O tag, they must be received before the value of required tag is received, otherwise they are not considered as archive values (because reading is consider to be done after the value of required I/O tag is done).
Example: After the request for the values of I/O tags with the addresses of 1,2..16, LFC terminal always sends the values of all the tags in the order of 1,2..16, therefore we must require for the value of the I/O tag with the address of 16.

If the parameter is not defined or LFC History=0, reading archive data are defined by Ipesoft (D2000 IEC104 Server partner is assumed).

If LFC History=1, then the value the time of which belongs into the time interval specified by the action GETOLDVAL (and transferred through ASDU 250) is considered to be historical one (it is to be stored in the archive and not I/O tag, etc.).

If LFC History=2 then see the description above for LFC History=1 except if the time of received value is later than the current value of the I/O tag, the received value is to be sent into the process D2000 Server as new one and not as historical one.

Note: When reading archive data of LFC terminal, the action GETOLDVAL may not contain station name (the parameter statIdent) but the I/O tag name. If the action contains a station name, ASDU 250 is to be sent for one I/O tag only.

-0
Kotva
mtd
mtd
Maximum Time Difference
Maximum acceptable time difference (in hours) between the time of received data and the time of process D2000 KOM. If partner station sends a value with a timestamp older or latter then MDT hours, the value is to be ignored and an error report is to be generated into the line's trace file. If the parameter Maximum Time Difference is a negative value (e.g. Maximum Time Difference=-5), there is used its absolute value and the system tag SystemError is generated as well. If the parameter's value is zero, the time difference is not to be checked.hrs0
Kotva
nf
nf
No Flags
If the parameter is True, then the status bit of incoming ASDUs is ignored and not saved into the flags FA...FH. Flags of output I/O tags are also ignored and they not set the status bit.-False
Kotva
oic
oic
Order of IC
Order of sending ASDU 100 [Interrogation Command] during connection initialization. If OIC<OCIC, ASDU 100 will be send before ASDU 101. If OIC=0, ASDU 100 will not be sent. The parameter can be set extra for each station.-1
Kotva
ocic
ocic
Order of Counter IC
Order of sending ASDU 101 [Counter Interrogation Command] during connection initialization. If Order of IC < Order of Counter IC, ASDU 101 will be sent before ASDU 100. If Order of IC=0, ASDU 101 will not be sent. The parameter can be set extra for each station.-2
Kotva
pcnt
pcnt
Ping Count
Number of repetitions, after which the IP address not responding to ping is known as non-functional.
See the parameter Ping TimeOut.
-3
Kotva
pto
pto
Ping TimeOut
If the parameter is other than zero, then defines the timeout (in milliseconds) of server response for ping (ICMP echo) packet. In the background, the process D2000 KOM sends ping packets to all defined IPs - Line IP address and Alternate Server 1, Alternate Server 2, B-Alternate Server 1, B-Alternate Server 2. If some of the addresses does not response for Ping Count-times, it is designated as non-functional. If the line is connected to this IP address, the connection is terminated. New connection is established just to a functional IP address. If the parameter Ping TimeOut=0, sending ping packet to IP addresses is disabled.ms0
Kotva
psd
psd
Post start delay
A delay between receiving StartDT Con response and sending Interrogation Command and/or Counter Interrogation Command in the initialisation phase.ms0
Kotva
prd
prd
Pre Reconnect Delay
A delay before connecting and reconnecting (after starting the process D2000 KOM and after communication break-up).ms0
Kotva
ssn
ssn
Send sequence number
Initial Send sequence number. According to the standard, having established the connection the Send sequence number is set to 0, other than zero could be appropriate e.g. for testing.-0
Kotva
srmin
srmin
Smart Redundancy Minimum
Number of values that must be identical in the Smart Redundancy Minimum mode to consider the connections synchronized. The following parameters are taken into account:
  • I/O tag and station addresses
  • value
  • time
  • flags (FA..FH)
-5
Kotva
srm
srm
Smart Redundancy Mode
Can be used for TCP Redundant line as alternative to Ignore Tests=1 or Ignore Control Field 3 bit 0=1. The process D2000 KOM assumes that the identical values go via the both connection of the TCP Redundant line in the same order. The process D2000 KOM is attempting to synchronize the connections. If the D2000 KOM process receives a number of identical values defined by the parameter Smart Redundancy Minimum, data are synchronized. After synchronisation is done, the value that comes earlier is taken into account, the same value via the other connection is ignored.
When the TCP connection is broken or two different values comes, the synchronisation is broken.
Compared to detection hot/standby partner by means of Ignore Tests/Ignore Control Field 3 bit 0, an advantage is that after communication failure with the hot server, there is no data loss, because the communication is still working with the standby partner and attempting to recover the connection with the hot server.
Having recovered the connection (if the second connection is working), there are ignored the values which are acquired by the command General Interrogation.
-False
Kotva
sko
sko
Standby Keep Open
If True, after changing the status of process D2000 Server (the process D2000 KOM is connected to) from Hot into Standby state (redundant system), connection with the server will not be closed.-False
Kotva
sscf3
sscf3
Standby Set Control Field
If TRUE, after changing the status of process D2000 Server (the process D2000 KOM is connected to) from Hot to Standby state (in the redundant system), the lowest bit of the 3rd Control Field byte of information APDUs (APDU containing data or commands) will be set to 1 instead of the standard value of 0. The behaviour does not strictly follow the standard and we recommend you to use the parameter Standby Set Test Bit instead of this parameter if it is possible.-False
Kotva
sstb
sstb
Standby Set Test Bit
If True, the Cause Of Transmission will have a Test bit set if the process D2000 KOM is connected to Standby server (redundant system) or is a passive instance.-False
Kotva
swv
swv
Standby Write Values
If True, after changing the status of process D2000 Server (the process D2000 KOM is connected to) from Hot into Standby state (redundant system), there will be sent new values.-False
Kotva
st_ce
st_ce
Station Communication Error
Number of unsuccessful connection attempts after the communication failure after which the station status is changed to St_CommErr. For redundant lines, the communication must be either failed on both TCP connections or only a TCP connection to standby-server must be established (see the parameters Ignore Control Field 3 bit 0 and Ignore Tests), i.e. data from the server are ignored.-2
Kotva
st_he
st_he
Station Hard Error
The status of all stations on line is changed into the state St_HardErr if the following conditions are met:
  • number of unsuccessful connection attempts reaches the value of ST_HE or higher,
  • an attempt to restore the communication lasts at least the time defined by the parameter Time filter (maximum value of all stations on line is taken into account),
  • for redundant lines, the communication must be either failed for both TCP connections or there is a working TCP connection only to a standby-server (see the parameters Ignore Control Field 3 bit 0 and Ignore Tests), i.e. the data from the server are ignored.
-5
Kotva
stdci
stdci
Stop Data Confirm Ignored
Workaround due to MetsoDNA server error: after connecting to IEC870-5-104 server from the firm Metso, the server sends a U-frame STOPDTcon (thereby confirms interruption in sending data). If the parameter Stop Data Confirm Ignored is True, this frame will be ignored and the communication will continue. Without the parameter Stop Data Confirm Ignored, the connection will be aborted.-False
Kotva
srcs
srcs
Strict Redundancy Connection Signalisation
Determines behaviour, when the protocol is used for TCP Redundant line
  • if Strict Redundancy Connection Signalisation=False, the line is in order (TRUE), if at least 1 connection is working
  • if Strict Redundancy Connection Signalisation=True, the line is in error state (FALSE), if both connections are working
-False
Kotva
tki
tki
Tcp Keep Init
The parameter is implemented for use on OpenVMS platforms only. If it is other than zero, then defines the timeout (in seconds) for opening a new connection to server. For OpenVMS, the default value is 75 seconds, for Windows it is 20 seconds. When timeout expires, connect procedure returns error.-0
Kotva
tnd
tnd
Tcp No Delay
Setting Tcp No Delay parameter causes low level socket option TCP_NODELAY being set, thus turning off default packet coalesce feature.-False
Kotva
w
w
W
Number of received I-frames, after which the process D2000 KOM sends a S-frame confirmation. According to the standard, the default value is 8. The relation W < K must be true, the standard recommends W = 2/3 * K.-8
Kotva
wt1
wt1
Wait Timeout T1
Timeout for receiving the confirmation of a sent I-frame (either confirmation within the I-frame or the S-frame itself) or a U-frame. If the process D2000 KOM does not get the confirmation in the time Wait Timeout T1, it closes the TCP connection. According to the standard, the Wait Timeout T1 default value is 15000 ms.ms15 000
Kotva
wt2
wt2
Wait Timeout T2
Timeout for sending the confirmation of a received I-frame. Wait Timeout T2 < Wait Timeout T2. If other I-frame (which confirms the received I-frame) is not sent in the time Wait Timeout T2 since the I-frame was received, so the process D2000 KOM sends a S-frame confirming the received I-frame to the partner. According to the standard, the Wait Timeout T2 default value is 10000 ms.ms10 000
Kotva
wt3
wt3
Wait Timeout T3
Timeout for sending test frames (U-frame TEST ACT). If no data are sent in any direction for a long time, an U-frame TEST ACT will be sent to the process D2000 KOM after expiration of the Wait Timeout T3 time and there is expected (in the Wait Timeout T1 time after sending) receiving a U-frame TEST CON. If the Wait Timeout T3 on the partner side is set to a lower value, it sends the test frames and the process D2000 KOM reply them. According to the standard, the Wait Timeout T2 default value is 20000 ms.
Setting the value to 0 disables sending test frames.
ms20 000
Kotva
wtn
wtn
Wait Timeout No answer
Timeout for receiving the confirmation of a sent value. Receiving e.g. S-frame with RSN (Receive Sequence Number) confirming, that the other party received previous I-frame doesn't mean, that the I-frame was processed. In the Wait Timeout Tn, the process D2000 KOM waits for receiving the response (e.g. after sending ASDU with TypeIdentificator=45 [Single Command] with CauseOfTransmission=6 [Activation] there is expected receiving Single Command with CauseOfTransmission=7 [Activation Confirmation].
After the expiration of the Wait Timeout Tn, the process D2000 KOM closes the TCP connection.
ms60 000

...