Note 2: The protocol supports sending long time stamps (CP56Time2a tag) in local time or UTC time with defined offset (see the parameter Use monotonic UTC time +).

The Browse button opens a browsing dialog for the station address. If the communication is functional, a dialog with the ASDU addresses received so far is displayed. The Refresh button can be used to clear the list of received ASDU addresses.

Image Added

Station protocol parameters

...

  • I/O tag address is mapped on Information object address, i.e. it has 3 bytes and must within the range of 0..16777215.
  • Input tags must be particular types (Ai, Ci, Di, Qi) for received ASDU, see the table 1.
  • For particular type of output tag (Ao, Dout, Co) it is necessary to set an ASDU type, that has to be used, see the table 2 and also the table 1 in the balanced mode.
  • Archive for providing old values: if client requires archive values using ASDU 250, the server sends:
    1. values of archived I/O tag, which are defined in this entry field
    2. if the entry field is not defined, values of archived I/O tag, that are directly archived by the I/O tag
    3. if the archived I/O tag does not exist, values of the I/O tag, that is archived by the control object of the I/O tag
    4. if the object doesn't exist (or the archive is not available), the server returns an error.
    Definition of an I/O tag allows e.g. to set sending 10-minute averages instead of sending all changes of the I/O tag.


Browse

For the I/O tags, it is possible to discover the list of objects, as long as the KOM process is running and communication with a station is established.
Clicking the Browse button opens the IEC870-TCPSRV Item Browser window and displays a list of objects that have been read so far. The object list is created dynamically as a result of received messages.

The list of objects is dynamic, i.e. when a new value arrives in the KOM process, it is updated. Filtering in individual columns is also supported, asterisks can be used in the mask (e.g. *Short*).

Double-clicking on a particular line will cause the Address parameter to be inserted into the configuration of I/O tag from which the IEC870-TCPSRV Item Browser window was opened.

The Refresh button clears the list of values in both the CNF and the KOM process.

The Value column contains the received value.

Image Added

Kotva
tell_cmd
tell_cmd
Tell commands

...