%EcoAve function


Old name
%EcoAveR


Function
The function returns the average of the specified object's values in an elapsed time period (given by the parameter ResetTrigger) according to the methodology based on flags of individual values entering the calculation. The result is a real value. An eval tag must be evaluated on a change (Evaluation method parameter set to On change value). Function evaluation time is rounded to a minute, i.e. seconds and milliseconds = 0.
Declaration
REAL %EcoAve(
   REAL in Arg, 
   REAL in ValidCriterion, 
   BOOL in ResetTrigger
 )
Parameters
ArgA parameter, average of which is to be calculated.
ValidCriterionValidation criterion value [%].
ImpulseChange of the parameter into the TRUE state causes evaluating the average, which is to be assigned to the eval tag value. At the same time, input values for the next period of time (Arg) are to be processed.
Note
Flag type Flag name

Meaning

Description for ESC Datalogger

CFAMeasurement invalidity<
BUnsteady operationF

VF

CCalibrationC
DMalfunctionB
EMaintenanceM
FPower supply failureP
GDisabled – disable (switching stopped)D
HMissing measurement
TFILayoffF
JStart
KPutting out of operation
LFuel change (unsteady process)
MDesulphurization failure
NReserve

IF

OReserve - fuel type - coal
PReserve

Types of flags for Automated measurement systems:

  • CF - complex flags (input attributes of value validity)
  • VF- validated flags (input attributes for measurement validity) - they condition A flag
  • TF- technological flags (input attributes of operation status) - they condition B flag
  • IF- informative flags

The value is valid if the A flag is not set, i.e. A=FALSE. The operation is stabilized if the B flag is not set, i.e. B=FALSE.

The following validation criteria are applied on CF flags of processed values:

  • Flag A  Resultant value of the flag is TRUE, if the sample count containing at least one of VF flags (with TRUE value), is bigger than 100 - ValidCriterion (%) of all measurements in a specified time period.
  • Flag B  Resultant value of the flag is TRUE, if the sample count containing at least one of TF flags (with TRUE value), is bigger than 100 - ValidCriterion (%) of all measurements in sa pecified time period.

Condition of flags processing:

  • Value with set at least one of VF flags is not included into average but a flag counter is added into it.
  • The processed values should have time with step of maximum 10 sec. If the value is missed during more than 10 seconds, the flag count „D“ - the counter for invalid measurements, is incremented.
  • If the resultant flag „A“ is TRUE, all flags that appeared in time period, are included in VF flags of calculated average.
  • If the resultant flag „A“ is FALSE, all VF flags are FALSE, even if some of them appeared in the processed data.
  • If the resultant flag „B“ is TRUE, all flags that appeared in time period, are included TF flags of calculated average.
  • If the resultant flag „B“ is FALSE, all TF flags are FALSE, even if some of them appeared in the processed data.