MODBUS Server communication protocol

Supported device types and versions
Communication line configuration
Communication station configuration
Line protocol parameters
I/O tag configuration
Literature
Changes and modifications
Document revisions

Supported device types and versions


The protocol executes a slaver communication with arbitrary devices that support standard MODBUS RTU in versions of serial communication and MODBUS over TCP/IP.

Communication line configuration


  • Line category: Serial (serial communication), SerialOverUDP Device Redundant (serial communication).
  • Line category TCP/IP-TCP (MODBUS over TCP/IP). Use a symbolic address ALL, KOM process listens on a selected TCP port on all existing network interfaces. TCP port 502 is commonly used, but any of the ports can be used.
    Line number - set the value for example 1.
    Note: KOM process works as a multitasking TCP server and that is why it is able to operate more clients at the same time.

Line protocol parameters


Configuration dialog box - table Parameters.
They influence some optional parameters of the protocol. Following line protocol parameters can be set:

Table 1

ParameterMeaningUnitDefault value
Silent Interval
Delay which is entered between the start of transmission of each data packet.ms50
No Request Timeout
If timeout passes and no valid request comes, all stations on the line will go to a communication error. However, the values of output I/O tags will not be invalidated (as this is a server protocol).mi:ss1:00
Single Server
If the value of the parameter is set on YES, the KOM process replies by error SLAVE_DEVICE_FAILURE to each request which is sent to a non-existent station (a station with unknown address). If the value is NO, the KOM process ignores this request and does not answer reply to it.YES/NOYES
Moxa Timeout
Switching time of Moxa redundant devices in case of communication error or some problems. As this is a server protocol which waits for requests from external devices, a failure to receive a communication request for longer time than the value of this parameter is considered to be an error. It is effective only for SerialOverUDP Device Redundant line.sec10 sec

Communication station configuration


  • Communication protocol "Modbus Server".
  • The station address is a decimal figure in the range of 1 up to 247. Address 0 is reserved for broadcast.

It is possible to configure more stations with different addresses on one line, KOM process will reply on behalf of every configured station. See also the line protocol parameters Single Server.

Station protocol parameters

Configuration dialog box - tab Parameter.
They influence some optional parameters of the protocol. Following station protocol parameters can be set:

Table 2

ParameterMeaningUnitDefault value
Addressing model
Sets an address model of MODBUS protocol:
MODBUS PDU
data are addressed from 0 up to 65535.
MODBUS data Model
data are addressed from 1 up to 65536.

Note:
MODBUS PDU is a default value. If the MODBUS data Model is set, the object with the address X is addressed as X-1 in MODBUS PDU.
After a change of this parameter, the KOM process must be restarted.
MODBUS PDU
MODBUS data Model
MODBUS PDU

I/O tag configuration


Possible value types: Ai, Ao, Di, Do, Ci, Co.

I/O tag address:

In the MODBUS protocol, the basic address space is divided into registers of Coils type (reading/writing), Discrete Inputs (reading), Holding Registers (reading/writing), and Input Registers (reading).

Every address space is independent, providing 2-byte addressing, i.e. addresses from 0 up to 65535.


Address format of I/O tag:
Address format is [I|U|L|Ll|S|Sl|f|F|C|D]Fn.Address[.BitNr] in which:

  • The first optional character defines the type of I/O tag:
    • I - Integer 16 bit
    • U - Unsigned 16 bit (default)
    • L - Unsigned long (4 bytes = 2 registers) - two registers with Address and Address+1 are read, unsigned and transmitted as big-endian (see Note)
    • Ll - Unsigned long (4 bytes = 2 registers) - two registers with Address and Address+1 are read and transmitted as little-endian, unsigned (see Note)
    • S - Signed long (4 bytes = 2 registers) - two registers with Address and Address+1 are read, signed and transmitted as big-endian (see Note)
    • Sl - Signed long (4 bytes = 2 registers) - two registers with Address and Address+1 are read and transmitted as little-endian, signed (see Note)
    • f - Float 32 bit (two registers) in big-endian format (bytes B4, B3, B2, B1 will be sent, B4 is highest byte and B1 is the lowest byte of float)
    • F - Float 32 bit (two registers) in little-endian format (bytes B2, B1, B4, B3 will be sent, B4 is highest byte and B1 is the lowest byte of float)
    • C - Request counter up (16 bit unsigned, which is incremented by every read request). Works only for Fn=3 or Fn=4
    • D - Request counter down (16 bit unsigned, which is decremented by every read request). Works only for Fn=3 or Fn=4
      Note: Request counter up/down can be used to configure a "watchdog" I/O tag to monitor the status and speed of Modbus communication.
  • Parameter Fn is a function of Modbus protocol for data reading, which inserts I/O tag into proper address space:
    • 1 - Coils: binary statuses
    • 2 - Discrete Inputs: binary inputs
    • 3 - Holding Registers: status registers
    • 4 - Input Registers: input registers
  • Parameter Address is a 2-bytes address of a register in the range of 0 up to 65535.
  • Parameter BitNr optionally specifies a bit of register in the range of 0 up to 15.

Implementation of protocol supports the following functions (commands of MODBUS Client for a D2000 KOM process):

  • 1 - Read Coils: reading of binary status - KOM process sends values of I/O tags of Do type.
  • 2 - Read Discrete Inputs: reading of binary inputs - KOM process sends values of I/O tags of Do type.
  • 3 - Read Holding Registers: reading of status registers - KOM process sends values of I/O tags of Co, Ao type (signed/unsigned).
  • 4 - Read Input Registers: reading of input registers - KOM process sends values of I/O tags of Co, Ao type (signed/unsigned).
  • 5 - Write Single Coil: writing of binary statuses - KOM process writes a received binary value in I/O tag of Di, Do type into system.
  • 15 - Write Multiple Coils - KOM process writes all received binary values of I/O tag of Di, Do type into system.
  • 6 - Write Single Register: writing of status registers - KOM process writes the received value in I/O tag of Ai, Ao, Ci, Co type into system.
  • 16 - Write Multiple registers: writing of multiple registers - KOM process writes all received values in I/O tags of Ai, Ao, Ci, Co type into system.

Note: This is a server type of protocol that is primarily intended for sending the values out of the D2000 system. Therefore the I/O tags should be configured as an output (Ao, Co, Do) because of the manipulation of their values directly or by control objects. If the I/O tag is configured as input (Ai, Ci, Di), the KOM process is unable to send a valid value in a reply to reading by functions 1 - 4 until the value is written by function 5, 15, 6 or 16 from outside.

If the KOM process does not have the valid value of I/O tag or request to read a nonexistent I/O tag is received, an implicit value False or 0 is sent as a response to a read request (MODBUS protocol does not support the transfer of value quality).

Literature



Blog


Changes and modifications


-

Document revisions


  • Ver. 1.0 - April 24th, 2009 - document creating
  • Ver. 1.1 - November 21st, 2010 - document update.
  • Ver. 1.2 - November 11th, 2011 - document update.
  • Ver. 1.3 - July 22th, 2019 - Implementation of signed/unsigned long values (L, Ll, S, Sl)

0 komentárov

Nie ste prihlásený. Akékoľvek zmeny, ktoré vykonáte, sa označia ako anonymné. Ak už máte svoj účet, pravdepodobne sa budete chcieť prihlásiť .