L&G ProfiBus communication protocol

Supported device types and versions 
Communication line configuration
Communication station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions

Supported device types and versions


The protocol LGPROFIBUS implements communication with Landis&Gyr devices on the basis of the ProfiBus communication protocol.

This communication supports (is verified) these Landis&Gyr devices:

Table 1

DeviceThe version of software on the deviceVersion of protocol
PRU10.64

Communication line configuration


The card KMFB02 (Incos a.s. Žilina) is used as a physical communication interface with the firmware by Ipesoft s.r.o. Žilina (stored in EPROM). The communication uses a baud rate of 93.75 kBd. Firmware in the card provides all basic tasks for access to the ProfiBus network. The card needs a KMFB02.SYS driver.

  • Communication line category: PROFIBUS
  • Line parameters (PROFIBUS tab):
    • Device ID – is ProfiBus Node Id, which is assigned to the KMFB02 card. It must be an unused number in the range of 0 up to 32 and reserved for the KMFB02 card in the ProfiBus network.

Communication station configuration


  • Communication protocol: L&G Profibus
  • The station address is ProfiBus Node Id of the device (PRU10) in the range of 0 up to 32.


Station protocol parameters

The parameters are configured in a dialog box – Communication station - configuration dialog box.

They influenced the behavior of the access to the communication medium. You can define the following parameters:

Table 2

KeywordFull nameMeaningUnitDefault value
WTWR_TIMEDelay before the message is sent.ms80
RTRD_TIMEDelay inserted into the executing of the transaction when the maximum count of transactions is exceeded.ms100
MTRMAX_TRANSACTION_NUMBERMaximum transactions that are unfinished.-5
MWRMAX_WR_RETRYMaximum retries during one record.-5
MTTMAX_TRANSACTION_TIMEMaximum waiting time for the response to end the transaction.sec6
MMTMAX_MESSAGE_TIMEMaximum time to complete at least one of unfinished transactions. After this timeout elapses, a communication error occurs in the station.sec10

The communication runs in the transaction way (Request/Response) for both data reading and writing. Data are read one point after another, always as a separate transaction.

A string containing the protocol parameters is being defined as follows:

Key_word=value;Key_word=value; ...

Example:

WT=90;RT=200;MTR=7;

If there is used a keyword with an invalid value in the initialization string, there will be used corresponding default value according to the table 1.

I/O tag configuration


I/O tags: Ai, Ao, Ci, Co, Di, Do, TiR, ToR, TxtI, TxtO

I/O tag types correspond to the following „Profibus_Type“:

Table 3

D2000 typeProfibus_Type
Ci, CoUnsigned16
Ai, AoFloatingPoint
TxtI, TxtOBit_String
TiR, ToRTimeDiff32, TimeDiff48
Di, DoUnsigned16

The address is a number in the range of 0 up to 65535.

Note:
You can use the RefGen software for easy configuration and servicing of the addresses of I/O tags when changing software in PLC. L&G utility „pointrep“ enables generating a „*.adr” file, which is an input for RefGen. RefGen uses the columns “ProfiBus_Type” (Table 3), “OV_Index” (the address) and “Access_Right” (input/output).

Literature


-

Changes and modifications


-

Document revisions


  • Ver. 1.1 – February 8, 2000 – Updating the document