Communication line of "RFC2217 Client" category

The "RFC2217 Client" communication line supports the communication with the converters of serial interfaces (device servers) according to RFC2217 (Telnet Com Port Control Option) standard. It supports a transfer of data and control commands (setting baud rate, number of bits, parity, etc.) over a single TCP connection.
Unlike the "SerialOverUDP Device Redundant" and "SerialOverUDP Line Redundant" lines, the transmission parameters may be set remotely, i.e. from the configuration of line in D2000 System. The line of "RFC2217 Client" category can be used on both Windows and Linux platforms.

Parameters


Configuration parameters of "RFC2217 Client" line.

Server IP/name

IP address (recommended) or DNS name of the target device (converter of serial interfaces). For redundant devices, multiple IP addresses or names separated by commas or semicolons can also be specified.

Port

The TCP port number (1-65535) on which the device is listening.

Line modes

Transmission parameters can be set for four modes, as when setting the "Serial" and "Serial Line Redundant" lines.
Parameter "ConstOpen" is ignored - TCP connection is established the first time it is used.


Related pages: