- Vytvoril D2000 Dev Team na okt 13, 2017
GETARCHARR action
GETARCHARR archIdent, locVarColValueIdent_Rec, [locVarColFlagsIdent_Rec], timeFromIdent_TmA, timeToIdent_TmA, stepIdent_Int, maxValsIdent_Int, statusIdent_Int[, archivInstance_Int]
archIdent | in | Reference to one value of historical value,
reference to object or
item identifier of Structured variable type object
(note: values of object or item must be archived). Warning: If the parameter is the reference to an object archived several times, there is not specified which one of the historical objects is to be used. |
locVarColValueIdent_Rec | out | Reference to column of a RECORD type local variable for result values |
locVarColFlagsIdent_Rec | out | Optional parameter. Reference to column of a RECORD type local variable for archive flags (Integer type). |
timeFromItemIdent_TmA | in | Identifier AbsTime type for the interval beginning. |
timeToItemIdent_TmA | in | Identifier of AbsTime type for the interval end. |
stepIdent | in | Identifier of Int type - time step for the oversampling of values in the archive. |
maxValsIdent_Int | in | Maximal number of values. If more values is in the required interval, they will be trimmed and the action returns the warning _ERR_MORE_DATA in the identifier statusIdent_Int. |
statusIdent_Int | out | Action success. |
archivInstance_Int | in | Optional identifier of Int type - identification of archive instance. If the parameter is not defined, the value 0 will replace it. |
timeFromIdent_TmA
to
timeToIdent_TmA
with the steps stepIdent_Int
(given in seconds). Maximal number of
values is given by the identifier maxValsIdent_Int
. See
reading the values.The parameter stepIdent_Int defines the oversampling (in seconds) of read values. If it is equal to 0, reading is not to be oversampled.
If the parameter archIdent is
the reference to an object of Historical
value type,
the action performance is described above. If the parameter is the reference
to an object (not of Historical value
type) or a structured variable item that is not of Object
type, the system is attempting to find an object of
Historical value type that archives
values of the object (item).
If the parameter archIdent is the
reference to a structured variable item that is of Object
type, the item "points" to an object in the system. If the object is of
Historical value type, the action will
read data from it. If it is not, the system is attempting to find an object
of Historical value type that archives
values of the object.
The return
code statusIdent_Int
can get one of the following values:
- _ERR_TRANS_ABORT
- _ERR_TRANS_ERROR
- _ERR_TRANS_IGNORED
- _ERR_NO_ERROR
- _ERR_NO_DATA - no data within given interval
- _ERR_MORE_DATA - more data than
maxValsIdent_Int
within given interval - _ERR_OBJECT_IS_NOT_IN_ARCHIVE
The error _ERR_MORE_DATA has only informative character and the required
number of data is available. If the value of the identifier stepIdent_Int
= 0, then values from the given interval are not be oversampled.
locVarColValueIdent_Rec
- is the reference to an
item of a RECORD type local variable.
The action, after successful reading of values, resizes the array
(internally the action REDIM) to the required
number of rows and in sequence (from 1...) assign a value from the archive
to the given item. Likewise locVarColFlagsIdent_Rec
-
is the reference to an item in a local variable of RECORD type. The
item must be Int type. Analogous to the previous parameter, the action
will resize the array (the sizes will be equal) and assign flags from the
archive to the given item in each row (see the action GETARCHVAL).
The parameter is optional and it can be omitted. An item for data from the archive and an item for archive flags may be
from the same local variable.
Value of parameter archivInstance_Int defines the instance of archive which executes the request. If the parameter is not defined (or the value is 0), the active instance of archive will execute the request.
SD.ArchDemo
of
Structure definition type, that contains the following items: Structure definition items
Item name | Item type |
Text | Text |
Value | Real number |
Flags | Integer |
Reading values from the archive. Values and archive flags are in two various arrays.
TIME _timeFrom TIME _timeTo INT _maxVals INT _step INT _status
RECORD (SD.ArchDemo) _locAValArr RECORD (SD.ArchDemo) _locAFlagsArr
_timeTo := %StrToTime("10:00:00 31-12-1999") _timeFrom := %StrToTime("09:00:00 31-12-1999") _maxVals := 100 _step := 0 GETARCHARR H.ArchObj, _locAValArr^Value, _locAFlagsArr ^Flags, _timeFrom, _timeTo, _step, _maxVals, _status
IF (_status = _ERR_NO_ERROR) | (_status = _ERR_MORE_DATA) THEN ; data are loaded ELSE ; an error occurred ENDIF
TIME _timeFrom TIME _timeTo INT _maxVals INT _step INT _status
RECORD (SD.ArchDemo) _locAValArr
_timeTo := %StrToTime("10:00:00 31-12-1999") _timeFrom := %StrToTime("09:00:00 31-12-1999") _maxVals := 100 _step := 0
GETARCHARR H.ArchObj, _locAValArr^Value, _locAValArr^Flags, _timeFrom, _timeTo, _step, _maxVals, _status
IF (_status = _ERR_NO_ERROR) | (_status = _ERR_MORE_DATA) THEN ; data are read ELSE ; an error occurred ENDIF
TIME _timeFrom TIME _timeTo INT _maxVals INT _step INT _status INT _row RECORD (SD.ArchDemo) _locAValArr _timeTo := %StrToTime("10:00:00 31-12-1999") _timeFrom := %StrToTime("09:00:00 31-12-1999") _maxVals := 100 _step := 0 _row := 4 ; row 4 GETARCHARR (H.StructArchObj\HBJ, _row, 5) _locAValArr^Value, _locAValArr^Value, _timeFrom, _timeTo, _step, _maxVals, _status IF (_status = _ERR_NO_ERROR) | (_status = _ERR_MORE_DATA) THEN ; data are read ELSE ; an error occurred ENDIF