- types S7-300 and S7-400 equipped by an ethernet interface for the communication S7 ISO over TCP.
- types S7-1200, S7-1500
- types Siemens LOGO
- Siemens Microbox
Note: communication via Profinet/Profibus adapter ACCON-NetLink-PRO compact produced by company DELTALOGIC has been verified. Communication with multiple S-300 series PLCs on Profibus worked after firmware upgrade of adapter to version V2.54 (31. march 2015) with adapter's BIOS version V2.39 (7. june June 2011). When the adapter's firmware was version V2.37 (8.august 2011), communication could not be correctly established.
Note: communication with PLC Siemens LOGO was tested. A part of memory that is accessible for readreading/write writing is the V area that is seen as DB1.
Note: the protocol has a "big endian" data representation.
Kotva |
---|
| komunikacna_linka |
---|
| komunikacna_linka |
---|
|
Communication line configuration
...
- Communication line category: TCP/IP-TCP, TCP Redundant.
- IP address (addresses) is set according to a network configuration of a specific device Siemens SIMATIC device.
- Port The port number is 102 (according to specification RFC 1006).
- Line The line number is not used, set on 1.
When the communication line is set as TCP Redundant you can configure an IP address and port of a backup device. If a communication process lost the connection or is unable to connect to the device, it will switch periodic periodically between the configured devices. KOM process tries to connect to a primary device at first.
...
Note: Multiple IP addresses of primary/backup device can also be configured (separated by commas or semicolons).
Kotva |
---|
| linka_parametre |
---|
| linka_parametre |
---|
|
Line protocol parameters...
A dialog window of
...
A dialog window of communication line configuration - Protocol parameters tab.
They influence some optional protocol parameters.
The following line protocol contains the following parameters are defined:
Parameter | Meaning | Unit / size | Default value |
---|
| Siemens Simatic rack number. Rack 0 is most often used. | 0 to 7 | 0 |
| Siemens Simatic slot number. Slot 2 is most often used. | 0 to 31 | 0 |
|
conresconres | Connection Resource Connection resource, it inputs as MSB byte to calculation of the value of Remote TSAP at initialization of ISO Connection-request.See description of S7 subnet address sent as a part of Remote TSAP if parameter Use long TSAP |
. 0xFF3ltsapltsap | Local TSAP ISO Local TSAP (Transport Service Local Point). Source TSAP value at initialization of ISO Connection-request.See description of S7 subnet address sent as a part of Remote TSAP if parameter Use long TSAP |
. is set to True | 0x0 to 0xFFFF |
0x1000srcrefsrcrefSource ReferenceISO Source Reference. Value of SRC-REF at connection of ISO Connection-request. | 0 to 65535 | 1 | Kotva |
---|
ult | ult | Use long TSAPEnables a long format of local and remote TSAP which is sent during connection setup phase. Short TSAP is 2 bytes long. Short local TSAP has following format:Short remote TSAP has following format:Long local TSAP is 28 bytes long. Last 2 bytes are higher and lower byte of parameter Local TSAP Full remote TSAP is 28 bytes long and it contains: | - | False | Kotva |
---|
mpiaddr | mpiaddr | MPI/Profibus AddressMPI/Profibus address sent as a part of Remote TSAP, if parameter Use long TSAP is set to True | 0 to 126 | 1 | Kotva |
---|
s7sub1 | s7sub1 | S7 Subnet ID-part 1 (hex)S7 subnet address sent as a part of Remote TSAP, if parameter Use long TSAP is set to True | 0x0 to 0xFFFF | 0 | Kotva |
---|
s7sub2 | s7sub2 | S7 Subnet ID-part 2 (hex)S7 subnet adresa sent as a part of Remote TSAP, if parameter Use long TSAP is set to True | 0x0 to 0xFFFF | 0 | Kotva |
---|
tpdus | tpdus | ISO TPDU Size Variable ParameterMaximum required size of ISO TPDU. The parameter value at initialization of ISO Connection-request. | 8192, 4096, 2048, 1024, 512, 256 or 128 bytes | 1024 bytes | Kotva |
---|
pnj | pnj | Nr. of Parallel Network ThreadsMaximum parallel communication threads. Increase value if there is a request on more data read from device in shorter time. | 1 to 4 | 1 | Kotva |
---|
ct | ct | Cycle TimeRequired time of one data reading cycle. | ms | 1000 ms | Kotva |
---|
wt | wt | Message TimeoutMaximal wait time on reply from other device. | ms | 2500 ms | Kotva |
---|
imd | imd | Inter Message DelayDelay which is used before sending a data request. When high data transfer rate is required, set 0 ms. | sec.ms | 20 ms | Kotva |
---|
rd | rd | Reconnect DelayDelay before reconnection to other device if the connection has failed or some communication error has occurred. | sec.ms | 2 sec | Kotva |
---|
cet | cet | Connection Error TimeoutWhen Timeout passes and communication error occurs in all threads, a communication error status is set on the stations. FALSE state is set on the communication line. | sec.ms | 20 sec | Kotva |
---|
pdu | pdu | S7 PDU SizeMaximum PDU in bytes at S7 communication with other device. | 240, 480, 960 bytes | 480 bytes | Kotva |
---|
tnd | tnd | Tcp No DelaySetting Tcp No Delay parameter causes low level socket option TCP_NODELAY being set, thus turning off default packet coalesce feature. | - | False | Kotva |
---|
nvd | nvd | Debug ValuesActivates a debug info about the loaded values of I/O tags. Use this parameter only when communication must be debug because it highly uses CPU and slows down the communication. | YES/NO | NO | Kotva |
---|
iopd | iopd | Debug I/O Binary Packets InfoActivates a debug info about a binary content of packets. Use this parameter only when communication must be debug because it highly uses CPU and slows down the communication. | YES/NO | NO | Kotva |
---|
rdd | rdd | Debug Requests InfoActivates a basic debug info about requested data. | YES/NO | YES | Kotva |
---|
rad | rad | Debug Answers InfoActivates a basic debug info about received packets. | YES/NO | YES | ...
| The parameter allows the use of redundant PLCs, which may differ in the settings of some parameters (Rack, Slot, S7 Subnet ID). If its value is True, the primary and secondary parameters are used alternately when connecting to the PLC using the specified IP addresses. | - | False |
Connection Resource (hex) | Connection resource, it enters as MSB byte to the calculation of the value of Remote TSAP at initialization of ISO Connection-request. See the description of parameter Use long TSAP. Note: in the specific case, when two systems (one of them D2000) needed to communicate with S7-300, they each had to have a different Connection resource, otherwise after sending the initial sequence of D2000 KOM process, the connection broke:/TSK1/Sending CR-TPDU: CLASS=0, SRC-REF=0x0001, TPDU size=1024, SRC-TSAP=10-00, DST-TSAP=03-02 /TSK1/OUT-<03><00><00><16><11><E0><00><00><00><01><00><C0><01><0A><C1><02><10><00><C2><02><03><02> recv error '10.94.11.237:102 (handle: 2888, objId: 2563271)' - WSA_ECONNRESET [ 10054] Task: L.N337-S7ExecTsk/TSK1/ After changing the Connection resource from 3 to 2, the communication started working. | 0x0 to 0xFF | 3 |
| ISO Local TSAP (Transport Service Local Point). Source TSAP value during the initialization of ISO Connection-request. See the description of parameter Use long TSAP. | 0x0 to 0xFFFF | 0x1000 |
| ISO Source Reference. Value of SRC-REF during the initialization of ISO Connection-request. | 0 to 65535 | 1 |
| Enables a long format of local and remote TSAP which is sent during the connection setup phase. Short TSAP is 2 bytes long. Short local TSAP has the following format:Short remote TSAP has the following format:Long local TSAP is 28 bytes long. Last 2 bytes are higher and lower byte of parameter Local TSAP Full remote TSAP is 28 bytes long and it contains: | - | False |
| MPI/Profibus address sent as a part of Remote TSAP, if parameter Use long TSAP is set to True | 0 to 126 | 1 |
ISO TPDU Size Variable Parameter | The maximum required size of ISO TPDU. The parameter value the initialization of ISO Connection-request. | 8192, 4096, 2048, 1024, 512, 256 or 128 bytes | 1024 bytes |
Nr. of Parallel Network Threads | Maximum parallel communication threads. Increase the value if there is a request on more data read from the device in a shorter time. | 1 to 4 | 1 |
| The required time of one data reading cycle. | ms | 1000 ms |
| Maximal wait time on a reply from the device. | ms | 2500 ms |
| Delay which is used before sending a data request. When a high data transfer rate is required, set 0 ms. | sec.ms | 20 ms |
| Delay before reconnection to the device if the connection has failed or some communication error has occurred. | sec.ms | 2 sec |
| When Timeout passes and communication error occurs in all threads, a communication error status is set on the stations. FALSE state is set on the communication line. | sec.ms | 20 sec |
| Maximum PDU in bytes at S7 communication with the device. | 240, 480, 960 bytes | 480 bytes |
| Setting Tcp No Delay parameter causes low-level socket option TCP_NODELAY to be set, thus turning off the default packet coalesce feature. | - | False |
| Activates a debug info about the loaded values of I/O tags. Use this parameter only when communication must be debugged because it highly uses CPU and slows down the communication. | YES/NO | NO |
Debug I/O Binary Packets Info | Activates a debug info about a binary content of packets. Use this parameter only when communication must be debugged because it highly uses CPU and slows down the communication. | YES/NO | NO |
| Activates a basic debug info about requested data. | YES/NO | YES |
| Activates a basic debug info about received packets. | YES/NO | YES |
Kotva |
---|
| komunikacna_stanica |
---|
| komunikacna_stanica |
---|
|
Communication station configuration...
- Communication protocol: Siemens SIMATIC S7 ISO over TCP.
- No station address, no protocol parameters on the station.
- The time parameter setting is ignored. See the line parameter Cycle Time.
- Time synchronization of device is not supported.
I/O tag configuration...
Possible I/O tag types: Ai, Ao, Ci, Co, Di, Dout, TiA, ToA, TiR, ToR, TxtI.
I/O tag address is compatible with Siemens SimaticNET OPC server.
I/O tag address is a character string according to the following:
{
...
- Communication protocol: Siemens SIMATIC S7 ISO over TCP.
- No station address, no protocol parameters on station.
- Time parameter setting is ignored. See the line parameter Cycle Time.
- A time synchronization of device is not supported.
...
Possible I/O tag types: Ai, Ao, Ci, Co, Di, Dout, TiA, ToA, TiR, ToR, TxtI.
I/O tag address is compatible with Siemens SimaticNET OPC server.
I/O tag address is a character string according to following:
{;}{S7:[connectionname]}DB<no>,<type><address>
{;}{S7:[connectionname]}DI<no>,<type><address>
{;}{S7:[connectionname]}<object>{<type>}<address>
or for structured I/O tags with configured Destination column
{;}{S7:[connectionname]}DB<no>,<type><address>{, <items>}
{;}{S7:[connectionname]}DI<no>DB<no>,<type><address>{, <items>}
{;}{S7:[connectionname]}<object>{<type>}<address>{, <items>}
Where:
DI<no>,<type><address>
{;}{S7:[connectionname]}<object>{<type>}<address>
or for structured I/O tags with configured Destination column
{;}{S7:[connectionname]}DB<no>,<type><address>{, <items>}
{;}{S7:[connectionname]}DI<no>,<type><address>{, <items>}
{;}{S7:[connectionname]}<object>{<type>}<address>{, <items>}
Where:
; | Optional parameter. It disables the I/O tag from communication, stops I/O tag address check when it is saved and can be useful when the communication with the device is activated or debugged. |
S7:[connectionname] | Optional parameter. It does not contain |
; | Optional parameter. It disables the I/O tag from communication, stops I/O tag address check when it is saved, and can be useful when the communication with device is activated or debugged. |
S7:[connectionname] | Optional parameter. It does not contains any useful information but it is supported only because of backward compatibility with Siemens SimaticNET OPC server. |
DB | Data block. S7 variable identifier from "Data block". |
DI | Instance data block. S7 variable identifier from " Instance data block". |
<no> | Number A number of "data block" or "instance data block". |
<object> | Specification of block or area in S7 PLC. Possible values: Value
| Description (German name) |
---|
I | Input (Eingang, E) | I | Input | QOutput | Output (Ausgang, A) | PIPeripheral input | Peripheral Input ( Peripherie Eingang, PE) | PQPeripheral output | Peripheral Output ( Peripherie Ausgang, PA) | M | Memory Memory bit (F) | C | Counters (Counter (Zähler, Z) - BCD coded integer numbers <0-999>) | T | Timers (BCD coded time values from intervals <0.00-9.99>, <00.0-99.9>, <000-999>, <0000-9.9990>) | Kotva |
---|
szl | szl | SSZL (System-ZustandsListen - system status lists) - lists with diagnostic information which are available on CPU family S7-300 and S7-400. Diagnostic information differs for various classes of PLC and details are described in manuals (e.g. System Software for S7-300/400 System and Standard Functions, Volume 1/2) Note: I/O tag S must be of TxtI type. | Timer (Timer, T) - BCD coded time values from intervals <0.00-9.99>, <00.0-99.9>, <000-999>, <0000-9.9990> | | System Status Lists (System-ZustandsListen, SZL) - lists with diagnostic information that are available on CPU family S7-300 and S7-400. Diagnostic information differs for various classes of PLC and details are described in manuals (e.g. System Software for S7-300/400 System and Standard Functions, Volume 1/2) Note: I/O tag S must be of TxtI type. |
|
<type> | Data type of S7. It is not specified for T, C and S objects.
Identifier <type> | Description |
---|
X | Bit (boolean). Specify a bit number 0 to 7 - e.g. DB9,X8.3 | B | Byte (8 bits unsigned). | W | Word (16 bits unsigned). | D | Double word (32 bits unsigned). | CHAR | Character (8 bits signed). | INT | Integer (16 bits signed). | DINT | Double integer (32 bits signed). | BCD | BCD-coded 2-byte number (0-9 999) | LBCD | BCD-kódované 4-byte number (0-99 999 999) | REAL | Floating point number (32 bits according to IEEE754 standard). | LREAL | Long floating point number (64 bits according to IEEE754 standard). | STRING | String. Specify maximal length of string. | CHARARR | Array of CHARs interpreted as a string. Array length must be specified. | DT | Date and Time, 8 bytes in BCD format. | TIME | Time (32 bits signed) in ms. Note: if the I/O tag is of the TiR type, it is necessary to ensure the conversion by configuring the linear conversion (A=0.001, B=0) on the Conversion tab | TOD | Time of day (32 bits unsigned) in ms. |
Note: The CHARARR type is a D2000 extension that allows you to read/write an array of CHARs as a string. This type is not compatible with the Siemens SimaticNET OPC server addressing. The difference between CHARARR and STRING is as follows: - STRING - standard format of the S7 string, when there are 2 bytes in front of the string itself (maximum and current string length). For example, a 10-character STRING takes up 12 bytes.
- CHARARR - array of characters, without a 2-byte header. For example, CHARARR with a length of 10 characters takes up 10 bytes
| <type> | Data type of S7. It is not specified for T, C and S objects.
|
Identifier <type> | Description |
---|
X | Bit (boolean). Specify a bit number 0 to 7 - e.g. DB9,X8.3 |
B | Byte (8 bits unsigned). |
W | Word (16 bits unsigned). |
D | Double word (32 bits unsigned). |
CHAR | Character (8 bits signed). |
INT | Integer (16 bits signed). |
DINT | Double integer (32 bits signed). |
REAL | Floating point number (32 bits according to IEEE754 standard). |
LREAL | Long floating point number (64 bits according to IEEE754 standard). |
STRING | String. Specify maximal length of string. |
DT | Date and Time, 8 bytes in BCD format. |
TIME | Time (32 bits signed) in ms. |
TOD | Time of day (32 bits unsigned) in ms<address> | Address of variable. Possible types:types:- Byte offset (offset within a block, a number 0-65535)
- Byte offsetByte offset.bit (only for X data type, bit number in the range of 0 to 7)
- Byte offset.String length (only for STRING data type, string length from 1 to 254 characters)
- Id.Index[.StringOffset[.StringLength]] - only for object S (system status list):
- Id and Index are 16-bit numbers in range 0-65535 defining ID of specific system status list and index of item in this list
- StringOffset and StringLength are byte offset (0..65535) and length (1..65535) of substring in answer, which will be parsed as a value of I/O tag.
Example: address S237.1.10.20 represents status list 237 (0x0111), index 1 (Identification of the module). S7-300 will answer to this request by a 36 byte-long string (bytes 0..35) in which bytes 10..29 (i.e. offset=10, length=20) represent "Order number of the module", e.g. '6GK7 342-5DA02-0XE0 '. Example of addresses:- DB10,W35
- DB8,X10.0
- DB1,REAL12
- DB5,STRING5.14
- DB5,CHARARR5.14
- T20
- C7
- MB11
- MDINT30
- QX3.7
|
<items> | number of elements for structured I/O tags with configured Destination column. Every read element (1,2,3 .. items) will be written to one item of destination column. Structured I/O tags are not supported for objects of type T (timers), C (counters) and S (system status lists) nor for data type STRING. Note: All items elements are read at once. If e.g. 100 elements of type D (double word) are configured, it means reading of a block of 400 bytes. If a smaller size of packet (S7 PDU size) is agreed on during establishment of connection, reading of this I/O tag will not be performed and trace file of line will contain an error message. Agreed S7 PDU size is minimum of size offered by D2000 (parameter S7 PDU Size) and supported size of specific device. Note: syntax of address when specifying number of elements is compatible with Siemens S7 OPC server (e.g. S7:[MyPLC]DB120,INT1050, 24), which facilitates simple transition from OPC communication to Siemens SIMATIC S7 ISO on TCP protokol by configuring a new line, a new station and then changing parent of I/O tags (e.g. via CSV or XML export and import).
Example of addresses:- DB10,W35, 20 a block of 20 words will be read (i.e. 40 bytes) from addresses 35-54
- DB8,X10.0, 100 a block of 100 bits will be read (i.e. 13 bytes) from addresses 10-22
|
...
For the communication with these devices to work, beside settings described in note above, it is necessery to disable "Optimized block access" in TIA Portal tool. Following screenshot is taken in TIA Portal version 12:
Image Removedversion 12:
Image Added
After changing the security settings in TIA Portal, it is necessary to go to menu Compile → "Software (Rebuild all)" and after compiling to uploat the project to PLC. Partial rebuild may not be sufficient.
Literature
...
- Ver. 1.0 - September 17, 2010 - Document written.
- Ver. 1.1 - July 2, 2020 - Support for CHARARR.
- Ver. 1.2 - July 9, 2020 - Support for BCD and LBCD.
- Ver. 1.3 - August 27, 2020- Support for Siemens Microbox
...