Porovnávané verzie

Kľúč

  • Tento riadok sa pridal
  • Riadok je odstránený.
  • Formátovanie sa zmenilo.

...

ParameterDescriptionUnitDefault value
Kotva
prof
prof
Profile
Analyzed profile.-P.01
Gorlitz PRM62 ModuleFiles from device Gorlitz PRM62 are analyzed.YES/NONO
Kotva
adm
adm
Archive Subdirectory Time Mask
Mask for creating subdirectories in the main archive directory according to time of file processing or timestamp of the file (if the Input file parameter specifies a directory).-rrrrmmdd
Kotva
fcc
fcc
Formatted Codes (Annex C)

Numerical addresses of I/O tags are used according to the specification of IEC62056-21 standard, Annex C.
If numerical addresses are used, the station address is acquired from the value of the object with address D000, the timestamp is acquired from the value of the object with address C001.

YES/NONO
Kotva
cec
cec
External Command File 1, 2
The complete path to a periodically called external command file (.cmd). It is used only if a non-empty value has been configured. It is possible to configure two independently executed command files with different periods.--
Kotva
cep
cep
External Command File Period 1,2
Call period of the external command file 1 or 2.mi:ss1:00
Kotva
ces
ces
Call External Command File 1,2 Synchronously
Call external command file 1 or 2 synchronously.YES/NOYES
Kotva
ceaa
ceaa
Ext. Command File After Activation
The complete path to the external command file which is launched on change of redundancy status to HS. It is called only once and always synchronously. It is used only if a non-empty value has been configured.--
Kotva
dff
dff
Debug Files Flow
Show debug information about processed files.YES/NOYES
Kotva
dfc
dfc
Debug Files Content
Show debug information with the content of processed files.YES/NOYES
Kotva
dval
dval
Debug Values
Show debug information with measured values of the measure points.YES/NOYES
Kotva
fcp
fcp
Files Checking Period
Period of input directory content check (if the Input file parameter specifies a directory).mi:ss1:00
Kotva
ufdir
ufdir
Unknown Files Backup Directory
File, where unknown files are saved (if the Input file is directory). If it is not written, the files will be canceled. The unknown files are the files not-matching the configured mask (see Station protocol parameters) or the station with the required device number was not found.--
Kotva
fdf
fdf
Future Data Filter
Time data filter. If the timestamp of acquired values is newer from the current time by more than the configured number of hours, they are ignored. Enter 0 (zero) to ignore the time filter.hours24
Kotva
hdf
hdf
History Data Filter
Time data filter. If the timestamp of acquired values is older from the current time by more than the configured number of hours, they are ignored. Enter 0 (zero) to ignore the time filter.days31
Kotva
addir
addir
Abnormal Timestamp Data Dir
Directory where the files with ignored data by time filter will be saved (Future Data Filter and History Data Filter).--
Kotva
apt
apt
After Processing Timeout
TimeoutA delay, it which is inserted after the file was analyzed.ss.mss0.100
Kotva
addef
addef
Additional Error Logfile
Error file to write information about errors during processing (unknown file in directory, too old or too new values). Empty An empty value means that this error file will not be created.--

...

ParameterDescriptionUnitDefault value
Kotva
wt
wt
Maximum File Timeout
If the Input file is a particular file, after this timeout passes without a file being processed, then the Station goes to a communication error.min45
Kotva
fnm
fnm
Filename Mask
Mask for the name testing of the processed files. The following digit placeholder can be used:
{N} - electrometer number, beware of mind the number of figurefigures, e.g.{NNNNNNNN},
{yy} or {yyyy} - year,
{mm} - month,
{dd} - day,
{hh} - hour,
{mi} - minute,
{ss} - second.
Exmple of mask: "Meter_{NNNNNNNN}{yy}{mm}{dd}{hh}{mi}.abl".
If a timestamp can be obtained from the file name, it is used for saving the file to the archive directory (see Communication line protocol parameter Archive subdirectory time mask).
If the electrometer number can be obtained, it is used for searching for the proper station.
In the mask is not used, leave the parameter empty. The station address is then acquired from the value of object 0.0.0, C.1.0, or ZNR1 (previously, ZNR1 was previously used only in the case ofGorlitz PRM62 Module, currently it is used also for other types of energy meters).
--
Kotva
csec
csec
External Command File
The complete path to a periodically called external command file (.cmd). The command file is called before accessing the input file. It is used only if a non-empty value has been configured.--
Kotva
csep
csep
External Command File Period
Period of calling the external command file.mi:ss1:00

Kotva
cses
cses
Call Ext. Command File Synchronously

Call the external command file synchronously.YES/NOYES

Kotva
anv
anv
Old Values As New Values

All values from communication (even old ones) go to the system as new values.YES/NONO

Kotva
s2f
s2f
PRM62 Status To Flags

The parameter is only used when analyzing files from the Gorlitz PRM62 (see the Gorlitz PRM62 Module line parameter). When enabled, attributes Invalid (invalid value), ShortPeriod (data for the whole measurement period are not available to electrometer), and TimeSet (time has been set during the measurement period) are mapped into flags FA, FB, FC.

YES/NONO

...

Kotva
adresa_bodu
adresa_bodu
I/O address

...

Address The address of the I/O tag corresponds to standard IEC 62056-61:2002 Object Identification System (OBIS), "Annex A - Code presentation".

...