IEC62056-21:2002 File I/O communication protocol

Supported device types and versions
Communication line configuration
Communication line protocol parameters
Communication station configuration
Station protocol parameters
I/O tag configuration
I/O address
Literature
Changes and modifications
Document revisions

Kotva
typy_verzie
typy_verzie
Supported device types and versions

...

This protocol analyzes the files containing measurement data about measurement according to the IEC 62056 international standard IEC 62056.

Kotva
komunikacna_linka
komunikacna_linka
Communication line configuration

...

  • Communication line category File I/O (communication by via files).

Communication line configuration parameters File I/O communication line configuration parameters:

  • Kotva
    inputfile
    inputfile
    Input file
    - complete path to the file or directory with data.

In the case of analyzing the particular file, its size is tested with a period of 1 secsecond. If the file does not increase in size during two consecutive periods, it is processed.

If a directory is entered (in case of a Win32 platform Win32 with reverse solidus a backslash (\) at the end), all files that match the mask are processed (see station Station protocol parameters).

  • Archive directory -path to the directory, where the processed files are archived. If the directory is not setspecified, the processed files will be cancelleddeleted.

Kotva
linka_parametre
linka_parametre
Communication line protocol parameters

...

Dialog window communication line configuration - Protocol parameters tab Protocol parameters, select the protocol "IEC62056-21:2002 File I/O" protocol.

Table 1

ParameterDescriptionUnitDefault value
Kotva
prof
prof
Profile
Analyzed profile.-P.01
Gorlitz PRM62 ModuleFiles from device Gorlitz PRM62 are analyzed.YES/NONO
Kotva
adm
adm
Archive Subdirectory Time Mask
Mask for generation of creating subdirectories in the main archive directory according to time of file processing or time stamp timestamp of the file (if the Input file is the entered parameter specifies a directory).-rrrrmmdd
Kotva
fcc
fcc
Formatted Codes (Annex C)

Numerical addresses of I/O tags are used according to the specification of standard IEC62056-21 standard, Annex C.
If numerical addresses are used, the station addresss address is then acquired from the value of the object with address D000, time stamp the timestamp is acquired from the value of the object with address C001.

YES/NONO
Kotva
cec
cec
External Command File 1, 2
Complete The complete path to a periodically called external command file (.cmd). It is used only if a non-empty value has been configured. It is possible to configure two independently executed command files with different periods.--
Kotva
cep
cep
External Command File Period 1,2
Call period of the external command file 1 or 2.mi:ss1:00
Kotva
ces
ces
Call External Command File 1,2 Synchronously
Call external command file 1 or 2 synchronously.YES/NOYES
Kotva
ceaa
ceaa
Ext. Command File After Activation
Complete The complete path to the external command file wich which is launched at on change of redundancy status to HS. It is called only once and always synchronously. It is used only if a non-empty value has been configured.--
Kotva
dff
dff
Debug Files Flow
Show debug information about processed files.YES/NOYES
Kotva
dfc
dfc
Debug Files Content
Show debug information with the content of processed files.YES/NOYES
Kotva
dval
dval
Debug Values
Show debug information with measured values of the measure points.YES/NOYES
Kotva
fcp
fcp
Files Checking Period
Period of input directory content check (if the input Input file is parameter specifies a directory).mi:ss1:00
Kotva
ufdir
ufdir
Unknown Files Backup Directory
File, where unknown files are saved (if the input Input file is directory). If it is not written, the files will be cancelledcanceled. The unknown files are the files inconvenient to not-matching the configured mask (see station Station protocol parameters) or the station with the required device number was not found.--
Kotva
fdf
fdf
Future Data Filter
Time data filter. If the time stamp timestamp of acquired values is different newer from the current time by more than stated the configured number of hours in future, they are ignored. Enter 0 (zero) to ignore the time filter.hours24
Kotva
hdf
hdf
History Data Filter
Time data filter. If the time stamp timestamp of acquired values is different older from the current time by more than stated the configured number of hours in past, they are ignored. Enter 0 (zero) to ignore the time filter.days31
Kotva
addir
addir
Abnormal Timestamp Data Dir
Directory where the files with ignored data by time filter will be saved (Future Data Filter and History Data Filter).--
Kotva
apt
apt
After Processing Timeout
TimeoutA delay, it which is inserted after the file was analyzed.ss.mss0.100
Kotva
addef
addef
Additional Error Logfile
Error file to write information about errors during processing (unknown file in directory, too old or too new values). Empty An empty value means that this error file will not be created.--

...

  • Communication protocol "IEC62056-21:2002 File I/O".
  • Station address - the station address is ignored if the input Input file is  is the particular file. If the directory is entered, the device number (electrometer) must be entered to assign the processed file to a particular station. If the station with this number does not exist, the file is considered to be unknown (see communication line protocol parameter Unknown files backup directory).

...

ParameterDescriptionUnitDefault value
Kotva
wt
wt
Maximum File Timeout
If the input Input file is  is a particular file, after this timeout passes without a file being processed, then the station value is transferred to Station goes to a communication error.min45
Kotva
fnm
fnm
Filename Mask
Mask for the name testing of the processed files. The following digit placeholder can be used:
{N} - electrometer number, beware of mind the number of figurefigures, e.g.{NNNNNNNN},
{yy} or {yyyy} - year,
{mm} - month,
{dd} - day,
{hh} - hour,
{mi} - minute,
{ss} - second.
Exmple of mask: "Meter_{NNNNNNNN}{yy}{mm}{dd}{hh}{mi}.abl".
Time stamp gained If a timestamp can be obtained from the file name (if , it is possible) is used at file saving to used for saving the file to the archive directory (see communication Communication line protocol parametersparameter Archive subdirectory time mask).
If the electrometer number is gainedcan be obtained, it is used for searching for the proper station.
In case of not using the mask is not used, leave the parameter should be empty. The station addresss address is then acquired from the value of object 0.0.0, C.1.0, or ZNR1 (previously, ZNR1 was previously used only in the past only in case ofGorlitz PRM62 Module, currently it is used also for other types of energy meters).
--
Kotva
csec
csec
External Command File
Complete The complete path to a periodically called external command file (.cmd). The command file is called before accessing the input file. It is used only if a non-empty value has been configured.--
Kotva
csep
csep
External Command File Period
Call period Period of calling the external command file.mi:ss1:00

Kotva
cses
cses
Call Ext. Command File Synchronously

Call the external command file synchronously.YES/NOYES

Kotva
anv
anv
Old Values As New Values

All values from communication (even old ones) go to the system as new values.YES/NONO

Kotva
s2f
s2f
PRM62 Status To Flags

The parameter is only used when analyzing files from the Gorlitz PRM62 (see the Gorlitz PRM62 Module line parameter). When enabled, attributes Invalid (invalid value), ShortPeriod (data for the whole measurement period are not available to electrometer), and TimeSet (time has been set during the measurement period) are mapped into flags FA, FB, FC.

YES/NONO

...

Kotva
adresa_bodu
adresa_bodu
I/O address

...

Address The address of the I/O tag corresponds to standard IEC 62056-61:2002 Object Identification system System (OBIS), "Annex A - Code presentation".

Shortened The shortened address format is supported: C.D[.E][*F]

...

A special I/O tag with address "$SW" acquires the value of the profile status word.

File example

...

P.01 - profile
(041022094500) - the time stamp timestamp of the first row with values
(00000000) - the profile status word
(15) - period of measurement in minutes
(4) - number of channels
(1.5) - first channel, 1 = Value Group C = Reactive power+, 5 = Value Group D = Last average 1
(MW) - unit of the first channel
etc.

...