VONSCH VQfrem 400 protocol
Supported device types and versions
Communication line configuration
Communication station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions
Kotva | ||||
---|---|---|---|---|
|
...
Table 2 - quantities available for reading according to the documentation
Address | Description | Meaning |
---|---|---|
#0001 | Software version | 609h for ver. 6.09, (402h for ver.4.02, 304h for ver.3.04) |
#0004 | Voltage range | 190h for 400V, 191h for 400 ...M, 2b2h for 690V |
#0025 | Freq. INV - the frequency of voltage on converter’s output (stator frequency) | +/- XXX,XX Hz |
#0026 | Revolves - output revolutions of the motor | +/- XXXX rev/min |
#0027 | Revol/i - evolutions behind gear/transmission | +/- XXXX,X rev/min |
#0028 | Freq.RT - rotor frequency (evaluated from speed encoder – IRC) | +/- XX,XX Hz |
#0029 | Freq.RF - required converter frequency | +/- XX,XX Hz |
#002A | MT Curr. - effective current value into the motor | XXX,X A |
#002B | R.torque - required mechanical motor torque | +/- XXX,X Nm |
#002C | Torque - mechanical motor torque | +/- XXX,X Nm |
#002D | Mag. flux - rotor magnetic flux | X,XXX Wb |
#002E | Volt. MT - momentary motor supply voltage (100.0% responds to 400 V) | XXX,X % |
#002F | Volt. DC - real voltage of converter’s unidirectional DC bus | XXX V |
#0030 | Inp.pow. - momentary input power into the motor | XXX,X kW |
#0031 | MT power - motor power | XXX,X kW |
#0032 | kW hours - motor energy consumption in kWh | XXXX kWh |
#0033 | MW hours - motor energy consumption in MWh | XXXX MWh |
#0034 | Teplota chladiča meniča | XX,X °C |
#0035 | Temp.INV. - air temperature in the converter | XX,X °C |
#0036 | PR ref. - required value of process regulator | XX,X % |
#0037 | PR real - feedback of process regulator (real value) | XX,X % |
#0038 | Inp. AIN1 - the value of analogue input AIN1 in % range | XX,X % |
#0039 | Inp. AIN2 - the value of analogue input AIN2 in % range | XX,X % |
#003A | Hodnota analógového vstupu 3 v % rozsahu | XX,X % |
#003B | BIN 1-6 - status of binary inputs BIN 1 - BIN 6 (bits 0-5 from the received value - bit numbering is from 0 to 15). | 0=input is open 1=input is closed |
#003C | RELAY 1-2,3 - the status of relay inputs RELAY 1 - RELAY 4 (bits 8-10 from the received value - bit numbering is from 0 to 15). | 0=relay is open 1=relay is closed |
#003D | Hours INV - converter operating time counter | XXXX h |
#003E | Hours MT - motor operating time counter | XXXX h |
#003F | Pos.ref. - required position in a case of „position“ variable | +/- XXXX,X cm |
#0040 | Position - real position | +/- XXXX,X cm |
#0041 | Pos. TSW2 - the trajectory for running down when Terminal switch TSW2 is on | +/- XXXX cm |
#0042 | Deviation from zero position when calibrating the ARC position sensor | XXXX d |
#0043 | cos(fi ) - momentary value of motor power factor | +/- X,XX |
#0044 | See Warnings register 2 | - |
#0045 | See Warnings register 1 | - |
#0046 | See Faults register | - |
#0048 |
Overload - a momentary value of overload | XXX.X % |
#0049 |
Service SL - service displayed variable Slave | +/- XXXX d |
#004a |
Service MS - service displayed variable Master | +/- XXXX d |
Všetky hodnoty sú prenášané ako All values are transmitted as 16-bitové čislabit numbers. KOM proces ich interpretuje ako znamienkové alebo kladné podľa adresy (znamienkové sú The KOM process interprets them as signed or positive by address
(signed are #0025-#0027, #002B, #002C, #003F-#0041, #0043, #0049- #004a#004a).
Pokiaľ je číslo desatinné, treba v konfigurácii meraného bodu v záložke Prevod zadať príslušný lineárny prevod (napr. koeficient If the number is fractional, the corresponding linear conversion must be entered in the I/O tag configuration in the Conversion tab (e.g. coefficient A=0.1 pre #0030for #0030, A=0.01 pre #0028for #0028).
Kotva | ||||
---|---|---|---|---|
|
...
Table 3 -
...
If an arbitrary bit is set to logical 1, the corresponding fault/failure has arisen in the converter.
Bit | Význam |
---|---|
0 |
Converter Overcurrent |
1 |
Converter Overload |
2 |
Converter Undervoltage |
3 |
Converter Overvoltage |
4 |
Motor Overheat |
5 |
Heatsink Temperature |
6 |
Incorrect parameters of currents, motor constants, or speed |
7 |
Regulation error |
8 |
Identification error |
9 |
Output short circuit |
10 |
IRC failure (ARC), RM-ARC |
11 |
Input or Output phase loss |
12 |
External failure |
13 |
Temperature in inverter |
14 |
AIN1, AIN2 |
, or AIN3 disconnected | |
15 | rezervované |
Kotva | ||||
---|---|---|---|---|
|
...
Table 4 - Warnings register
...
1 (values of I/O tag with address
#0045
: If an arbitrary bit is set to log.1, the converter generates a corresponding warning.
Bit | Význam |
---|---|
0 |
some warnings W1-W5: |
W2 - Počas odbudzovania klesol magn. tok na minimálnu hodnotu
W3 - Regulátor magnetického toku je v nasýtení (len vo vektorovom režime)
W4 - Regulátor momentu motora je v nasýtení (len vo vektorovom režime)
W5 - Regulátor rýchlosti je v nasýtení (len vo vektorovom režime)
- The converter reduces motor magnetic flux in order to achieve over-synchronous revolutions. | |
1 | W6 - Motor cooler has reached an increased temperature (over 75 °C). For VQFREM 400 005, 007, and 011 types, the module temperature is over 90 °C |
2 | W7 - The converter switches itself into scalar mode due to IRC/ARC failure. |
3 | W8 - Signalisation of reverse direction of IRC/ARC. |
4 | F7 - The time needed for motor field suppression has not expired yet (before subsequent start). |
5 | W12 - Process regulator is saturated. Converter frequency has reached its maximum value. |
6 | F9 - Position calibration initiated by 9.4.3 command, or calibration of IRC encoder on the synchronous motor. |
7 | F11 - The speed decreased to zero by activating a software terminal switch. |
8 | F8 - Dynamic deceleration was activated as a result of a sharp decrease in speed. |
9 | W16 - Sensored motor temperature has achieved nonpermissible value. |
Pri typoch VQFREM 400 005, 007 a 011 je teplota modulu vyššia ako 90 °C
F9 - Prebieha kalibrácia polohy od povelu 9.4.3 alebo sa kalibruje IRC (ARC) snímač na synchrónnom motore
F10 -Prebieha hľadanie nulového impulzu IRC na synchrónnom motore po zapnutí meniča na sieť a povele ŠTART
10 | W17 - Ak je EOPN panel aktívny (2.4.1), a prerušilo sa spojenie s meničom |
11 | F2 - Aktivuje sa regulátor max. prúdu (par.13.3.1) a obmedzuje prúd na hodnotu par. 9.10.1 |
12 | F3 - Menič je v režime kinetického zálohovania po výpadku elektrickej energie |
13 | F4 - Prebieha nafázovanie meniča na roztočený motor |
14 | F5 - Prebieha parkovanie procesného regulátora |
15 | F6 - Brzdný modul je aktívny |
Kotva | ||||
---|---|---|---|---|
|
Tab. č. 5 - register varovaní 2 (hodnoty bodu s adresou #0044). Ak je ľubovoľný bit nastavený na hodnotu 1, menič generuje príslušné varovanie
Bit | Význam |
---|---|
0 | W23 - Pri povele ŠTART menič zistil neprítomnosť záťaže na výstupných svorkách U,V,W |
1 | F12 - Je zopnutý koncový spínač 1 alebo koncový spínač 2 |
2 | F13 - Funkcia „brzdenie tokom“ zvyšuje budenie motora úmerne rozdielu UDC-UDCnom |
3 | W9 - Prerušenie vstupnej fázy meniča |
4 | rezervované |
5 | F14 - Prebieha OFF-LINE identifikácia niektorého z parametrov motora (Rs, Ls+Lm, Upoč) |
6 | W25 - Teplota vzduchu v meniči je vyššia ako 70 °C |
7 | rezervované |
8 | W18 - Nastala chyba pri komunikácii po sériovej linke RS232 ( RS485) |
9 | F16 - Signalizuje, že Relé s funkciou „vypne, preťaženie“ práve rozoplo |
Kotva | ||||
---|---|---|---|---|
|
...