  • Communication protocol "IEC62056-21:2002 File I/O".
  • Station address - the station address is ignored if the input Input file is  is the particular file. If the directory is entered, the device number (electrometer) must be entered to assign the processed file to a particular station. If the station with this number does not exist, the file is considered to be unknown (see communication line protocol parameter Unknown files backup directory).

...

ParameterDescriptionUnitDefault value
Kotva
wt
wt
Maximum File Timeout
If the input Input file is  is a particular file, after this timeout passes without a file being processed, then the station value is transferred to Station goes to a communication error.min45
Kotva
fnm
fnm
Filename Mask
Mask for the name testing of the processed files. The following digit placeholder can be used:
{N} - electrometer number, beware of number of figure, e.g.{NNNNNNNN},
{yy} or {yyyy} - year,
{mm} - month,
{dd} - day,
{hh} - hour,
{mi} - minute,
{ss} - second.
Exmple of mask: "Meter_{NNNNNNNN}{yy}{mm}{dd}{hh}{mi}.abl".
Time stamp gained If a timestamp can be obtained from the file name (if , it is possible) is used at file saving to used for saving the file to the archive directory (see communication Communication line protocol parametersparameter Archive subdirectory time mask).
If the electrometer number is gainedcan be obtained, it is used for searching for the proper station.
In case of not using the mask is not used, leave the parameter should be empty. The station addresss address is then acquired from the value of object 0.0.0, C.1.0, or ZNR1 (ZNR1 in the past previously, ZNR1 was used only in case ofGorlitz PRM62 Module, currently it is used also for other types of energy meters).
--
Kotva
csec
csec
External Command File
Complete The complete path to a periodically called external command file (.cmd). The command file is called before accessing the input file. It is used only if a non-empty value has been configured.--
Kotva
csep
csep
External Command File Period
Call period Period of calling the external command file.mi:ss1:00

Kotva
cses
cses
Call Ext. Command File Synchronously

Call external command file synchronously.YES/NOYES

Kotva
anv
anv
Old Values As New Values

All values from communication (even old ones) go to the system as new values.YES/NONO

Kotva
s2f
s2f
PRM62 Status To Flags

The parameter is only used when analyzing files from the Gorlitz PRM62 (see the Gorlitz PRM62 Module line parameter). When enabled, attributes Invalid (invalid value), ShortPeriod (data for the whole measurement period are not available to electrometer), and TimeSet (time has been set during the measurement period) are mapped into flags FA, FB, FC .

YES/NONO

...

Address of I/O tag corresponds to standard IEC 62056-61:2002 Object Identification system System (OBIS), "Annex A - Code presentation".

Shortened The shortened address format is supported: C.D[.E][*F]

...

A special I/O tag with address "$SW" acquires the value of the profile status word.

File example

...

P.01 - profile
(041022094500) - the time stamp timestamp of the first row with values
(00000000) - the profile status word
(15) - period of measurement in minutes
(4) - number of channels
(1.5) - first channel, 1 = Value Group C = Reactive power+, 5 = Value Group D = Last average 1
(MW) - unit of the first channel
etc.

...