The protocol implements ANSI X3.28 communication. The communication was verified against the SPIO 500M communication unit of ABB's SPACOM protectin and control system.
The D2000 KOM process  process periodically reads all configured I/O tags (see the Read Data Timeout parameter). The communication unit spontaneously sends events (Events) that can also cause the I/O tag of DI type to be set to 0 or 1 (see the I/O tag configuration).

Kotva
komunikacna_linka
komunikacna_linka
Communication line configuration

...

Kotva
stanica
stanica
Station configuration

...

  • Communication protocol: "ABB SRIO X3.28".
  • Station address: a number in the range of 0 - 255.

...

Dialóg Communication station - Protocol parameters tab.
The parameters influence some optional protocol parameters. The following protocol line parameters can be used:

Table 1

ParameterDescriptionUnitDefault value
Kotva
sa
sa
Host Station Address
The address of
Master
the master station (
LOM Process
D2000 KOM process) is a number in the range 0 to 255.-0
Kotva
rc
rc
Retry Count
Number
The number of request retries in case of a communication failure.-3
Kotva
wft
wft
Wait First Timeout
First waiting
on
for a response after sending the request.ms100 ms.
Kotva
wt
wt
Wait Timeout
Delay between reading
The delay between individual readings of the response until its completing.ms100 ms.
Kotva
mwr
mwr
Max Wait Retry
Retry count of response reading until its completing.-50
Kotva
so
so
Scan-only Mode
Activate a permanent passive mode (Scan only) without sending requests and only processing received messages.YES/NONO
Kotva
fd
fd
Full Debug
Full communication monitoring. It enables to show the I/O tag values and other debug information.YES/NONO
Kotva
didadr
didadr
DI Data Address
Start
The start address of the block of DI data (digital inputs). Blok's length is 500 words, data are 16-bit binary numbers.
The parameter is used only for communication logs and analysis.
-0
Kotva
didadr
didadr
DO Data Address
Start
The start address of
block of
the block of DO data (digital outputs). Blok's length is 250 words, data are 16-bit binary numbers.
The parameter is used only for communication logs and analysis.
-500
Kotva
evdadr
evdadr
EV Data Address
Start
The start address of
block of
the block of EV data. Blok's length is 250 words, data are 16-bit binary numbers with timestamps.
The parameter is used only for communication logs and analysis.
-750
Kotva
aidadr
aidadr
AI Data Address
Start
The start address of
block of
the block of AI data (analog inputs). Blok's length is 500 words, data are 32-bit binary numbers.
The parameter is used only for communication logs and analysis.
-1000
Kotva
aodadr
aodadr
AO Data Address
Start
The start address of
block of
the block of AO data (analog outputs). Blok's length is 500 words, data are 32-bit binary numbers.
The parameter is used only for communication logs and analysis.
-1500
Kotva
tadr
tadr
Time Address
Start address
The start address of Time Write data where time is written during time synchronization. Data's length is 9 words, data is BCD encoded.-2300
Kotva
edadr
edadr
Event Data Address
Start address
The start address of Event
Data
data. The data is 4 words in length, the data
is
are 32-bit
binary
binary numbers (containing 10-bit SPACOM Unit Number, 7-bit Channel Number and 5-bit Event Number which can be specified in the I/O tag configuration) with a time stamp.-2400
Kotva
rdl
rdl
Request Data Length
The size of the block of data specified in the BLOCK_READ data request sent by the KOM process (2-244 bytes).bytes100
Kotva
rdat
rdat
Read Data Period
Period
A period (10-1440 minutes) in which the KOM process performs readout of all data (integrity readout).min15
Kotva
drt
drt
Diagnostic Request Timeout
Period
A period (10-60 sekúnd) in which the KOM process sends a diagnostic request (DIAG_LOOP) to verify line functionality.s5

String containing the protocol parameters is defined as follows:

...

Kotva
merany_bod
merany_bod
I/O tag configuration

...

Possible value type: Ai, Di.

I/O tag address items:

  • Word Address: 16-bit data address in device memory (0-65535) used during readout of all data (see Read Data Timeout).
  • Kotva
    spunit
    spunit
    SPACOM Unit (Di tags only): optional 10-bit address of SPA Unit (0-1023) within the SPACOM system.
  • Channel (Di tags only): optional 7-bitová adresa SPA Channel (0-127) within the SPACOM system.
  • EventNr 0->1 (Di tags only): optional 6-bit number of Event (0-63), that will cause transition to value True.
  • EventNr 1->0 (Di tags only): optional 6-bit number of Event (0-63), that will cause transition to value False.

Note: Optional address items SPACOM Unit, Channel, EventNr 0->1, EventNr 1->0 are used when the Di I/O tag§s value is to be set after the arrival of Event Data.

Kotva
zmeny_upravy
zmeny_upravy
Changes and modifications

...