Protocol specification
Protocol OPC XML DA is a transitive protokolom between protocols OPC Data Access Client and OPC Unified Architecture Data Access Client.
An improvement to OPC Data Access Client is a transition to platform-independent communication (using XML data format and SOAP-Web Services over HTTP protocol).
The latest from OPC protocol family is the protocol OPC Unified Architecture Data Access Client which maintains platform independence and optimizes performance by replacing XML / SOAP communications with binary encoding and by eliminating HTTP protocol.
Communication line configuration
Communication line category: HTTP client
URL: URL address of OPC XML server in form http://host[:port][/path[?query]], e.g. http://172.16.0.1 or http://myopcserver.domain:8080/opcxml
Proxy: IP address or name of optional proxy server. If entered, KOM process will connect to proxy server instead of host listed in parameter URL.
User: optional name for authentication on proxy server (support for authentication has not been implemented).
Password: optional password for authentication on proxy server (support for authentication has not been implemented).
Protocol line parameters
Parameter | Meaning | Unit | Default value |
---|---|---|---|
Debug Responses Parsing | Enable debug messages at the OPC XML server response level. | YES/NO | NO |
Debug Http I/O Data | Turn on debug messages at HTTP communication level. | YES/NO | YES |
Debug Http Responses | Turn on debug messages with headers and body of HTTP response. | YES/NO | NO |
Debug Received Values | Turn on debug messages with received values. | YES/NO | YES |
Protocol configuration on the communication station
- Communication protocol: OPC XML Data Access 1.01 Client.
- Station address: unused.
Station protocol parameters
Table 1
Full name | Description | Default value |
---|---|---|
Request option ReturnErrorText | Parameter of Subscribe and Write requests. If set to YES, the server will return verbose error description. | NO |
Request option ReturnDiagnosticInfo | Parameter of Subscribe and Write requests. If set to YES, the server will return verbose server specific diagnostic information to provide additional information relative to item specific errors. | NO |
Request option ReturnItemTime | Parameter of Subscribe and Write requests. If set to YES, the server will return the timestamp for each Item. | YES |
Request option ReturnItemPath | Parameter of Subscribe and Write requests. If set to YES, the server will return ItemPath (a path to Item within Namespace) for each Item. | NO |
Request option ReturnItemName | Parameter of Subscribe and Write requests. If set to YES, the server will return ItemName (a fully qualified identifier of Item) for each Item. | NO |
Request option ReturnValuesOnReply | Parameter of Subscribe and Write requests. If set to YES, the server will return values of all Items in reply to Subscribe and value of Item in reply to Write as if the client had performed a Read request directly after the Write request. | YES |
I/O tag configuration
I/O tag configuration dialog window is used for setting the monitored objects.
Object address setting
Name | Meaning |
---|---|
Item Name | Unique text identifier of Data in OPC XML server. |
Subscribe | If the setting is checked, the KOM process uses this Item in Subscribe request to query the value of the object. This setting can be unchecked for objects that are not supposed to be read (e.g. write-only I/O tags or objects that have been removed from the communication). |
Literature
OPCconnect.com manuals can be obtained from http://www.opcconnect.com/xml.php
Changes and modifications
- May 12, 2017 - creating the document
Document revisions
- Ver. 1.0 – May 12, 2017