Configuration of system texts

Configuration of system texts is performed by means of the D2000 CNF process.

Configuration of system texts

The system texts are divided into the following categories:


The objects, values of which do not contain system texts:

  • I/O tags of AI, AO, CI, CO, TiA, ToA, TiR, ToR, TmRo, TxtI a TxtO types
  • Evaluated tags
  • User variables of Integer, Real, TmA, TmR, Txt types

* Displaying of values of Integer, Real, Absolute time and Time interval types might be controlled by transformation palette.


Boolean values

Label in the systemPredefined labelCause
B_FalseFalseFalse value
B_TrueTrueTrue value
B_OscillateOscillateOscillating value (TRUE <-> FALSE).



Di, Do measured values

Label in the systemPredefined labelCause
D_FalseOFFFalse value
D_TrueONTrue value
D_OscillateOSCILLATEOscillating value (TRUE <-> FALSE). The system sets the value as the oscillating one according to defined parameters of filtering - Oscillation limits.



Process object values

Label in the systemPredefined labelCause>
P_RunRunThe process is running.
P_CrashCrashThe process is terminated by an error (incorrect termination). If it is possible, the D2000 Server will try to start the process again.
P_StopStopThe process is correctly terminated.
P_WDErrWDErrError when communicating with the D2000 Server - Watch Dog Error (interrupted flow of Watch Dog messages between the client process and the D2000 Server).



System alarm values

Label in the systemPredefined labelCause
A_NormNormalThe condition to raise the alarm is not met.
A_AlarmAlarmThe condition to raise the alarm is met.
A_KvitKvitThe alarm is acknowledged by the operator.
A_BlockBlockThe alarm is blocked by the operator, or at the alarm configuration is enabled Blocked alarm option.
A_UnBlockUnBlockThe D2000 Alarm process is not running and the operator unblocks the given alarm in the Blocked state.
A_NoKvitNoKvitThe condition to finish the acknowledge-required alarm is met before its acknowledgement.



Station values

Label in the systemPredefined labelCause
St_OnONThe station communicates
St_OffOFFThe station does not communicate. The communication is disabled by the operator (via the control window in the D2000 HI process) or at the station configuration in the D2000 CNF process.
St_CommErrCOMERRThe occurrence of a "soft" error of the communication. Such error occurs after unsuccessful data transmission.
St_HardErrHARDERRThe occurrence of "hard" errors in the communication. Such error occurs if the communication with the station is in StCOMERR state within the period given by the Time filter parameter. If the station value is StHARDERR, then all the I/O tags of the station will pass to an undefined state.
St_SimulSIMULCommunication with the station is simulated.
St_WaitWAITThe station is in AUTO mode. Communication is stopped. The control object value is TRUE. Requests for output are postponed and they will be executed when the control object value will be FALSE.



Qi measured values

Label in the systemPredefined labelCause
SwTransTRANSChange of quadrature value from TRUE into FALSE or vice-versa.
SwOffOFFFalse value
SwOnONTrue value
SwErrERRORInvalid (illegal) value.
SwOscOSCILLATEOscillating value (TRUE <-> FALSE). The system sets a value as the oscillating one according to defined parameters of filtering - Oscillation limits.



Process alarms

Label in the systemPredefined labelCause
NoAlarmNoAlarmNo process alarm is active
ToTrueToOnProcess alarm occurred - change into ON (TRUE) level.
ToFalseToOffProcess alarm occurred - change into OFF (FALSE) level.
TrueOnProcess alarm occurred - ON (TRUE) level.
FalseOffProcess alarm occurred - OFF (FALSE) level.
InvalidErrInvalid (illegal) value.
OscillateOscillateOscillating value.
HLHLProcess alarm occurred - limit state of HL value.
VHLVHLProcess alarm occurred - limit state of VHL value.
LLLLProcess alarm occurred - limit state of LL value.
VLLVLLProcess alarm occurred limit state of VLL value.
ToHLToHLProcess alarm occurred- value change into HL limit state.
ToVHLToVHLProcess alarm occurred- value change into  VHL limit state.
ToLLToLLProcess alarm occurred - value change into LL limit state.
ToVLLToVLLProcess alarm occurred - value change into  VLL limit state.
SwToTransSwToTransProcess alarm occurred - change of quadrat value into Q_Trans value.
SwToOffSwToOffProcess alarm occurred- change of quadrat value into Q_Off (FALSE) value.
SwToOnSwToOnProcess alarm occurred- change quadrat value into Q_On (TRUE) value.
SwToErrorSwToErrProcess alarm occurred - change of quadrat value into Q_Err value.
SwTransSwTransProcess alarm occurred- quadrat value is Q_Trans.
SwOffSwOffProcess alarm occurred - quadrat value is Q_Off.
SwOnSwOnProcess alarm occurred - quadrat value is Q_On.
SwErrorSwErrProcess alarm occurred - quadrat value is Q_Err.
ErrorWriteCmdErrWriteCmdError at the setting of output tags.
Sw_ErrorCmdOnErrCmdOnError during cm_SetSwitchOn command execution.
Sw_ErrorCmdOffErrCmdOffError during cm_SetSwitchOff command execution.
Sw_ErrorBkpCmdOffErrZalCmdOffError during cm_SetSwitchBkpOff command execution.
ChangeChangeProcess alarm occurred - change of integer or analog value.
SysPrAlSysProcAlarmThe special type of process alarm is used just for two objects of System variable type - SystemError and SystemWarning.



Value limits

Label in the systemPredefined labelCause
Is_InLimitInLimitThe object value is at once greater or equal to LL and less or equal to HL (LL<=values<=HL).
Is_VL_LimitVL_LimitThe object value is less than VLL (value<VLL).
Is_L_LimitL_LimitThe object value is at once greater or equal to VLL and less than LL (VLL<=value<LL).
Is_H_LimitH_LimitThe object value is at once greater than HL and less than VHL (HL<value<=VHL).
Is_VH_LimitVH_LimitThe object value is greater than VHL (VHL<value).
Is_LimitsProblemLimitsProblemIn the case of dynamic limits, there is a validity mismatch of the conditions: VLL<LL<HL<VHL.



Value states

Label in the systemPredefined labelCause
s_val_InvalidInvalidInvalid object value.
s_pa_AlarmProcAlarmThe state occurs in the case that the given object has an active process alarm.
s_pa_NoAckNoAckPAlarmThe state occurs in the case that the process alarm is not acknowledged by the operator in the D2000 HI process.
s_pa_BlockedPrAlSilentThe state occurs in the case that the given object has not any active process alarm, or the Silent option is enabled at the configuration of object process alarms in the D2000 CNF process.
s_val_WeakWeakA weak (suspicious) value is a value not valid in the system because all the conditions of its validity are not met.
s_val_NoAckNoAckValueThe state occurs in the case that the last object value change is not acknowledged by the operator in the D2000 HI process.
s_val_TransientTransientA transient state of the value occurs, if the command that sets the object value was executed, but backward reading has not yet verified the value setting.
s_val_DefaultDefaultThe default state of the object value occurs, if the I/O tag value gained by the process D2000 KOM is replaced by another value - the control object value, or is manually set by the operator in the D2000 HI process.
s_val_ManualManualThe object value is in a Manual state if it is manually set by the operator in the D2000 HI process.
s_pa_CriticalPrAlCritThe status occurs in the case that the process alarm is defined as a critical one in the D2000 CNF process.
s_pa_UnknownUnknown



Operator commands

Label in the systemPredefined labelCause
cm_SetDefautManualSetDefManManual setting of the object default value.
cm_SetDefautAutoSetDefAutoActivation of the automatic mode of the object default value control. The default value in this mode will be copied the control object value.
cm_SetManualSetManualManual setting of output object value.
cm_SetAutoSetAutoActivation of the automatic mode of the output object value control. The object value in this mode copies the control object value.
cm_SetDefaultOffSetDefOffCancel the validity of the object default value.
cm_SetSwitchBlockAOnSetBlockAOnActivation of blockade A of the switch.
cm_SetSwitchBlockAOffSetBlockAOffDeactivation of blockade A of the switch.
cm_SetSwitchOnSetSwitchOnSwitch on the switch.
cm_SetSwitchOffSetSwitchOffSwitch off the switch.
cm_SetSwitchBkpOffSetSwitchBkpOffBackup switch off the switch.
cm_SetSwitchBlockBOnSetBlockBOnActivation of blockade B of the switch.
cm_SetSwitchBlockBOffSetBlockBOffDeactivation of blockade B of the switch
cm_SetSwitchNormalOffSetSwitchNormalOffSet the switch to the normal state - OFF.
cm_SetSwitchNormalOnSetSwitchNormalOnSet the switch to the normal state - ON.
cm_SetSwitchNormalNoneSetSwitchNormalNoneSet the switch to the normal state - NONE.



Alarm commands

Label in the systemPredefined labelCause
cm_AlarmKvitKvitThe alarm is acknowledged by the operator.
cm_AlarmBlockBlockThe alarm is blocked by the operator, or the Blocked alarm option is enabled at its configuration in the D2000 CNF process.
cm_AlarmUnblockUnblockThe alarm is unblocked by the operator.
Napíšte komentár