Event logging in the system

"Log database" dialog box in the process D2000 CNF allows to set the log database parameters. The dialog box contains table comprising the following columns:

  • Event - category of system events,
  • Log - [Yes/No] - enable / disable logging particular event into the log database,
  • History depth [days] - [0-365] - writing period of event into the log database (in days),
  • Use device - [Yes/No] - enable / disable event logging to output device,
  • Device - name of output device. Output device is the type of device, where logged data will be written. There are these types of output devices:
    • PRN, LPT1, LPT2 - output to specified printer,
    • FileName.Ext - saving to a text file of given name.
Event category System events
Alarms All changes of alarm states (information about particular alarm states and their changes, see the on-line guide D2000 System Configuration - topic Alarm states).
System Start and stop of D2000 system
Operator's logon into D2000 system (logon with incorrect name or password).
Process All status changes of D2000 system processes (e.g. start, stop, breakdown).
Kom process Communication failures.
Operator All operator's interactions into the system (e.g. changes of system objects' values via control windows in the process D2000 HI).
Event Logs written by performed LOG commands.
Logon/Logoff Operator's logon / logoff  from / to D2000 system processes.
ManualEntry Not implemented yet.
Change value Spontaneous changes of values.
PostMortemData Special communication data.

To set parameters to write events of given category into the log database:

  1. Click required category of events.
  2. Using Log, History depth, Use device and Device placed bellow the table, set parameters for the given category of events.
  3. Click the Save button to confirm the log database configuration.