IEC62056-21:2002 Serial communication protocol

Supported device types and versions
Communication line configuration
Communication line protocol parameters
Communication station configuration
Station protocol parameters
I/O tag configuration
I/O tag address
Literature
Changes and modifications
Document revisions

Supported device types and versions


The protocol communicates in series with devices according to international standard IEC62056-21, protocol mode C.

Communication line configuration


Communication line protocol parameters


Configuration dialog box, tab Protocol parameters - select the protocol "IEC62056-21:2002 Serial".

Table 1

ParameterMeaningUnitDefault value
Area Code
The common call prefix for phone modem connection (only lines of MODEM category).

Software 7E1
YES option switches SW emulation of transfer parameters of 7 data bits, even parity when the transfer parameters of 8 data bits are set, none parity (i.e. emulation 7E1 when 8N1 is set).YES/NONO

Communication station configuration



Station protocol parameters


Configuration dialog box - tab Protocol parameters.
These parameters influence some optional protocol parameters. Following station protocol parameters can be set:

Table 2

ParameterMeaningUnitDefault value
Modem Telephone Number
Phone number for connection via modem with this station (only lines of MODEM category).

Dial Timeout
Maximal waiting time on connection via modem (only lines of MODEM category).sec60
Dial Retry Count
Maximum number of attempt to connect via modem (only lines of MODEM category).1..201
Dial Retry Timeout
Delay before attempting to dial after an unsuccessful connection attempt (only lines of MODEM category).sec30
Wait First Timeout
Time delay between sending the request and reading the answer.
Note: a device sends a 3-character manufacturer's identification in the identification message. Standard defines that if the 3-rd character is a lower case letter, (e.g. in identifications ELm or UNi), minimum reaction time for such device is 20 ms instead of 200 ms. If the 3-rd character is an upper case letter, this does not preclude supporting a 20 ms reaction time.
ms200
Wait Timeout
Time delay between reading the answer till it is completed. See the note of parameter Wait First Timeout.ms200
Max Wait Retry
Retry count of reading response till its completion.1 .. 10020
Retry Timeout
Delay between the request retry if the error communication occurs.ms1000 ms
Retry Count
Retry count of request as far as the error communication.1 .. 203
Disconnect Timeout
Timeout for waiting for answer to modem hangup operation (only lines of MODEM category).sec15
Ack Delay
Delay after transmitting acknowledgement of received data (ACK).ms100
Baudrate Changeover (Z)
Value of parameter 'Z' - Baud rate identification (for baud rate changeover) of request Acknowledgement/option select message of protocol C mode.

Option AUTO finds out automatic the value 'Z' from acknowledgement of answer and uses it.

300 Baud
600 Baud
1200 Baud
2400 Baud
4800 Baud
9600 Baud
19200 Baud
38400 Baud
57600 Baud
115200 Baud
AUTO
2400 Baud
Data Readout
Permission to read the current values ("data readout").YES/NOYES
Manuf. Spec. Table Readout Nr.1 (Y)
Permission to read the "manufacturer specific table" values, 1-st block.
Choice '-' means the values are not read, choice '6' to '9' means selected "manufacturer specific table" will be read.
-
6
7
8
9
-
Manuf. Spec. Table Readout Nr.2 (Y)Permission to read the "manufacturer specific table" values, 2-nd block.
Choice '-' means the values are not read, choice '6' to '9' means selected "manufacturer specific table" will be read.
-
6
7
8
9
-
Manuf. Spec. Table Readout Nr.3 (Y)Permission to read the "manufacturer specific table" values, 3-rd block.
Choice '-' means the values are not read, choice '6' to '9' means selected "manufacturer specific table" will be read.
-
6
7
8
9
-
Load Profile
Permission to load the historical data from profile.YES/NOYES
Profile
Profile name - OBIS code of load profile used during loading of historical data from profile.
P.01
Profile Time Mask
Date and time mask used to read historical data from profile.
The letter " z" is used to set the time and is replaced by a value of 0, 1 or 2 according to the parameter Session Recognition Flag.

zyymmddhhmi
Profile History Depth
Time depth of historical profile readings.hour24
Time Round
Time round of data from profile.min15
Profile Read Step
Time range of data which is queried from profile in one request. It is entered as a multiple of the parameter "Time Round".x Time Round2

Profile Read Level

Access level used to read historical data from profile.0-95

Profile Read Mode

Method of reading from profile:

  • VDEW read command (R5) : READ command will be used (the R5 default level can be changed by parameter Profile Read Level).
  • VDEW block read command (R6) : BLOCK READ command will be used (the default level should be changed to R6 by parameter Profile Read Level).
  • P1 + VDEW read command (R5) : first, a Level 1 password will be set (see the parameter Password - level 1) and then READ command will be used 
  • P1 + VDEW block read command (R6): first, a Level 1 password will be set (see the parameter Password - level 1)  and then BLOCK READ command will be used 

BLOCK READ divides the data into several blocks with the size of Profile Read Block Length rows. Block reading makes sense on lines with higher error rates.

-VDEW read command (R5)

Profile Read Block Length

Block size (number of rows) if BLOCK READ from the profile is used - if Profile Read Mode is VDEW block read command (R6) or P1 + VDEW block read command (R6)row4

Profile Read Formatted Execution

This parameter enables specifying a special sequence which may be required by some electrometers. So far the only known sequence is F101()
(The whole sequence sent to electrometers is <SOH>E2<STX>F101()<ETX><SOH> ).
-
Password - level 1
Password necessary for changing configuration of device (level 1) used to set the date and time.
"00000000"
Session Recognition Flag
Flag that indicates type of date/time used by the device. Electrometers LZQJ manufactured by EMH Elektrizitätszähler indicate type of date/time by this flag (0=Normal Time, 1=Summer Time, 2=UTC Time).
This flag is used by parameters Time Mask and Date Mask to set the time and by parameter Profile Time Mask to read historical data from profile.
Note: Both Normal Time and Summer Time values will cause the flag to be set depending on the time currently set or read.
Normal Time
Summer Time
UTC Time
Normal time
Time Register
Register used to set the time.
The parameter is important only if the synchronization is enabled on the tab "Time parameters" in the configuration of station.

0.9.1
Time Mask
Mask used to set the time.
The letter " z" is used for time conversion according to the parameter Session Recognition Flag.
The parameter is important only if the synchronization is enabled on the tab "Time parameters" in the configuration of station.
Note: some meters are disturbed by summer / winter time ("z") flag and require mask hhmiss

zhhmiss
Date Register
Register used to set the date.
The parameter is important only if the synchronization is enabled on the tab "Time parameters" in the configuration of station.

0.9.2
Date Mask
Mask used to set the date.
The letter " z" is used for dátumu conversion according to the parameter Session Recognition Flag.
The parameter is important only if the synchronization is enabled on the tab "Time parameters" in the configuration of station.
Note: some meters are disturbed by summer / winter time ("z") flag and require mask ddmmyy or require a year-month-day order (zyymmdd or yymmdd)

zddmmyy

Time Date Mode

Special settings used when setting the date and time. These may be required by some electricity meters.

  • Normal: no special settings
  • (00000000): this string is added after the written date / time.
    Example: if Date Mask is zddmmyy,  is zddmmyy, the date 31 Dec 2019 is written as (0311219)(00000000)
Normal
(00000000)
Normal

AT Command 1

A special initial string of modem 1 (only for MODEM lines).
AT&FE0V1Q0B0X3L0M0
AT Command 2
A special initial string of modem 2 (only for MODEM lines).

Explanation of recommended settings:

S37=5   1200bps DTE-DTE speed - limits the speed for modems. Many devices use modems with limited transfer speeds and this setting can speed-up the connection establishment process. Higher transfer speeds must be negotiated individualy.

&D2   DTR drop to hangup - for matching with tha parameter of modem line (line configuration, tab "Modem - parameters", check the option "Use DTR for Hangup").

S0=0   Disable auto-answer. Auto-answer will not be used.

S30=2   20 sec inactivity timeout - automatic hangup after idle timeout expired. Necessary for assuring connection termination after the communication with the last device is over.



ATS37=5&D2S0=0S7=60S30=2
Full Debug
Full tracing of communication, loaded values of I/O tags and other debug information are shown.YES/NONO
Unicontrols Devices
It activates data processing according to software implementation of protocol from Unicontrols.YES/NONO
Unicontrols Read Index
Activates reading of profile index (map of records stored in memory) within reading of historical data from profile (Unicontrols device only). Retrieved index is not processed further and serves only as debugging information for Unicontrols.YES/NONO

I/O tag configuration


Possible types of I/O tag values: Ai, Ci, Di, TxtI, TiA, TiR.

I/O tag address


I/O tag address correspond to standard IEC 62056-61:2002 Object Identification system (OBIS) in terms of "Annex A - Code presentation".

Abbreviated format of address is supported: C.D[.E][*F] as well as full format A.B.C.D[.E][*F]

in which:

Example of addresses:

0.0.0            Meter address
0.0.1            Identity number
0.9.1            Time
0.9.2            Date
1.2.1            Cumulative P+ Tariff 1
1.2.2            Cumulative P+ Tariff 2
1.6.1            Maximum P+ Tariff 1
1.8.1            Energy P+ Tariff 1
3.6.1            Maximum Q+ Tariff 1
3.6.1*01       01.Pre-value Maximum Q+ Tariff 1