Supported device types and versions
Communication line configuration
Communication station configuration
Station protocol parameters
I/O tag configuration
Literature
Changes and modification
Document revisions
Communication supports reading and writing data by means of the UNIP protocol (© IpeSoft Žilina).
Note:
The UNIP SCAN protocol is a passive protocol that tracks active communication of other UNIP master/slaves system. It doesn't send polls, but decode the tracking communication.
Communication station - configuration dialog box - Protocol parameters tab.
They influence some optional protocol parameters. The following station protocol parameters can be defined:
Table 1
Parameter | Meaning | Unit | Default value |
---|---|---|---|
Retry Count | Poll repetition count in case of a communication error. | - | 3 |
Retry Timeout | Delay between poll repetition in case of a communication error. | ms | 2000 ms |
Wait First Timeout | First waiting for response after sending the poll. | ms | 500 ms |
Wait Timeout | Delay between response readings till its finalization. | ms | 500 ms |
Max Wait Retry | Repetition count of response readings till its finalization. | - | 8 |
Wait ACK Timeout | First waiting for response after writing, the ACK acknowledge is expected. | ms | 700 ms |
Wait First Get Stored | Waiting for a response after a request to read archive data. | s | 1 s |
AI Back Compatible | In D2000 V5.00.017 Rel.A020430541, the interpretation of I/O tags of the AI and AO types of the forms of 3, 5, 6 and 7 has been modified to signed ones. The value of AIBC=YES enables backward compatibility and these I/O tags will be interpreted as unsigned. | - | NO |
Max. Activity Wait | For the UNIP SCAN protocol only – time (in seconds) within which the response for given station must be received, otherwise the station passes to communication error. | s | 600 s |
Use Daylight Saving Time in TS Req. | Setting the parameter to YES activates the use of daylight saving time in the timestamped requests. | - | NO |
String containing the protocol parameters is being defined as follows:
Keyword=value;Keyword=value; ...
Example:
RC=1;RT=500;
If there is used a keyword with an invalid value in the initialization string, there will be used corresponding default value according the table 1.
Possible I/O tag types:
Ai, Ci, Di for the UNIP Input Only and UNIP Input Only Time Synchro protocols.
Ai, Ao, Ci, Co, Di, Dout for the UNIP, UNIP Time Synchro and UNIP SCAN protocols.
Address: Decimal number within the range of 0...255.
-