Closing of a graph, graphic picture or composition.
Declaration
CLOSE grObjIdent [INSTANCE instanceExprInt]
or
CLOSE grObjIdent ON procIdent [INSTANCE instanceExprInt]
or
CLOSE grObjIdent ON ALL [INSTANCE instanceExprInt]
or
CLOSE DIRECT
Parameters
grObjIdent
in
Reference to an object of Graph, Picture or Composition types.
procIdent
in
Identifier of a Process type object (Human Interface).
instanceExprInt
in
Expression of Int type, which specifies the object instance number.
Description
The action will close given graphic object (optionally also the given instance) on specified console (if not declared, then on SELF.HIP) or on all running consoles.
Action with the DIRECT clause is permitted only for:
the script of active picture - the action closes the active picture,
next actions may not be executed - so it is recommended to put the
CLOSE DIRECT
action at the end of RPC procedure).
Examples
Closing a graph in the process SELF.HIP
BEGIN
ALIAS _newGraph
INT _newGraphHBJ
SET _newGraph AS D.graf
IF _newGraph\HBJ = 0 THEN
ELSE
OPEN _newGraph ; opening a graph in SELF.HIP process
DELAY 2[s]
CLOSE _newGraph ; closing a graph in SELF.HIP process
ENDIF
END
Closing an instance of graph in all HIP processes
BEGIN
ALIAS _newGraph
INT _newGraphHBJ
SET _newGraph AS D.graf
IF _newGraph\HBJ = 0 THEN
ELSE
OPEN _newGraph ON ALL INSTANCE 0 ; opening the first instance
OPEN _newGraph ON ALL INSTANCE 1 ; opening the second instance
DELAY 2[s]
CLOSE _newGraph ON ALL INSTANCE 1 ; closing the second instance
ENDIF
END
Closing the particular instance of graph in HIP process
BEGIN
ALIAS _newGraph
INT _newGraphHBJ
SET _newGraph AS D.graf
IF _newGraph\HBJ = 0 THEN
ELSE
OPEN _newGraph ON srvskol1v.HIP INSTANCE 0 ; opening the first instance
OPEN _newGraph ON srvskol1v.HIP INSTANCE 1 ; opening the second instance
DELAY 2[s]
CLOSE _newGraph ON srvskol1v.HIP INSTANCE 1 ; closing the second instance
ENDIF
END