ZPA INMAT 51/66 communication protocol
Supported device types and versions
Communication line configuration
Communication station configuration
Station protocol parameters
I/O tag configuration
Literature
Changes and modifications
Document revisions
Supported device types and versions
This protocol supports data reading and writing to the dataloggers INMAT 66 and INMAT 51 produced by ZPA Nová Paka (Czech republic).
Communication line configuration
- Communication line category: Serial, SerialOverUDP Device Redundant.
- The parameters of asynchronous line are set according to version and type of
device connection:
- the settings from manufacturer (you can find out it on a display in the control menu): 9600 Baud, 8 data bits, even parity, 1 stop bit.
Note:
When testing, we found out that there was a short period between sending the
request and receiving the response (less than 10 ms). You should enter the
similar values (1 to 10 ms) into the parameter "Receive delay" in line mode. If
there are several devices on one line (RS485), you should set such value which
is suitable for all devices to ensure 100% success of data transfer.
Communication station configuration
- Communication protocol: ZPA INMAT 51/66.
- The station address is a decimal number in the range of 0 up to 126 (you can find it on a display of device).
- When necessary, you may enable the synchronization of real-time on station – INMAT devices.
Station protocol parameters
Communication station - configuration dialog box -
tab Protocol parameters.
They influence some of the optional parameters. You can set the following
station protocol parameters:
Table 1
Parameter | Meaning | Unit | Default value |
---|---|---|---|
Wait Timeout | Delay between reading the response until it is completed. | ms | 200 millisec. |
Wait First Timeout | First waiting for response after sending the request. | ms | 200 millisec. |
Retry Timeout | Delay between the response retry if some error in communication occurs. | ms | 500 millisec. |
Max Wait Retry | Maximum retries of reading the response until it is completed. | - | 4 |
Retry Count | Number of response retries if some error in communication occurs. | - | 2 |
Local Source Address | Local source address of D2000 KOM process. | - | 0 |
Full Debug | Communication monitoring high level, information about reading I/O tags and received values are displayed. | NO |
I/O tag configuration
I/O tags: Ai
For address, you must set two parameters:
INX and IY
These address parameters are provided by the producer (ZPA Nová Paka) when buying the device.
The values are in hexadecimal format:
- INX – 0 up to FF
- IY – 0 up to FF