Porovnávané verzie

Kľúč

  • Tento riadok sa pridal
  • Riadok je odstránený.
  • Formátovanie sa zmenilo.

Parameters for the D2000 Server process

The process The D2000 Server process reads the following parameters from the system registry during its start. Values are adjusted using the process D2000 Application Manager (D2Smc.exe).

...

ParameterPossible valuesMeaning
AckForValue0/1If the parameter value is 1, every new value in the system will be set to the attribute NoAckValue. Operator An operator can acknowledge that he saw the value in the object control window.
AlarmsWithoutFocus0/1If the value of this parameter is 1, the window opening opened by a new alarm , dondoesn't take the focus of another window of the HI process
AllowNonAdminConfLogin0/1If the value of this parameter is 1, users without administrative rights are allowed to log in to the configuration processes of the D2000 system D2000. Default The default value is 0. That means, non-administrative users can not log in to configuration processes.
AuditDepth_RES_GROUP

The value

different from

differing from 0 sets

the

the full monitoring of changes in the configuration of the Object group. It represents

a

the time depth of the stored information in months. The value 0 (or absence of parameter) deactivates the monitoring.

AuditDepth_USER
The value different from differing from 0 sets the the full monitoring of changes in the configuration of the User. It represents a the time depth of the stored information in months. The value 0 (or absence of parameter) deactivates the monitoring.
APPL_NAME
Application name.
AuthMethod
Default authentication method. The parameter can acquire the following values:Detail Detailed information about the parameter is mentioned in the topic Authentication in D2000, part AuthMethod.
AuthSecPrinc
Security principal for Kerberos authentication.
Detail Detailed information about the parameter is mentioned in the topic Authentication in D2000, part AuthSecPrinc.
BackupSysCfgDeep
Depth of configuration database backups that are created automatically. The backups older than defined depth are automatically deleted. It is defined in seconds.

Note: If the value is 0 (zero), the automatic backup of the configuration database is disabled.
BackupSysCfgOffset
Shift A shift of automatic backup of configuration database in a given period. It is defined in the format HH:MM, i.e. shift in hours and minutes.
BackupSysCfgPath
Path to directory in which the backups of configuration database, created automatically, are to be stored. Default setting is %D2000_APP%\%application_name%\SysCfg\Backup.

Note: For proper functionality of automatic backup of configuration database, any no other directories and files should not be created in the directory for storing where these backups are stored.
BackupSysCfgPeriod
Period of an automatic backup of the configuration database. it is defined in the format NX, where N is integer and X is a time unit. The permitted time units are H - hour, D - day, W - week, M - monthemonth.

Note: If you set an empty value or 0H, the backup of the configuration database is disabled.
Kotva
colman
colman
ColorMandatoryItems

Background color for a mandatory item in active pictures (Text entry field and List box). Default value = FFFFFF – i.e. no background. The color is represented by the number that can be derived from the RGB by the following formula: R + 256*G + 65536*B (see %MakeRGB function)
Kotva
colcon
colcon
ColorConditionalItems

Background color for a conditional item in active pictures (Text entry field and List box). Default value = FFFFFF – i.e. no background. The color is represented by the number that can be derived from the RGB by the following formula: R + 256*G + 65536*B (see %MakeRGB function)
Kotva
configbackuptimeout
configbackuptimeout
ConfigBackUpTimeout
0...Maximum time [s] of backup of syscfg the configuration database. The backup is executed through the external process.
If the parameter is:
> 0 - the process is ended forcibly if the backup has not been executed successfully in a defined time.
= 0 - the process is ended after the database backup is executed. It can take very long when the process is jammed.
Kotva
configsynchrotimeout
configsynchrotimeout
ConfigSynchroTimeout
0...Maximum time [s] of synchronizing of the syscfg configuration database.
If the parameter is:
> 0 - the synchronization is ended forcibly if it has not been finished in a defined time.
= 0 - the synchronization can take unlimited time.
ControlRightForKvit0/1If the parameter value is 1, a user can acknowledge an alarm only if he/she has the access right with the level Control or higher to the alarm. If the value is 0, the user needs the access level with the level Read (default state) only.
character_encoding_APP_DEFAULT
Initial character encoding in the application. This parameter is used, when there is "@APP_DEFAULT@" encoding in the ESL function. The initial value is "@OS_ACTUAL@".
CheckDODMTreesInterval
Defines DODM tree consistency check in regular intervals. A default value is 0 (zero) in seconds. The time of next processing of the parameter value depends on the parameter value that has been set while processing it (it may be changed while the system is running):
  • value > 0: it starts the DODM tree consistency check and then calculates the time of next processing (clock + interval[s]),
  • other stateotherwise: a check is disabled; the processing starts in a minute (clock + 60[s]).
Start Debug info, via DBG.CHECK.DODM_TREES, to see the information on the process of the DODM tree consistency check.
More detailed reports regarding this activity are mentioned thereinafter.
CtrlAckDialog0/1

Confirm setting a new value by opening a new window asking: Do you want to set the X value X ?

0 - no, 1 - yes.

CtrlCloseAfterSetValue0/1

Auto close control window based on application parameter

0 - no, 1 - yes.

descInTitleBar0/1Displaying of description in the titlebar title bar of graphs, reports, pictures, or structures instead of the object name.
0 - hide description (shows object name only), 1 - show description
The parameter is not valid for users with the Administrator access rights.
dynamGraphMaxTime
Time length [min], that determines the range of the horizontal (time) axis of dynamic graphs.
dynamGraphShiftTime
The parameter [min] determines the shift of the time axis of dynamic graphs, when  when drawing a graphic flow reaches the right margin of the axis.
dynamGraphLineType0/1Definition of a graphic flow type for dynamic graphs.
0 - a smooth line, 1 - a straight line.
dynamGraphDescTable0/1Displaying the descriptive table of dynamic graphs.
0 - hide table, 1 - show table.
dynamGraphAllStatistics0/1Displaying all the graphic flows of statistic values in dynamic graphs.
0 - hide graphic flows, 1 - show graphic flows.
dynamGraphMultiArchFALSE/TRUEOpens the archive objects in multigraphs.
TRUE - the archive objects are opened in the separate multigraphs (default).
FALSE- the archive objects are opened together with other objects in the multigraphs.
dynamGraphPointer0/1Displaying the pointer on opening dynamic graphs.
0 - hide the pointer, 1 - show the pointer
HeapArrSizeRef
It represents the size of auxiliary "HEAP" arrays. The parameter is set automatically when the application is started for the first time. Default The default value is 100 000. It enables the optimization of some bulk allocations. The settings setting is especially important especially for XML Import. The An example of the log of allocated space for "HEAP" arrays is stated available here.
ExpandTree0/1If the value of the parameter is 1, then all selection windows in the system will consist complete list of logical groups (expanded). If the value is 0, then all the windows will consist list with basic logical groups only (collapsed list).
KeepObjectValueAfterSave0/10 - after saving the configuration, the setting of object value is set to "invalid" - (standard behaviour behavior - the default value of the parameter).
1 - after saving the configuration, the setting of object is same as previous till acquiring new valuevalue is not invalidated.
LIC_DoNotAllowConsoleOverLimit0/1Disables to the logon of the console (HI) if the licence license limit is exceeded. Default = off (0).
LIC_DoNotAllowSysProcOverLimit0/1Disables to Disables the logon of the system process if the licence license limit is exceeded. Default = off (0).
LIC_PostponeLicWrnToUsersDWORDWhen occurring the a problem with the licencelicense occurs, first the administrator is informed until this time expires. After this, all users will be informed. Default The default value is 1 hour. The permitted maximum is the constant integer limited by the time
Constant Integer := 10*24; – [hours].
Kotva
logrecslatesynchro
logrecslatesynchro
LogRecsLateSynchro
0/1Defines whether CfgSynchroAuto starting -  will be started with or without parameter /NO_OBJLIFE parameter (the object life logs are not synchronized). CfgSynchroAuto is called by D2000 Server, which is in HS a HOT state , when it receives a demand on request for synchronization of the configuration database from other another D2000 Server connecting to a redundant group.

Allowed values:
0 - default synchronization
1 - synchronization with /NO_OBJLIFE
A detailed
Detailed meaning of the parameters for cfgsynchroauto is for CfgSynchroAuto is described in Synchronization of configuration databases.

Kotva
logtrezorpath
logtrezorpath
LogTrezorPath

Path to the directory, where the log database depository will be created.
Kotva
logtrezorcompresspath
logtrezorcompresspath
LogTrezorCompressPath

Path to the directory for storing compressed log database depositories.
Kotva
logtrezorcompresstime
logtrezorcompresstime
LogTrezorCompressTime

Time period, during which disconnected log database depository is available for writing delayed data. The database will be compressed after the expiration of this period. Value The value of this parameter LogTrezorPeriod LogTrezorCompressTime must be less than the value of the parameter LogTrezorPeriod. It is given in the format NX, where N is an integer number and X gives a time unit.
Permitted time units: H - hour, D - day, W - week, M - month.
Kotva
logtrezorperiod
logtrezorperiod
LogTrezorPeriod

Period for creating the log database depository. It is given in the format NX, where N is an integer number and X gives a time unit.
Permitted time units: H - hour, D - day, W - week, M - month.
Zero value (e.g. 0H) disables the log database depository. The default value of this parameter is 0H.

Kotva
APP_PARAM_MailingAddress
APP_PARAM_MailingAddress
MailingAddress


The email address to which the user can send the application error information.
MaxMonitorItems
Maximal The maximal number of items, that the process D2000 Server gives to the process D2000 HI on request for the list from the log database.
numLastUsers
Number The number of last entered users in the list of Logon dialog box of HI and GrEditor - max. 10.

If the number is equal to 1, a text box displays at nameis displayed instead of a list box.
If the number is greater than 1, the list of the last entered <numLastUser> users displays at nameis displayed.

OEM_ProtX_Name
Name of OEM protocol nr. X, as will be displayed in the D2000 CNF environment.
For more details, see the description of the D2000 KomAPI interface.
OEM_ProtX_DLL
Name of a dynamic library (.dll on Windows, .so on Linux), in which the communication protocol OEM nr. X is implemented. The name is specified without a suffix.
For more details, see the description of the D2000 KomAPI interface.
OldMasks
Change of the format masks behaviour behavior.
0 - the character # after the decimal point means that the occurrence of number is not required
1 - the character # after the decimal point is identical with the character 0 (required number occurrence) - compatible with D2000 v5.0 and older versions.
Kotva
securitypolicy
securitypolicy
SecurityPolicy
0/1If 1 - activation of new rules, if 0 - default behaviour behavior during a change of user's password.
ShowConsoleUsers0/1It determines if the users of console type (*.HIP.LOG) will be displayed in the List of objects.
SingleCommand0/1If the value of this parameter is 1, just one control window can be opened for one object at the same time in the process D2000 HI.
SP_MinLength0...20Minimal password length.
SP_MinLowerCaseLetters
Minimal count of lower case in the password.
SP_MinNumbers0...10Minimal count of numbers in password.
SP_MinSpecials0...10Minimal count of special symbols (e.g. ! @ # $ % ^ & a pod.) in a password.
SP_MinUpperCaseLetters
Minimal count of upper case in the password.
SP_Similarity0...100Ratio The ratio for similarity of the new password to previous ones. The value can be within the interval 0...100.
SP_History0...10Number The number of previous passwords, which are to be compared with the new password.
SP_AccountLockoutDuration
Time [s], that which determines how long a user's account will be blocked, when the user exceeds the permitted count of logons.
SP_AccountLockoutTreshold
Number The number of permitted invalid logons. If the number is exceeded, the user's account will be blocked for the time defined by the parameter SP_AccountLockoutDuration. If the value of the parameter SP_AccountLockoutTreshold is 0, the user's account will never be blocked.
SP_MaxConsecutiveCharacters
Maximum The maximum number of consecutive characters included in the password.
SP_CheckMinCharacters0/1If the value is 1 - the number of digits and non-digits in the password is to be also checked. In this case, the value of the parameter SP_MinNumbers defines the minimum number of both digits and non-digits.
SrvApplHelpTypeHelpFileChm

Selection of Application Help Types - NoHelp, HelpFileChm, HelpWebServerConfluence, HelpWebServerHtml, HelpSharedDir, HelpLocalApplDir, HelpLocalAnyPath

SrvApplHelpPath
Set the location of the help by type SrvApplHelpType.
SrvApplHelpMainPage
Default application help page.
SrvD2000HelpTypeHelpWebIPSSelection of help types for D2000 - HelpWebIPS, HelpWebServerHtml, HelpSharedDir, HelpLocalD2000Dir, HelpLocalAnyPath
SrvD2000HelpPathhttps://doc.ipesoft.com/label/D2DOCVSet the location of the help by type SrvD2000HelpType. Popis nastavenia umiestnenia závisí je vysvetlený je nižšie.

Kotva
tcp_no_delay
tcp_no_delay
TCP_NO_DELAY

DEFAULT
TRUE
FALSE
During registration of every client connecting via TCP/IP protocol (start parameters /TP or /TPP) the process D2000 Server can change the value of the socket parameter TCP_NODELAY to TRUE/FALSE. More details are available in the description of tell command the TCP_NO_DELAY command.
If the value of the TCP_NO_DELAY parameter is not set or is equal to DEFAULT, parameter TCP_NODELAY will not be changed.
Kotva
testversion
testversion
TestVersion

Color The color distinction of production and test server in the process D2000 HI:
  • 0 - the server is a production server, not a test server (default)
  • 1 - the server is a test server: the heading of D2000 HI has a red color
Note: Parameter is implemented since the version 7.02.001.
TNS_Service_Name
Configuration parameter for the configuration and log databases on Oracle platform - defines TNS of the database the configuration and log tablespaces are in.
UseServerTimeZone0/1 Allows the client processes to use the server time zone offset (KERNEL). By default, each process uses its system time zone offset.
WinDisColorUse
Indication for the usage of the defined colour color in WinDisColorValue as the color in disable wincontrols in schemes.
0 - no
1 - yes
WinDisColorValue
Colour in banned window controls in schemes (text input, buttons, trees, and lists).
The color is represented by the number that can be derived from the RGB by the following formula: R + 256*G + 65536*B (see %MakeRGB function)

Kotva
xmlgitrepository
xmlgitrepository
XmlGitRepositoryEnabled

0/1

If the value is 1 and the path to the GIT repository is set - all changes to objects in D2000 are stored in the GIT object history

XmlGitRepositoryPath

Path to GIT repository where are stored all changes to of objects are stored.

XmlGitSharedRepoInRedundancy0/1

If the value is 1 and the system is in redundant mode and storing changes into the GIT repository is enabled - all changes are written only by the active (hot) server


The following four parameters allow to set setting the logic logical beginning and end of the day for the application. The settings have an effect on the dialog boxes for defining a time interval - when you define time interval, hours and minutes are to be adjusted according to the parameters.

ParameterMeaning
day_start_hour *Hour of the beginning of the day. Default value: 0.
day_start_min *Minute of the beginning of the day.
day_end_hour *Hour of end day.
day_end_min *Minute of end day.
day_end_strong_ineq **
  • TRUE - for a selected time interval, there is the following will be valid: StartTime ≤interval<EndTime
  • FALSE - for a selected time interval, there is the following will be valid: StartTime ≤interval≤EndTime

...

Kotva
hlasky
hlasky
Parameter CheckDODMTreesInterval - detailed reports

When Debug info are activate  is activated via DBG.CHECK.DODM_TREES for this activity, these messages are written into D2000 Server log:

...