- the types of output I/O tag and respective input I/O tag must be the same (Ao-Ai, Dout-Di, TxtO-TxtI, ...)
- configuration of output I/O tag must be set to ASDU 252 (the tab Address, the parameter ASDU type)
Note for patches from 19.5.2023 and later: if the respective input and output I/O tags are not of the same type, the conversion will take place, and at the same time a warning will be saved in the line log.
Communication station parameters: Kotva parametre_stanice parametre_stanice
Keyword | Full name | Meaning | Unit | Default value | ||||||
---|---|---|---|---|---|---|---|---|---|---|
| D2000 Copy Limit Status | The parameter is set on the station that is the parent of input I/O tags for which the partner station sends ASDU 252. Such I/O tag then ignores its defined limits and copies the ValueLimitStatus (basic object attribute) of its control object. If there are configured process alarms for input I/O tag, they will be evaluated according to the ValueLimitStatus copied from the control object. Note: The parameter D2VCO must be set on the partner station. | - | False | ||||||
| D2000 Copy Process Alarms | The parameter is set on the station that is the parent of input I/O tags for which the partner station sends ASDU 252. Such I/O tag then ignores its configuration and copies process alarms of the control object of partner output I/O tag. Note: The parameter D2VCO must be set on the partner station. | - | False | ||||||
| D2000 ASDU Value from Control Object | The parameter is set on the station that is the parent of output I/O tags with defined ASDU 252. If a control object is defined for such I/O tag, then the value of the control object is sent to communication as the output value (along with its basic object attributes - ValueType, ValueTime, ValueStatus, ValueLimitStatus, ValueProcAlarmStatus, ...). Warning: In this case, there are ignored all configuration of output I/O tag concerning process alarms, limits and value conversion ! Value of output I/O tag seems to be correct within D2000 system, but there is sent "raw" value of control object into communication. Note: To send "raw" value of control object, the value types of control object and output I/O tag must be the same, otherwise there is sent ordinary output value. This behavior was modified in patches from 19.5.2023 and later - the value is always sent. | - | False |
Notes:
- The parameters D2CLS and D2CPA allow getting values of process alarms and ValueLimitStatus of control object only (not given I/O tag) - because process alarms and ValueLimitStatus of I/O tag are being set after its writing.
- Implemented functionality (combination of the parameters D2CLS, D2CPA and D2VCO) may cause the value of output I/O tag to be "inconsistent" (e.g. value is in IN_LIMIT status and there is the process alarm HL active at the same time). !!! WE RECOMMEND TO USE IT CAREFULLY !!!
...