This protocol supports data reading and writing to the dataloggers INMAT 66 and INMAT 51 dataloggers produced by ZPA Nová Paka (Czech republic).

...

  • Communication line category: Serial, SerialOverUDP Device Redundant.
  • The parameters of an asynchronous line are set according to version and type of device connection:
    • the settings from the manufacturer (you can find out it on a display in the control menu): 9600 Baud, 8 data bits, even parity, 1 stop bit.

Note:
When testing, we found out that there was a short period between sending the request and receiving the response (less than 10 ms). You should enter the similar values (1 to 10 ms) into the parameter "Receive delay" in the line mode. If there are several devices on one line (RS485), you should set such value which is suitable for all devices to ensure 100% success of data transfer.

Kotva
komunikacna_stanica
komunikacna_stanica
Communication station configuration

...

  • Communication protocol: ZPA INMAT 51/66.
  • The station address is a decimal number in the range of 0 up to 126 (you can find it on a display of device).
  • When necessary, you may enable the synchronization of real-time on the station – INMAT devices.

Kotva
stanica_parametre
stanica_parametre
Station protocol parameters

...

Communication station - configuration dialog box - tab Protocol parameters.
They influence some of the optional parameters. You can set the following station protocol parameters:

Table 1

ParameterMeaningUnitDefault value
Kotva
wt
wt
Wait Timeout
Delay
The delay between
reading
the response
until it is completed
readings.ms200
millisec.
ms
Kotva
wft
wft
Wait First Timeout
First waiting for response
The delay after sending the request and before reading the response.ms200
millisec.
ms
Kotva
rt
rt
Retry Timeout
Delay between the response retry if some error in communication occurs
Timeout before resending a request if no response has been received.ms500
millisec.
ms
Kotva
mwr
mwr
Max Wait Retry
Maximum
The maximum number of retries of
reading
the response
until it is completed
reading.-4
Kotva
rc
rc
Retry Count
Number of response retries if some error in communication occurs
Maximum count of request retries. If no response returns after a request had been sent, the station's status will change to a communication error.-2
Kotva
sa
sa
Local Source Address
Local
The local source address of the D2000 KOM process.-0
Kotva
fd
fd
Full Debug
Communication monitoring high level, information about reading I/O tags, and received values are displayed.
 

NO

Kotva
merany_bod
merany_bod
I/O tag configuration

...

I/O tags: Ai

For address, you must set two parameters:

INX and IY

These address parameters are provided by the producer (ZPA Nová Paka) when buying the device.

...