Remia E3 communication protocol

Supported device types and versions
Communication line configuration
Communication station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions

Supported device types and versions


This protocol supports data reading/writing from a controller of quarter-hour maximum Remia EEE.

Communication line configuration


  • Communication line category: Serial, SerialOverUDP Device Redundant, TCP/IP-UDP.
  • Parameters of the serial line:
    • Baud rate - 1200 Baud
    • No parity, 8 data bits, 1 stop bit
  • Parameters of UDP line:
    • Host: IP address of the controller
    • Port: UDP port of the controller where requests are sent.
    Note: The parameters of the backup server (Host and Port) are not used in this protocol.

Communication station configuration


  • Communication protocol: Remia E3.
  • The station address is set according to the address on a device (0 to 15) specified as a decimal number or as a hexadecimal number with a hash at the beginning (e.g. #6A).


Station protocol parameters

The configuration dialog box of station - the tab "Protocol parameters".

Table 1

KeywordFull nameMeaningUnitDefault value
RC
Retry CountMaximum count of request retries. If no response returns after a request had been sent, the station's status will change to a communication error.-2
RT
Retry TimeoutTimeout before resending a request if no response has been received.ms100 ms
WFT
Wait First TimeoutThe delay after sending the request and before reading the response.ms100 ms
WT
Wait TimeoutThe delay between the response readings.ms300 ms
MWR
Max Wait RetryThe maximum number of retries of the response reading.-10

I/O tag configuration


I/O tag types: Ai, Ci, Co, Di, TiA, TiR.

The address is a number in the range from 0 to 300 (as a decimal number or as a hexadecimal number with a hash at the beginning, e.g. #0A).
The meaning of the addresses is stated in Table 2:

Table 2

Value typeAddressDescriptionRead/Write
Ai
Ai0Instantaneous power.R
Ai1Average power.R
Ai2Peak VT.R
Ai3Peak NT.R
Ai4Measurement 1 (main) - the last 1/4 hour (see Note).R
Ai5Measurement 2 (secondary) - the last 1/4 hour (see Note).R
Ci
Ci0The number of electrometers.R
Ci1The number of regulatory degrees.R
Ci2The number of appliances.R
Ci3Regulatory degree.R
Ci4Tariff (0=VT, 1=NT).R
Ci5Current regulatory degree.R
Ci6Current average power (%).R
Co
Co0Regulated power VT.R/W
Co1Regulated power NT.R/W
Di
Di0 až 7Type of electro meter (FALSE=active power [kW], TRUE=reactive power [kVAr]).R
Di100 až 164Appliances (FALSE=idle state, TRUE=control state).R
Di200 až 264Status signal (FALSE=inactive, TRUE=active).R
TiR
TiR0The time within a 15-minute interval.R
TiA
TiA0Date and time of initialization.R
TiA1Date and time of power failure.R
TiA2Date and time of the configuration change.R
TiA3Date and time of the last reset.R
TiA4Current date and time.R
TiA5Time to reach peak VT.R
TiA6Time to reach peak NT.R
TiA7Time of the last quarter-hour.R

Note: You can obtain also the values from an archive of the device for the current and previous month for both the main and secondary measurement. The reading of archive values may be started in the station dialog box or by the GETOLDVAL Tell command.

Literature


-

Changes and modifications


-

Document revisions


  • Ver. 1.0 - August 22, 2001 - Creation of document
  • Ver. 1.1 - April 22, 2008 - Updating