Supported device types and versions
Literature
Document revisions

Supported device types and versions


The Jablotron 100 protocol enables communication with the RS-485 - JA-121T bus interface of the JABLOTRON 100 Alarm system.

The Jablotron 100 protocol is implemented as an ESL script using the Generic User Protocol.

Serial interface parameters:

  • RS485 (two-wire connection)
  • 9600 baud
  • 8 data bits
  • no parity
  • 1 stop bit

The protocol supports:

  • determining the state of the section/sections 1-15: the STATE command
  • checking the status of PG outputs 1-128: the PGSTATE command
  • determining the status of peripherals 0-229 (really only 0-30 were present): the PRFSTATE command
  • enabling/disabling protection in sections: SET, SETP, UNSET commands
  • switching on/off PG outputs: PGON/PGOFF commands

Both the active mode of communication (interface spontaneously sends changes) and passive mode (periodic polling is required) are supported.

The received values are stored in D2000 in structured variables (sections/peripherals/PG outputs).

Literature


Document revisions


  • Ver. 1.0 - March 21st, 2024 - Document creation.
Napíšte komentár