KomUniVal structure
struct KomUniVal { unsigned short uvStatus; TLimitStatus uvLimitStatus; unsigned int uvProcAlarmStatus; TValueType uvValType; unsigned short uvFlags; D2Time uvValTime; D2Time uvProcAlarmTime; TBVal uvBoval; int uvIntval; double uvRealval; TStVal uvStationval; D2Time uvTmAval; double uvTmRval; TQVal uvQval; int64_t uvIntval64; char *uvTxtval; };
Structure KomUniVal transfers the value and status of the D2000 system object (I/O tag, station, line). The meaning of individual items of the structure:
uvStatus
It can get a combination of the following values:
#define SB_Val_Valid 0x0001 #define SB_Pa_Alarm 0x0002 #define SB_Pa_NoAck 0x0004 #define SB_Pa_Blocked 0x0008 #define SB_Val_Weak 0x0010 #define SB_Val_NoAck 0x0020 #define SB_Val_Transient 0x0040 #define SB_Val_Default 0x0080 #define SB_Val_Manual 0x0100 #define SB_Pa_Critical 0x0200
Implementation of a communication protocol can change the following values for objects of I/O tag type:
- SB_Val_Valid – the validity of I/O tag value
- SB_Val_Weak – I/O tag value is suspicious (weak)
Other values are changed internally by the communication process.
uvLimitStatus
typedef enum {LS_InLimit, LS_VL_Limit, LS_L_Limit, LS_H_Limit, LS_VH_Limit, LS_LimitsProblem} TLimitStatus;
The parameter marks limit states of the I/O tag value. Implementation of a protocol sets up this parameter only in case of the value ST_SOURCE_LIMITS of the parameter Stat call-back of the function PointNewValue.
Possible values:
- LS_InLimit - value is in limits
- LS_VL_Limit - value is below the lowest limit (only for the I/O tag types Ai, Ao, Ci, Co)
- LS_L_Limit - value is below the low limit (only for the I/O tag types Ai, Ao, Ci, Co)
- LS_H_Limit - value is above the high limit (only for the I/O tag types Ai, Ao, Ci, Co)
- LS_VH_Limit - value is above the highest limit (only for the I/O tag types Ai, Ao, Ci, Co)
- LS_LimitsProblem - limits problem (crossing the values or a dynamic limit value is invalid)
uvProcAlarmStatus
Process alarms attributes. Implementation of a protocol must not change this parameter.
uvValType
typedef enum {VT_NAN, VT_Bo, VT_Int, VT_Re, VT_Di, VT_Do, VT_De, VT_Ai, VT_Ao, VT_Ae, VT_Ci, VT_Co, VT_Ce, VT_St, VT_Li, VT_Al, VT_Pr, VT_TmA, VT_TmR, VT_TiA, VT_ToA, VT_TiR, VT_ToR, VT_Txt, VT_Arr, VT_Qi, VT_Unused1, VT_TxtI, VT_TxtO, VT_Rec, VT_Ci64, VT_Co64} TValueType;
Object value type. The important types of communication:
- VT_Ai - real input
- VT_Ao - real output
- VT_Ci - integer input (if the value fits into a 32-bit integer)
- VT_Co - integer output (if the value fits into a 32-bit integer)
- VT_Ci64 - integer input (if the value does not fit into a 32-bit integer)
- VT_Co64 - integer output (if the value does not fit into a 32-bit integer)
- VT_Di - digital input
- VT_Do - digital output
- VT_TiA - absolute time input
- VT_ToA - absolute time output
- VT_TiR - relative time input
- VT_ToR - relative time output
- VT_Qi - quaternary input
- VT_TxtI - text input
- VT_TxtO - text output
This value must not be changed!
uvFlags
#define VF_A 0x0001 #define VF_B 0x0002 #define VF_C 0x0004 #define VF_D 0x0008 #define VF_E 0x0010 #define VF_F 0x0020 #define VF_G 0x0040 #define VF_H 0x0080 #define VF_I 0x0100 #define VF_J 0x0200 #define VF_K 0x0400 #define VF_L 0x0800 #define VF_M 0x1000 #define VF_N 0x2000 #define VF_O 0x4000 #define VF_P 0x8000
Implementation can optionally set up arbitrary combinations of 16 user flags ABCDEFGHIJKLMNOP of I/O value. Values of the flags are from VF_A up to VF_P.
uvValTime
The timestamp of the current value.
uvProcAlarmlTime
The timestamp of the last change of process alarms flag. Do not change!
uvBoval
The current value of digital input or output Di and Do.
Values:
- D_False - FALSE
- D_True - TRUE
- D_Oscillate - oscillating value – do not set, it is analyzed and set by the D2000 KOM process!
uvIntval
The current value of integer input or output Ci and Co. The value is set if uvValType is VT_Ci or VT_Co, i.e. if the integer input/output fits into a 32-bit integer.
Note: uvIntval has been used for integer input or output Ci and Co values in the past when these types were defined as 32-bit Integer. After switching to 64-bit Integer, the D2000 KOM process sets uvValType to VT_Ci or VT_Co when the value fits in 32 bits, and as VT_Ci64 or VT_Co64 when it does not, for compatibility reasons.
Note: The value written by the OEM protocol can be of type VT_Ci64/VT_Co64 (always) or of type VT_Ci/VT_Co (if the value fits into 32 bits).
uvIntval64
The current value of integer input or output Ci and Co. The value is always set for I/O tags of the Ci and Co type (regardless of whether the uvValType is VT_Ci/VT_Co or VT_Ci64/VT_Co64).
Note: this behaviour makes it easier to work with protocols that support writing 64-bit integers - the value being written is always in uvIntval64 (and if it fits in 32 bits, it is also in uvIntval).
Note: The value written by the OEM protocol can be of type VT_Ci64/VT_Co64 (always) or of type VT_Ci/VT_Co (if the value fits into 32 bits).
uvRealval
The current value of real input or output Ai and Ao.
uvStationval
Station status – not used, do not change!
typedef enum {ST_ON, ST_OFF, ST_COMERR, ST_HARDERR, ST_SIMUL, ST_WAIT} TStVal;
uvTmAval
The current value of absolute time input and output TiA and ToA.
uvTmRval
The current value of relative time input an output TiR and ToR.
uvQval
The current value of quadrat input Qi.
typedef enum {Q_Trans, Q_Off, Q_On, Q_Err, Q_Oscillate} TQVal;
Possible values are Q_Trans, Q_Off, Q_On, Q_Err or Q_Oscillate. Do not use the value Q_Oscillate, it is set by the process D2000 KOM in case of evaluation of oscillation.
uvTxtval
Pointer to a string of current value of text types TxtI a TxtO.
Note: The communication process allocates its own copies of text variables' values after calling the function PointNewValue.