System tags

System tags are objects, values of which are calculated, or detected by process D2000 Server on the basis of their definition. Values are calculated periodically or on change.

Usage of system tags in D2000 system (examples):

  • controlling of output tags in the AUTO mode
  • operands in logical a arithmetical expressions
  • operands in conditions to raise and finish alarms
  • displaying in pictures
  • displaying in graphs

The following system tags are implemented in D2000 system at the time of creating this documentation:

Name Type Period Meaning
ActNrDynamicObject Integer 60 s Current number of dynamic object in the system.
ActTagNr Integer on change Current number of tags in the application.
ActTransListNr Integer 1 s Number of active transactions that have been opened by D2000 Server.
Act_Client Integer on change Number of connected clients.
AllocatedMem Integer 10 s Allocated memory size [kB].
ArchivChange   not calculated Change of values in the archive.
CPU_Load Integer 1 s Processor load [%] of the process D2000 Server.
Note: This is a total average processor load which is computed by following formula:
(user_time + kernel_time)/TimeFromStart
Day Integer 24 h Current day
DiskSpace Integer 30 s Free disk space [kB]
FreeMem Integer 10 s for Win32 - Free memory size [kB]
for VMS - Remaining paging file quota of process D2000 Server in pagelets (on Alpha systems)
Hour Integer 1 h Current hour
IN_QUEUE Integer not calculated Number of requests for D2000 Server
LogFileSize Integer 15 min Log database size [kB]
Min Integer 1 min Current minute
Month Integer 24 h Current month
Pending_Cfg_Rq Integer 10 s Number of queued write requests for the configuration database. These requests may cause a configuration change, alarm blocking or a value change of the object with enabled start value saving.
Pending_Monitor_Rq Integer 10 s Number of queued write requests for the log database.
Perf_Cfg_Rq Integer 10 s Number of executed configuration database write requests per second.
Perf_Kernel_Rq Integer 10 s Number of executed requests for process D2000 Server per second (message processing rate per second).
Perf_Monitor_Rq Integer 10 s Number of executed log database write requests per second.
ProcAlarmsNr Integer on change Number of active process alarms
Sec Integer 1 s Current second
Signal_Trigger Boolean on change Start signal of trigger. The system will generate the impulse of the value of TRUE on this system tag according to configuration of system or process alarms - the parameter Raise Signal.
SysAlarmsNr Integer on change Number of active system alarms.
SystemError     System error information. Value of the variable is set by the system - D2000 Server and D2000 system processes. Value of the variable shows the last warning. Each value change sets process alarm of the object. The text in the columns Event description (the Alarm list window in process D2000 HI) and Incident (the Logging window in process D2000 HI) for process alarm is controlled by the display mask of the alarm - SM.SystemError (predefined value of the mask is {V} - so it copies object value). Occurrence of a system error is signalized by process alarm and history is stored in the log database.
SystemWarning     System warning information. Value of the variable is set by the system - D2000 Server and D2000 system processes. Value of the variable shows the last warning. Each value change sets process alarm of the object. The text in the columns Event description (the Alarm list window in process D2000 HI) and Incident (the Logging window in process D2000 HI) for process alarm is controlled by the display mask of the alarm - SM.SystemError (predefined value of the mask is {V} - so it copies object value). Occurrence of a system error is signalized by process alarm and history is stored in the log database.
SysTime Time 1 s System time
TimeFromStart Relative time 10 s Time from starting the D2000 system.

Note: For redundant D2000 systems, it is the running time of HS (Hot Server).

UpTime Relative time 10 s Running time of redundant D2000 system.

Note: For non-redundant D2000 systems - UpTime = TimeFromStart.

WeekDay Integer 24 h Day in week
Year Integer 24 h Current year