Fisher-Rosemount RS3 RNI communication protocol
Supported device types and versions
Communication line configuration
Communication station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions
Supported device types and versions
The protocol allows reading and writing data into Fisher-Rosemount RS3 system by means of RNI Ethernet network driver (Remote Network Interface) -there is used TCP/IP network communication.
Communication uses the following methods for data acquisition from RNI:
- DDS: Dynamic Data Server – acquisition of process tag values when they change.
- RW Services: Read/Write Services – used for value writing into RS3.
The methods are described in the Fisher-Rosemount Systems RNI Programmer’s Manual documentation, Software Version 2.3, April 1997.
Communication line configuration
- communication line category: API,
- The other parameters - see the D2000 System configuration.
Communication station configuration
- communication protocol: Fisher-Rosemount RNI.
- Station address consists of the following parameters :
RNI Name – RNI name allows to find RNI IP address (in the OS Win NT, the name together with the IP address is stored in the file %SystemRoot%\system32\drivers\etc\hosts)
Name – user access name (it is configured together with access rights on the boot PC for RNI in the file userfile.cfg – see the RNI configuration manual)
Password – password to given access menu
You must pay attention when you select the user's access right (D2000 KOM) - if there is required writing to RS3, the user access rights must be CONFIGURE.
I/O tag configuration
Possible types: Ai, Ao, Ci, Co, Di, Do, TiA
Address is the name of of I/O RS3 tag. For analog I/O tags, the address can be defined in the following forms:
SYSTEM_3_TAG_NAME
SYSTEM_3_ADDRESS
SYSTEM_3_TAG_NAME.COMMAND
SYSTEM_3_ADDRESS.COMMAND
For example:
AI-701 - AI-701 tag output (Q)
=1H-01 - tag output (Q) =1H-01
AI-701.B - B input of AI-701 tag
=7A-02.@ - all @ tag flags =7A-02 as 16-bit unsigned integer
For digital tags, the I/O address can be defined in the following forms :
SYSTEM_3_TAG_NAME.COMMAND\FLAG
SYSTEM_3_ADDRESS.COMMAND\FLAG
Or if COMMAND is @:
SYSTEM_3_TAG_NAME.@FLAG
SYSTEM_3_ADDRESS.@FLAG
For example:
AI-702.U\d
=1H-1.U\c
AI-702.@e
=1H-1.@a
Note:
- RS3 tag name is each valid tag name.
- RS3 address is in form of =NXXNNN for I/O blocks and =NX-NN for control blocks, where N is a number and X is a character.
- System flags and User flags that are read as analog values are represented by 16-bit unsigned integer.
The following table contains valid ‘command’ names for RNIDDE. The first column contains the short name of RS3 I/O tag as the letter of T, the tag name is followed by the character (.) and a ‘command‘.
Item name | D2000 type | I/O | Comment |
---|---|---|---|
T or T.Q | AI, AO | I/O | Output Value |
T.VS | CI | I | System Flags – all |
T.MD | CI, CO | I/O | Block Mode |
T.A up to T.O | AI, AO | I/O | Input Values |
T.U | CI, CO | I/O | User Flags – all |
T.U\a up to T.U\p or
T.Ua up to T.Up or T.a up to T.p |
DI, DO | I/O | User Flag – individually |
T.@ | CI | I/O | Discrete Inputs – all |
T.@a up to T.@p | DI | I/O | Discrete Input – individually |
T.TS | CI | I | T System Flags |
T.UMD | CI | I | User Modes |
T.SA up to T.SO | CI | I | System Flags A – O |
T.UA up to T.UO | CI | I | User Flags A – O |
T.ATP | AI | I | Auto Tune Phase |
T.AGF | AI | I | Actual Gain Factor |
T.CGF | AI | I | Calculated Gain Factor |
T.AIT | AI | I | Actual Integral Time |
T.CIT | AI | I | Calculated Integral Time |
T.ADT | AI | I | Actual Derivate Time |
T.CDT | AI | I | Calculated Derivate Time |
When you configure an I/O tag, you must select one of four radio buttons (UR1 to UR4) of the parameter Update rate. The update rate is used by the DDS service and defines a data read period from RS3. The update rate is configured on the boot computer in the file dds.cfg.
Literature
-
Changes and modifications
-
Document revisions
- Ver. 1.1 – February 9th 2000 – Document update.