D2000 GateWay Client may be configured also for direct transfer of values of selected objects from the source D2000 System (shows data through the D2000 GateWay Server) to the destination one without need to configure objects of "Remote tag" type.

This transparent gateway enables transferring values of these types of D2000 objects:

The value transfer is executed only on the basis of verification of object match between D2000 Systems. To transfer the values, select the particular objects or group of objects filtered by mask and then enter them to the start parameters of GateWay Client process.

The destination system tries to verify whether the required objects exist in the source system and if so, it ensures transferring value of these objects. If the source system does not contain the particular object, it will have the invalid value in the destination system.
If the list of objects is changed (any object is added or deleted) while running the GateWay Client in the destination system, which corresponds with mask, the proper action is executed towards the source system (logging on / off of object).

Any values are not transferred from the destination system to the source one. The value transfer is always unidirectional.

The structured variables can be transferred only as whole.

There is not supported the feature Destination column for I/O tags. A user must select the values of given destination structure that are to be transferred.

GateWay Client process may be executed both as it is defined for remote tags and as the transparent gateway.


Use of transparent gateway

The transparent gateway is a temporary solution providing that:

  • there are done the changes or modifications of functional and used system, which are first tested on a parallel system,
  • there is executed the test of a new hardware when upgrading the existing system,
  • other testing or debugging purposes.

Limitations

You should realize that the transparent gateway assigns the values to objects those administrative processes in DODM system. Therefore, these processes must be stopped in the destination D2000 System. It concerns the communication processes and calculation processes.

The user cannot change the value on the destination D2000 System (commanding values). As the administrative communication process does not run, the setting of value ends with error.


Start parameters

To activate the transparent gateway, start GateWay Client with one or more /ROV parameters.

Syntax:    /ROVobj_mask1[+][,][obj_mask2][+][,]......

/ROV parameter is followed by a name (or more names separated by a comma) of object or mask for more objects. To transfer the object values together with the child, add '+' (plus) character at the end.

Examples:

/ROVSELF.KOM+ Ensures the value transfer of the SELF.KOM process together with its children (lines, stations, I/O tags).
/ROVM.*  It is used for value transfer of I/O tag which name starts according to the ordinary naming 'M.'. 
/ROVM.OBJ1,M.OBJ2  Value transfer of objects M.OBJ1 and M.OBJ2. 

Filtering of process alarms

When transferring the values to the destination system, the values of process alarms are usually filtered. To transfer values together with the process alarms, start GateWay Client with the /ROA parameter.


Diagnostic information

To activate the detailed debug information, start GateWay Client with these parameters:

/E+DBG.GTW_TR  Enables listing of the debug information about the objects when executing of the transparent gateway. 
/E+DBG.GTW_TR.VAL  Enables listing of the debug information about the value transfer of selected objects to the destination system. 

This listing of debug information can be enabled /disabled also while running the GateWay Client through the D2000 System Console.

Tell command TRGTW

After receiving the TRGTW command, GateWay Client lists the status of all required objects.

Related pages:

Napíšte komentár