ALYA Lubrications communication protocol
Supported device types and versions
Communication line configuration
Communication station configuration
I/O tag configuration
Literature
Document revisions
Supported device types and versions
This protocol supports data reading/writing from the controllers of ALYA lubricant reservoirs.
Since July 2015, this protocol supports a group of I/O tags for data reading/writing from/to the Manex production lines - see Table 4.
Communication line configuration
- Communication line category: Serial,SerialOverUDP Device Redundant, TCP/IP-TCP
- Serial line parameters:
- Baud Rate: 38400 Baud
- Odd parity, 8 data bits, 1 stop bit
Communication station configuration
- Communication protocol: ALYA Lubrikacie.
- The station address is an address of the control station for the communication over RS485 bus. The address is a one-byte value.
Note: commonly used station addresses (A, B, C...) must be configured as their ASCII codes, i.e. 65, 66, 67 ...
Station protocol parameters
Communication station - configuration dialog box - "Protocol parameters" tab.
They influence some of the optional parameters of the protocol.
Table 1
Key word | Full name | Meaning | Unit | Default value |
---|---|---|---|---|
WT | Wait Timeout | Delay between the readings of response until it is completed. | ms | 100 millisec. |
WFT | Wait First Timeout | First waiting for a response after sending the request. | ms | 100 millisec. |
RT | Retry Timeout | The delay between the retry of a request if a communication error occurs. | ms | 100 millisec. |
MWR | Max Wait Retry | The number of response reading retry until it is completed. | - | 6 |
RC | Retry Count | The number of request retries in case of a communication failure. | - | 2 |
A string containing the protocol parameters must be written as follows:
Key_word=value;Key_word=value; ...
Example:
WT=150;MWR=10;
If a keyword with an invalid value in the initialization string is used, the corresponding default value according to the table 1 will be used.
I/O tag configuration
I/O tags: Ai, Ao, Di, Dout.
I/O tag address is an abbreviation of the mnemonic name of I/O object. The list of objects is shown in the table below:
Table 2
Address | Meaning | Value type | Read/Write |
---|---|---|---|
AV | Current weight [kg] | Ai | R |
HI | Emergency minimum [kg] | Ai, Ao | R/W |
HA | Emergency maximum [kg] | Ai, Ao | R/W |
PN | Operating minimum [kg] | Ai, Ao | R/W |
PX | Operating maximum [kg] | Ai, Ao | R/W |
SP | Filling status (TRUE - filling, FALSE - draining) | Di | R |
EN | Error number - see Table 3 | Ai | R |
WS | Write to serial EEPROM (all changes of Ao must be written to EEPROM - if not, they will be lost during the next reset) | Do | W |
RT | Reset (it causes the reset of the control station) | Do | W |
The list of error codes when reading the "EN" parameter:
Table 3
Error code | Meaning |
---|---|
0 | Weight is OK. |
1 | Weight is under the permitted range. |
2 | Weight is over the permitted range. |
3 | Weight is under the emergency minimum. |
4 | Weight is over the emergency maximum. |
10 | The weight converter does not respond. |
20 | The weight converter is not connected. |
30 | The strain gauge (tensometer) is not connected. |
I/O tags for data reading/writing from/to Manex production lines:
Table 4
Address | Meaning | Value type | Read/Write |
---|---|---|---|
RN | New weighted roving. After weighing and printing the weight ticket, the application writes a text string into the I/O tag in the format: ID;CV;VZ;POC;ZD; where:
| TxtO | Write |
RX | Canceling of a roving. After an operator puts down the roving from the scale, the application will write the number of the scale (1 or 2) into the I/O tag. | Co | Write |
PC | The number of spools on the lines. The I/O tag is in the format "C1;C2;C3; … Cn;", where Ci represents an integral number that indicates the number of spools on the line i. Example: "626;42;0;78;562;489;28;55;" | TxtI | Read |
NC | Reset the counters of spools on the lines. Write any valid value, to reset the counters. The control unit will send a message in the format "C1;C2;C3; … Cn;", where Ci represents an integer number that indicates the number of spools which were included on line i since the most recent information on the number of spools was sent (see PC). This message will be set as a new value of the I/O tag with the NC address. | TxtO | Write |
Literature
-
Document revisions
- Ver. 1.0 - August 21, 2001 - the creation of the document
- Ver. 1.1 - July 15, 2015 - support for Manex production lines
- Ver. 1.2 - January 25, 2023 - support for TCP/IP-TCP line
Related pages: