Configuration of system texts
Configuration of system texts is performed by means of
the process D2000 CNF.
The system texts are divided into the following categories:
The objects, values of which do not contain system texts:
- I/O tags of AI, AO, CI, CO, TiA, ToA, TiR, ToR, TmRo, TxtI a TxtO types
- Evaluated tags
- User variables of Integer, Real, TmA, TmR, Txt types
* Displaying of values of Integer, Real, Absolute time
and Time interval types might be controlled by transformation
palette.
Boolean values
Label in the system |
Predefined label |
Cause |
B_False |
False |
False value |
B_True |
True |
True value |
B_Oscillate |
Oscilate |
Oscillating value (TRUE <-> FALSE). |
Di, Do measured values
Label in the system |
Predefined label |
Cause |
D_False |
OFF |
False value |
D_True |
ON |
True value |
D_Oscillate |
OSCILATE |
Oscillating value (TRUE <-> FALSE). The system
sets the value as the oscillating one according to defined parameters of
filtering - Oscillation limits. |
Process object values
Label in the system |
Predefined label |
Cause> |
P_Run |
Run |
The process is running. |
P_Crash |
Crash |
The process is terminated by an error (incorrect
termination). If it is possible,
D2000 Server will try to start the process again. |
P_Stop |
Stop |
The process is correctly terminated. |
P_WDErr |
WDErr |
Error when communicating with
D2000 Server -
Watch Dog Error (interrupted flow of Watch Dog messages between the client
process and
D2000 Server). |
System alarm values
Label in the system |
Predefined label |
Cause |
A_Norm |
Normal |
The condition to raise the alarm is not met. |
A_Alarm |
Alarm |
The condition to raise the alarm is met. |
A_Kvit |
Kvit |
The alarm is acknowledged by operator. |
A_Block |
Block |
The alarm is blocked by operator, or at the
alarm configuration is enabled Blocked alarm option. |
A_UnBlock |
UnBlock |
The process
D2000 Alarm is not running and operator
unblocks the given alarm in Blocked state. |
A_NoKvit |
NoKvit |
The condition to finish the
acknowledge-required
alarm is met before its acknowledgement. |
Station values
Label in the system |
Predefined label |
Cause |
St_On |
ON |
The station communicates |
St_Off |
OFF |
The station does not communicate. The
communication is disabled by operator (via the control window in
process D2000 HI) or at the station configuration in the process
D2000 CNF. |
St_CommErr |
COMERR |
The occurrence of a "soft"
error of the communication. Such error is occurred after an unsuccessful
data transmission. |
St_HardErr |
HARDERR |
The occurrence of "hard" error of the
communication. Such error is occurred, if the communication with station is
in StCOMERR state within the period given by Time filter parameter.
If the station value is StHARDERR,
then all the I/O tags of the station will pass to undefined state.
|
St_Simul |
SIMUL |
Communication with the station is simulated. |
St_Wait |
WAIT |
The station is in AUTO mode. Communication is
stopped. The control object value is TRUE. Requests for output are postponed
and they will be executed when the control object value will be FALSE. |
Qi measured values
Label in the system |
Predefined label |
Cause |
SwTrans |
TRANS |
Change of quadrature value from TRUE into FALSE or
vice-versa. |
SwOff |
OFF |
False value |
SwOn |
ON |
True value |
SwErr |
ERROR |
Invalid (illegal) value. |
SwOsc |
OSCILATE |
Oscillating value (TRUE <-> FALSE). The system
sets a value as the oscillating one according to defined parameters of
filtering - Oscillation limits. |
Process alarms
Label in the system |
Predefined label |
Cause |
NoAlarm |
NoAlarm |
No process alarm is active |
ToTrue |
ToOn |
Process alarm occurred - change into ON
(TRUE) level. |
ToFalse |
ToOff |
Process alarm occurred - change into OFF (FALSE)
level. |
True |
On |
Process alarm occurred - ON (TRUE) level. |
False |
Off |
Process alarm occurred - OFF (FALSE) level. |
Invalid |
Err |
Invalid (illegal) value. |
Oscillate |
Oscillate |
Oscillating value. |
HL |
HL |
Process alarm occurred - limit state of HL
value. |
VHL |
VHL |
Process alarm occurred - limit state of VHL
value. |
LL |
LL |
Process alarm occurred - limit state of LL
value. |
VLL |
VLL |
Process alarm occurred limit state of VLL
value. |
ToHL |
ToHL |
Process alarm occurred- value change into
HL limit state. |
ToVHL |
ToVHL |
Process alarm occurred- value change into VHL limit state. |
ToLL |
ToLL |
Process alarm occurred - value change
into
LL limit state. |
ToVLL |
ToVLL |
Process alarm occurred - value change
into VLL limit state. |
SwToTrans |
SwToTrans |
Process alarm occurred - change of quadrat value
into Q_Trans value. |
SwToOff |
SwToOff |
Process alarm occurred- change of quadrat value
into Q_Off (FALSE) value. |
SwToOn |
SwToOn |
Process alarm occurred- change quadrat value
into Q_On (TRUE) value. |
SwToError |
SwToErr |
Process alarm occurred - change of quadrat value
into Q_Err value. |
SwTrans |
SwTrans |
Process alarm occurred- quadrat value is Q_Trans. |
SwOff |
SwOff |
Process alarm occurred - quadrat value is Q_Off. |
SwOn |
SwOn |
Process alarm occurred - quadrat value is Q_On. |
SwError |
SwErr |
Process alarm occurred - quadrat value is Q_Err. |
ErrorWriteCmd |
ErrWriteCmd |
Error at the setting of output tags. |
Sw_ErrorCmdOn |
ErrCmdOn |
Error during cm_SetSwitchOn command
execution. |
Sw_ErrorCmdOff |
ErrCmdOff |
Error during cm_SetSwitchOff command execution. |
Sw_ErrorBkpCmdOff |
ErrZalCmdOff |
Error during cm_SetSwitchBkpOff command execution. |
Change |
Change |
Process alarm occurred - change of integer or analog value. |
SysPrAl |
SysProcAlarm |
Special type of process alarm used
just for two objects of System variable
type - SystemError
and SystemWarning. |
Value limits
Label in the system |
Predefined label |
Cause |
Is_InLimit |
InLimit |
The object value is at once greater or equal to
LL and less or equal to HL (LL<=values<=HL). |
Is_VL_Limit |
VL_Limit |
The object value is less than VLL (value<VLL). |
Is_L_Limit |
L_Limit |
The object value is at once greater or equal to VLL and
less than LL (VLL<=value<LL). |
Is_H_Limit |
H_Limit |
The object value is at once greater than HL and
less than VHL (HL<value<=VHL). |
Is_VH_Limit |
VH_Limit |
The object value is greater than VHL (VHL<value). |
Is_LimitsProblem |
LimitsProblem |
In case of dynamic limits, there is the validity
mismatch of the conditions: VLL<LL<HL<VHL. |
Value states
Label in the system |
Predefined label |
Cause |
s_val_Invalid |
Invalid |
Invalid object value. |
s_pa_Alarm |
ProcAlarm |
The state is occurred in case that the given
object has an active process alarm. |
s_pa_NoAck |
NoAckPAlarm |
The state is occurred in case that the process
alarm is not acknowledged by operator in process D2000 HI. |
s_pa_Blocked |
PrAlSilent |
The state is occurred in case that the given
object has not any active process alarm, or Silent option is enabled
at configuration of object process alarms in the process
D2000 CNF. |
s_val_Weak |
Weak |
Weak (suspicious) value is a value not valid in
the system, because all the conditions of its validity are not met. |
s_val_NoAck |
NoAckValue |
The state is occurred in case that the last
object value change is not acknowledged by operator in process D2000 HI. |
s_val_Transient |
Transient |
Transient state of the value is occurred, if
the command that sets the object value was executed, but backward reading has
not yet verified the value setting. |
s_val_Default |
Default |
Default state of the object value is occurred,
if the I/O tag value gained by the process
D2000 KOM is replaced by other
value - the control object value, or is manually set by operator in
process D2000 HI. |
s_val_Manual |
Manual |
The object value is in Manual state, if it is
manually set by operator in process D2000 HI. |
s_pa_Critical |
PrAlCrit |
The status is occurred in case that the process
alarm is defined as critical one in the process
D2000 CNF. |
s_pa_Unknown |
Unknown |
|
Operator commands
Label in the system |
Predefined label |
Cause |
cm_SetDefautManual |
SetDefMan |
Manual setting of the object default value. |
cm_SetDefautAuto |
SetDefAuto |
Activation of the automatic mode of the object
default value control. The default value in this mode will be copied the
control object value. |
cm_SetManual |
SetManual |
Manual setting of output object value. |
cm_SetAuto |
SetAuto |
Activation of the automatic mode of the output
object value control. The object value in this mode copies the control
object value. |
cm_SetDefaultOff |
SetDefOff |
Cancel the validity of the object default
value. |
cm_SetSwitchBlockAOn |
SetBlockAOn |
Activation of
blockade A of the switch. |
cm_SetSwitchBlockAOff |
SetBlockAOff |
Deactivation of
blockade A of the switch. |
cm_SetSwitchOn |
SetSwitchOn |
Switch on the switch. |
cm_SetSwitchOff |
SetSwitchOff |
Switch off the switch. |
cm_SetSwitchBkpOff |
SetSwitchBkpOff |
Backup switch off the switch. |
cm_SetSwitchBlockBOn |
SetBlockBOn |
Activation of
blockade B of the switch. |
cm_SetSwitchBlockBOff |
SetBlockBOff |
Deactivation of
blockade B of the switch |
cm_SetSwitchNormalOff |
SetSwitchNormalOff |
Set the switch to the normal state - OFF. |
cm_SetSwitchNormalOn |
SetSwitchNormalOn |
Set the switch to the normal state - ON. |
cm_SetSwitchNormalNone |
SetSwitchNormalNone |
Set the switch to the normal state - NONE. |
Alarm commands
Label in the system |
Predefined label |
Cause |
cm_AlarmKvit |
Kvit |
The alarm is acknowledged by operator. |
cm_AlarmBlock |
Block |
The alarm is blocked by operator, or Blocked
alarm option is enabled at its configuration in the process
D2000 CNF. |
cm_AlarmUnblock |
Unblock |
The alarm is unblocked by operator. |