ABB SPA-Bus communication protocol
Supported device types and versions
Communication line configuration
Communication line parameters
Station configuration
Station parameters
I/O tag configuration
Literature
Changes and modifications
Document revisions
Supported device types and versions
A protocol support data reading / writing from the digital protection modules of ABB VN devices.
Communication line configuration
- Communication line category: Serial, SerialOverUDP Device Redundant.
- Transmission parameters are set to 9600 Baud, 7 data bites, even parity, 1 stop bit.
Communication line parameters
Communication line - configuration dialog -
Protocol parameters tab.
The parameters influence some optional
protocol parameters. The following protocol line parameters can be used:
Table 1
Parameter | Meaning | Unit / Size | Default value |
---|---|---|---|
Software 7E1 | Parameter starts a software generation and even parity check. A transmission device parameters can be set on 8N1 (i.e. 8 bits, no parity, 1 stop bit) instead of 7E1 (7 bits, even parity, 1 stop bit) which is commonly used in SPA-Bus protocol. | YES/NO | NO |
Moxa Redundancy Check Timeout | Switching time in Moxa redundant devices in case of a communication error. This parameter is only relevant for SerialOverUDP Device Redundant line. | sec | 5 sec |
Max. Data Number Optimization | Optimization data reading at polling. If there are I/O tags with Data Number successive addresses, the polling is executed together until the value of this parameter is reached (i.e. if the value is 3, three I/O tags will be polled together). Value 1 switches an optimization off, each I/O tag is polled separately. | 1 .. 32 | 1 |
Time T Broadcast Periode | Time T synchronization packet sending by broadcast at the address 900. When the parameter is 0 sec., the time synchronization sending is disabled. | 0 .. 60 sec | 10 sec |
Expected T Packet Transmission Duration | Expected duration of T synchronization packet transmission by all the transmitting devices until the whole packet is received in own protection devices. This time is added to a current time when packet is being sent so that the time in packet is also a current time in the moment of the packet complete receiving by the device. | msec | 20 msec |
Date and Time D Broadcast Periode | Duration of Time and Date synchronization packet sending by broadcast on the address 900. When the parameter is 0 sec., the synchronization sending is disabled. | 0 .. 3600 sec | 60 sec |
Expected D Packet Transmission Duration | Expected duration of Time and Date synchronization packet sending by all the transmitting devices until the packet is received completely in own protection device. This time is added to a current time when packet is being sent so that the time in packet is also a current time in the moment of the packet complete receiving by the device. | msec | 35 msec |
Station configuration
- Communication protocol: ABB SPA-Bus.
- Station address is a number in the range of 1 to 999, 0 is not used, 900 is reserved for broadcast.
- Time parameter settings - Polling parameters, are ignored, polling of the values is executed in the shortest period.
- Time parameter - Synchronization time, is ignored, a real time synchronization via the broadcast messages is controlled by the protocol line parameters "Time T Broadcast Period" and "Date and Time D Broadcast Period".
Station parameters
Communication station - Protocol
parameters tab.
The parameters influence some optional protocol parameters. The following
protocol line parameters can be used:
Table 2
Parameter | Meaning | Unit | Default value |
---|---|---|---|
Retry Count | Retry count of the request in case of a communication failure. | 1 .. 20 | 2 |
Retry Timeout | Delay between a request retry in case of a communication failure. | msec | 20 msec |
Wait First Timeout | First waiting on response after sending the request. | msec | 50 msec |
Wait Timeout | Delay between reading the response until its completing. | msec | 20 msec |
Max. Wait Retry | Retry count of response reading until its completing. | - | 20 |
Recovery Delay | Communication with station is delayed by defined time in case of communication error. If a line contains more stations (protective devices) and one of them will fail, it can slow down the communication of other functional stations. Next recovery of the communication with station will be delayed by a defined value (time). If the line contains only one station, the parameter value should be 0 sec. | sec | 10 sec |
Poll Events | Enables a periodic event reading by the function "Last events L". A time synchronization of the protective device must be also enabled. See the parameters "Time T Broadcast Periode" and "Date and Time D Broadcast Periode". | YES/NO | YES |
Value For Invalid Position | Integral value of "ERROR" state for conversion to a quadrat input Qi. | 0, 1, 2, 3 | 3 |
Value For Off/Open Position | Integral value of "OFF" state for conversion to a quadrat input Qi. | 0, 1, 2, 3 | 1 |
Value For On/Close Position | Integral value of "ON" state for conversion to a quadrat input Qi. | 0, 1, 2, 3 | 2 |
Value For Intermediate Position | Integral value of "TRANS" state for conversion to a quadrat input Qi. | 0, 1, 2, 3 | 0 |
Date Conversion Mask | Conversion mask to convert a date. | yyyy-mm-dd | |
Time Conversion Mask | Conversion mask to convert a time. | hh.mi;ss.mss | |
Debug Values | Starts a debug info about I/O tag values obtained by polling. | YES/NO | NO |
I/O tag configuration
Possible value types: Ai, Ao, Ci, Co, Di, Dout, Qi, TxtI, TxtO, TiA, ToA, TiR, ToR.
I/O tag address items:
- Channel: channel number is required numerical address parameter intended for all data categories except for F and C.
- Category: data category code; if it is unknown, write "Not
defined", if it is known, you can choose one of the following data
categories:
- Input data I
- Output data O
- Setting Values S
- Variable V
- Memory data M
- Slave identification F
- Slave status C
"Slave Identification F" and "Slave Status C" are unique. No other address parameter is required.
-
"Slave identification F" returns 10 signs which identifies a device. We recommend to configure it as I/O tag of TxtI type.
-
"Slave status C" returns the numbers 0, 1, 2 or 3. See also Note 1.
- Data Number: required numerical address parameter for all data categories except for F and C.
- Poll: enables a periodic polling for all data categories except for "Not defined". The data category "Slave identification F" does not required the polling because it is static. If the periodic polling is disabled, the object is polled while starting the communication or when I/O tag value is unknown.
- Event code - Intermediate position (00): a numerical event address when object is in "Intermediate position". Set "TRANS" for Qi I/O tag type or a number according to parameter "Value for intermediate position" for I/O tags of Ai, Ao, Ci, Co types. A configuration is not allowed for I/O tags of Di, Dout types.
- Event code - Off/Open position: a numerical event address when the object passes to "Off/Open position". Set "OFF" for Qi I/ tags or the number according to parameter "Value for Off/Open position" for Ai, Ao, Ci, Co I/O tags.
- Event code - On/Close position: a numerical event address when the object passes to "On/Close position". Set "ON" for Qi I/O tags or the number according to parameter "Value for On/Close position" for Ai, Ao, Ci, Co I/O tags.
- Event code - Invalid position (11): a numerical event address when the object passes to "Invalid position". Set "ERROR" for Qi I/O tags or the number according to parameter "Value for invalid position" for Ai, Ao, Ci, Co I/O tags. The configuration is not allowed for Di, Dout I/O tags.
Note 1
When E50 (slave reset) event or E51
(slave event buffer overflow) occur, the value 0 is written to "Slave status C"
aside from the I/O tag of C category exists or not.
Literature
- SPA-Bus Communication Protocol V2.5, Technical description, Version C, 1MRS 750076-MTD EN.
Changes and modifications
Document revision
- Ver. 1.0 - November 21st, 2010 - Document creation.
Related pages: