AMiT ATOUCH32 DB-Net communication protocol

Supported device types and versions
Communication line configuration
Communication station configuration
DB-Net initialization
I/O tag configuration
Errors and problems
Literature
Changes and modifications
Document revisions

Supported device types and versions


The protocol supports data acquisition using devices from the AMiT company (ADiS modular control system and ART267, ART4000, AMiRiS, and AMAP compatible control systems and others) via a DB-Net communication network. Communication requires the installation of the ATOUCH32 driver to communicate in a DB-Net ATOUCH32 network (you can download it at http://www.amit.cz). Communication was tested and tuned for the ATOUCH32 driver of V2.10, V2.30, V2.40, V2.60, V2.90, and V3.30 versions.

Limitations: The protocol does not support database variables of "self station", i.e. on the computer with ATOUCH32 driver running but allows to read/write variables on process stations. The DB-Net driver can be used by just one application (in our case the D2000 KOM process) at the same time.

When using the older versions of ATOUCH32 V2.x, just one communication line for DB-Net communication must be configured. ATOUCH32 V3.x versions enable so-called multithreading. It means, you may connect more lines, which will communicate in parallel, to ATOUCH32 and speed up the communication. The driver must be initialized only by one line (see "Init File" parameter, note 2). However, the rule that all lines must be configured within one KOM process on one computer still applies. This feature may be used in D2000 V9.00.021 rel.021 and higher.

Communication line configuration



Communication line parameters

Communication line - configuration dialog box - the Protocol parameter tab.
Parameters defined in the field have an effect on some optional protocol parameters. The following line protocol parameters can be defined:

Table 1

Full nameDescriptionUnits / sizeDefault value
HW Init File
Full path to the file containing the DB-Net configuration.

Note 1:
If the line protocol parameter INIFILE is not specified (an empty string), then the station protocol parameters described below must be configured correctly for all stations. The parameters of DB-Net IP can be configured only by "Init File".

Note 2: If you do not want so that the line initialized ATOUCH32 in the multithread mode, use "---", i.e. 3x "minus" character. One line within the D2000 KOM process must contain the path to the existing init file. It, then, executes the initialization for all other lines.
-

Communication station configuration



Communication station parameters

Communication station - configuration dialog box - tab Protocol parameter.
Parameters defined in the field influence some optional protocol parameters. The following station protocol parameters can be defined:

Table 2

Full nameMeaningUnit/ sizeDefault value
My Station
Address of "self station" (PC with ATOUCH32 driver running)-31
COM Port
COM port used for the communication-1
COM Speed
Communication baud rate.-19200
Max. Transactions Error
The maximum number of consecutive read commands which have to fail for the communication with the station to be marked as failed and the status of the station to be set to StCOMERR. If the number of failed readings of I/O tags exceeds the double of this value, the reading of the next I/O tags will be stopped. The purpose is to avoid communication delays due to non-working stations (the station is considered to be completely inaccessible).-10
Full Debug
High level of line debug messages - trace messages contain details about received values of I/O tags.-False
Enable Matrix Read
The reading of matrix variables will be optimized for slow networks (e.g. GPRS). Reading of variables with matrix types (INT MATRIX, LONG MATRIX, FLOAT MATRIX a DBNETTIME MATRIX) will be optimized. If multiple I/O tags share the same WID and type, only a single read request is generated and it incorporates a range of rows and columns of all these I/O tags.-False

DB-Net initialization


When starting, the DB-Net driver requires to get the configuration file or string containing the DB-Net network configuration for a particular application. If you use the communication via standard COM port, it is possible to avoid creating the configuration file on disk using the My Station, COM Port, and COM Speed station protocol parameters which must be configured for one of the stations.

If the Init File line protocol parameter is specified for a line (at least one), then the My Station, COM Port, and COM Speed protocol parameters will be ignored on all the stations. Instead, the configuration file on the disk (the path of which is defined by the Init File line protocol parameter) will be used.
For further information on the file contents, see the ATOUCH32 online help.

Example: configuration file contents:

[General]
MyStation=0
UDP.MyPort=222
UDP.MyPassword=111222333

[COM]
Com=2
Speed=38400
Station=1
Station=2
Station=4
Station=13

[COM]
Com=3
Speed=9600
OfsNet=32
Station=33
Station=34
Station=36
Station=45 

[UDP]
Address=192.168.168.1
Password=444555666
Offset=10
Station=10
Station=20
Station=30

[UDP]
Address="segment100.firmaXY.cz"
Password=777888999
Port=333
Offset=100
Timeout=5000
Station=105
Station=106
Station=107

I/O tag configuration


Possible I/O tag types: Ai, Ao, Ci, Co, Di, Do, TxtI, TxtO, TiA, ToA, TiR, ToR.

I/O tag address consists of:

Errors and problems


When starting or during communication, the following error messages can occur. To make the problem identification easier, set the communication tracking at least to the level Monitor (the best is to temporarily set it to Monitor & Disk). When you set the option Monitor & Disk, a file "line_name.LOG" will be created in the application subdirectory TRACE, which will contain all debug and error logs. If you are unable to correct the error and the problems still persist, please contact  IPESOFT's technical support.

Error:DB-Net Station Address Error - 'StationName', Address : 'StationAddress'
Solution:Invalid station address - check the Address tab in the communication station configuration dialog box (in the D2000 CNF process) and eventually save the station configuration and restart the D2000 KOM process.
Error:DB-Net Point Address Error - 'PointName', Address : 'PointAddress'
Solution:Invalid I/O tag address - check the Address tab in the I/O tag configuration dialog box (in the D2000 CNF process) and eventually save the I/O tag configuration.
Error:DB-Net ATOUCH32 ERROR - 0xXY - AtchInitFromStringA
Solution:Error when calling the ATOUCH32 function AtchInitFromStringA - check the station configuration and protocol parameters. During the start, the D2000 KOM process displays the configuration string (the communication tracing level at least Monitor must be enabled) - please check if it corresponds to your requirements.
Error:DB-Net ERROR - CreateSemaphore - ErrNr - Error description
Solution:System error of Windows API call. Restart the operating system.
Error:DB-Net ATOUCH32 ERROR - 0xXY - AtchReqGetVariable
DB-Net ATOUCH32 ERROR - 0xXY - AtchReqPutVariable
Solution:Error when calling the ATOUCH32 functions AtchReqGetVariable or AtchReqGetVariable for reading/writing a DB-Net database variable value. Previous communication tracing logs allow us to detect which I/O tag is in trouble and then its configuration can be checked.
Error:DB-Net ERROR - Reading 'PointName' - TNRES=0 !
DB-Net ERROR - Reading 'PointName' - TNRES=1 (reading on progress) !
DB-Net ERROR - Reading 'PointName' - TNRES=Invalid !
DB-Net ERROR - Writing 'PointName' - TNRES=0 !
DB-Net ERROR - Writing 'PointName' - TNRES=1 (reading on progress) !
DB-Net ERROR - Writing 'PointName' - TNRES=Invalid !
Solution:Transaction errors of reading/writing the DB-Net database variable. They should not occur.
Error:DB-Net ERROR - Reading 'PointName' - TNRES=4 (station not responded) !
DB-Net ERROR - Writing 'PointName' - TNRES=4 (station not responded) !
Solution:Transaction errors of reading/writing the DB-Net database variable. The station doesn't respond because it is switched off, there is a problem with the communication wire or a configuration error (e.g. wrong baud rate, address or port). The error could occur sporadically, especially at reading.
Error:DB-Net ERROR - Reading 'PointName' - TNRES=4 (station responded) !
DB-Net ERROR - Writing 'PointName' - TNRES=4 (station responded) !
Solution:Transaction errors of reading/writing the DB-Net database variable. The station responded with an error. Probably it is an attempt to read or write a variable, which does not exist in a device. Check the configuration of the corresponding I/O tag and compare it with the log from the AMiT PSP3 software tool.
Error:DB-Net ATOUCH32 ERROR - 0xXY - AtchInitFromFileA
Solution:Error when calling the ATOUCH32 function AtchInitFromFileA. Check if the protocol parameter INIFILE is configured just for one station and its value is a name of an existing file on a disk.

Literature


Changes and modifications


Document revisions


Communication protocols