Supported device types and versions
Communication line configuration
Line protocol parameters
Communication station configuration
I/O tag configuration
Notes on Fanuc Robot R-30iA/R-30iB
Literature
Changes and modifications
Document revisions
The protocol is an implementation of the "Service Request Transport Protocol" developed by General Electric Automation and Controls (formerly GE Fanuc) for communication with PLCs. Almost all GE devices equipped with Ethernet port support GE SRTP. GE SRTP is a successor to the serial protocols SNP and SNPX for Ethernet media.
The protocol was tested against the Fanuc Robot R-30iB:
Note: if all of the stations are in StOFF mode (or in simulation), the TCP connection will be closed. Thus it is possible to control TCP communication from the event using an STSTAT tell command.
A dialog window of communication line configuration - Protocol parameters tab.
They influence some optional protocol parameters.
The following line protocol parameters are defined:
Parameter | Meaning | Unit / Size | Default value |
---|---|---|---|
Maximum Payload | Maximum size (in bytes) of data read by a single request. I/O tags whose addresses are consecutive will be grouped into reading requests so that the size of the response data does not exceed the configured value. | 1 až 1024 B | 100 B |
Cycle Delay | Waiting after reading of all I/O tags on a station. This parameter allows you to set read cycles less than 1 second (the time parameters configured on the station have a resolution of 1 second). | ss.mss | 100 ms |
Debug Values | Activates debug info about the read/written values of I/O tags. Use this parameter only when communication must be debugged because it highly utilizes CPU and slows down the communication. | YES/NO | NO |
Possible I/O tag types: Ai, Ci, Di, TiR,TxtI, Ao, Co, Dout, ToR, TxtO
I/O tag address has the format [+]MemoryArea Position[:StringLength] [Count]
MemoryArea specifies the type of memory:
MemoryArea | Memory type description | Data size |
---|---|---|
%IGNORE | I/O tag will be ignored. Note: arbitrary character can follow after %IGNORE e.g. %IGNORE +%R1 | - |
%I | InputBit (Discrete inputs, bit access-mode) | 1 bit |
%IB | InputByte (Discrete inputs, byte access-mode) | 1 byte |
%Q | OutputBit (Discrete outputs, bit access-mode) | 1 bit |
%QB | OutputByte (Discrete outputs, byte access-mode) | 1 byte |
%T | TemporaryBit (Temporary references, bit access-mode) | 1 bit |
%TB | TemporaryByte (Temporary references, byte access-mode) | 1 byte |
%M | MemoryBit (Internal references, bit access-mode) | 1 bit |
%MB | MemoryByte (Internal references, byte access-mode) | 1 byte |
%S | SBit (System status references, bit access-mode) | 1 bit |
%SSB | SByte (System status references, byte access-mode) | 1 byte |
%SA | SABit (System status references A, bit access-mode) | 1 bit |
%SAB | SAByte (System status references A, byte access-mode) | 1 byte |
%SB | SBBit (System status references B, bit access-mode) | 1 bit |
%SBB | SBByte (System status references B, byte access-mode) | 1 byte |
%SC | SCBit (System status references C, bit access-mode) | 1 bit |
%SCB | SCByte (System status references C, byte access-mode) | 1 byte |
%G | GlobalBit (Discrete globals, bit access-mode) | 1 bit |
%GB | GlobalByte (Discrete globals, byte access-mode) | 1 byte |
%AI | AnalogInput (Analog input registers, byte access-mode) | 2 bytes |
%AQ | AnalogInput (Analog output registers, byte access-mode) | 2 bytes |
%R | Registers (System register reference, byte access-mode) | 2 bytes |
%RD | RegistersDouble (System register reference, 2 registers as a double word) | 4 bytes |
%RF | RegistersFloat (System register reference, 2 registers as a floating-point) | 4 bytes |
%L | LocalSubblock (Local registers, byte access-mode) | 2 bytes |
%P | ProgramBlockData (Program registers, byte access-mode) | 2 bytes |
Note: the order of bytes and words is little-endian: B1 B2 for 2-byte types, B1 B2 B3 B4 for 4-byte types.
According to FANUC Robot series R-J3/R-J3iB/R-30iA CONTROLLER CIMPLICITY HMI for Robots OPERATOR’S MANUAL, chapter 6 - ADDRESS ASSIGNMENT TO POINTS, subchapter 6.1 - READING AND WRITING I/O SIGNALS (%I, %Q, %M, %AI, %AQ) different types of I/O signals are mapped to SRTP protocol variables as follows:
Robot controller I/O signal | PLC address | Example |
---|---|---|
Digital Input DI[x] | %Qx | DI[1] <=> %Q1 |
Digital Output DO[x] | %Ix | DO[1] <=> %I1 |
Robot Input RI[x] | %Q(5000+x) | RI[1] <=> %Q5001 |
Robot Output RO[x] | %I(5000+x) | RO[1] <=> %I5001 |
UOP Input UI[x] | %Q(6000+x) | UI[1] <=> %Q6001 |
UOP Output UO[x] | %I(6000+x) | UO[1] <=> %I6001 |
SOP Input SI[x] | %Q(7000+x) | SI[0] <=> %Q7001 |
SOP Output SO[x] | %I(7000+x) | SO[0] <=> %I7001 |
Weld Input WI[x] | %Q(8000+x) | WI[0] <=> %Q8001 |
Weld Output WO[x] | %I(8000+x) | WO[0] <=> %Q8001 |
Wire Stick Input WSI[x] | %Q(8400+x) | WSI[0] <=> %Q8400 |
Wire Stick Output WSO[x] | %I(8400+x) | WSO[0] <=> %Q8400 |
Group Input GI[x] | %AQx | GI[1] <=> %AQ1 |
Group Output GO[x] | %AIx | GO[1] <=> %AI1 |
Analog Input AI[x] | %AQ(1000+x) | AI[1] <=> %AQ1001 |
Analog Output AO[x] | %AI(1000+x) | AO[1] <=> %AI1001 |
PMC keep relay DO[x] (x : 10001 – 10144) Ka.b | %Ix %I((a*8)+b+10001) | DO[10001] <=> %I10001 K2.5 <=> %I10022 |
PMC internal relay DO[x] (x : 11001 – 23000) Ra.b | %M(x-11000) %M((a*8)+b+1) | DO[11001] <=> %M1 R2.5 <=> %M22 |
PMCdata table GO[x] (x : 10001 – 12000) D(a*2), D((a*2)+1) | %AI(x-6000) %AI(a+4001) | GO[10001] <=> %AI4001 D4, D5 <=> %AI4003 |
According to the same document, subchapter 6.2 - READING FROM AND WRITING TO REGISTERS (%R), the standard mapping of registers from the robot controller to PLC addresses is as follows:
Robot controller data | PLC address | Example |
---|---|---|
Register | %Rx | R[1] <=> %R1 |
Values in registers are 16-bit signed numbers, the fractional part is rounded off.
The documentation further states that this standard mapping can be changed using the $SNPX_ASG system variable. This allows you to set up the multiplier for conversion and modify the mapping of registers. One register can be mapped to one %R variable (as 16-bit signed number), to two consecutive %R variables (32-bit signed number, use %RD in I/O tag address), or to two consecutive %R variables as a real number (32-bit float number, use %RF in I/O tag address).
The default mapping of R registers is related to the setting of $SNPX_ASG[1] to:
Item | Value |
---|---|
$ADDRESS | 1 |
$SIZE | 10000 |
$VAR_NAME | 'R[1]@1.1' |
$MULTIPLIFY | 1.000 |
With this setting, the registers R[1] .. R[10000] are mapped to registers %R1 .. %R10000 as 16-bit signed numbers.
The standard mapping of PR position registers (intended for storing robot positions) ensures the setting of $SNPX_ASG[2]:
Item | Value |
---|---|
$ADDRESS | 11000 |
$SIZE | 100 |
$VAR_NAME | 'PR[1]' |
$MULTIPLIFY | 0.000 |
With this setting, the individual position components (X, Y, Z, W, P, R, etc.) will be mapped as 32-bit float numbers at the addresses %RF11000, %RF11002, %RF11004, and so on (50 registers per one PR, a total of 100 registers per PR[1] and PR[2]). For more details see subchapter 6.3 READING FROM AND WRITING TO POSITION REGISTERS (% R).
The standard mapping of current position registers POS ensures the setting of $SNPX_ASG[3]:
Item | Value |
---|---|
$ADDRESS | 12000 |
$SIZE | 100 |
$VAR_NAME | 'POS[0]' |
$MULTIPLIFY | 0.000 |
With this setting, the individual position components (X, Y, Z, W, P, R, etc.) will be mapped as 32-bit float numbers at the addresses %RF12000, %RF12002, %RF12004, and so on (50 registers per one POS, a total of 100 registers per POS[0] and POS[1]). For more details see subchapter 6.3 READING AND WRITING THE CURRENT POSITION (%R).
The mapping of ALM registers containing alarm history is possible by setting $SNPX_ASG[x]:
Item | Value |
---|---|
$ADDRESS | 12100 |
$SIZE | 300 |
$VAR_NAME | 'ALM[1]' |
$MULTIPLIFY | 1.000 |
With this setting, the individual components of the alarm history (AlarmID, Alarm number, Alarm severity, Alarm message, etc) will be accessible at the configured addresses (100 registers per ALM, i.e. 300 registers will cover 3 alarms). For more details see subchapter 6.5 READING ALARM HISTORY (%R).
The mapping of PRG registers containing program execution status is possible by setting $SNPX_ASG[x]:
Item | Value |
---|---|
$ADDRESS | 12400 |
$SIZE | 18 |
$VAR_NAME | 'PRG[1]' |
$MULTIPLIFY | 1.000 |
With this setting, the individual components of program execution status (Program name, Line number, Execution status, Calling program name) will be accessible at the configured addresses (18 registers per PRG). For more details see subchapter 6.6 READING THE PROGRAM EXECUTION STATUS (%R).
The mapping of various system variables is also possible by setting $SNPX_ASG[x]. Example:
Item | Value |
---|---|
$ADDRESS | 12420 |
$SIZE | 2 |
$VAR_NAME | '$mcr.$genoverride' |
$MULTIPLIFY | 1.000 |
With this setting, the registers 12420 and 12421 will contain the OVERRIDE system variable (item $genoverride of system variable $mcr) as a 32-bit signed integer (address %RD12420, read/write access). For more details see subchapter 6.6 READING FROM AND WRITING INTO SYSTEM VARIABLES (%R).
The mapping of comments to registers, position registers, and various I/O is also possible by setting $SNPX_ASG[x]. Example:
Item | Value |
---|---|
$ADDRESS | 12440 |
$SIZE | 160 |
$VAR_NAME | 'R[C1]' |
$MULTIPLIFY | 1.000 |
With this setting, the registers %R12420 to %R12599 will contain comments to registers R1 to R4 (40 registers, i.e. 80 characters per comment - addresses %R12440:40, %R12480:40, %R12520:40 and %R12560:40). Similarly, it is possible to configure comments for other types of objects (e.g. 'PR[C1]', 'DI[C2]', 'GI[C1]', 'GO[C1]' etc). For more details see subchapter 6.8 READING AND WRITING THE COMMENT OF REGISTERS, POSITION REGISTERS, AND I/O (%R).
The mapping of I/O values and simulation status is also possible by setting $SNPX_ASG[x]. Example:
Item | Value |
---|---|
$ADDRESS | 12430 |
$SIZE | 4 |
$VAR_NAME | 'RO[S1]' |
$MULTIPLIFY | 1.000 |
With this setting, the registers %R12430 to %R12433 will contain the status of robot outputs RO[1] to RO[4] simulation. Similarly, it is possible to configure simulation status for other types of objects (e.g. 'DI[S1]', 'DO[S2]', 'DO[S1]', 'RI[S1]' etc) as well as values of these objects (e.g. 'DI[1]', 'DI[2]', 'UO[1]', 'SI[1]' atď). For more details see subchapter 6.9 READING AND WRITING THE VALUE AND SIM STATUS OF I/O (%R).