Event logging in the system

The "Log database" dialog box in the D2000 CNF process allows setting the log database parameters. The dialog box contains a table comprising the following columns:

Event categoryData purpose objectSystem events
AlarmsAlarmLoggingAll changes of alarm states (information about particular alarm states and their changes, see the online guide D2000 System Configuration - topic Alarm states).
SystemSystemLoggingStart and stop of the D2000 system
Operator's logon into the D2000 system (logon with incorrect name or password).
ProcessProcessLoggingAll status changes of the D2000 system processes (e.g. start, stop, breakdown).
Kom processKomLoggingCommunication failures.
OperatorOperatorLoggingAll operator's interactions into the system (e.g. changes of system objects' values via control windows in the D2000 HI process).
EventEventMsgLoggingLogs are written by performing LOG commands.
Logon/LogoffLogonLogoffLoggingOperator's logon/logoff from/to the D2000 system processes.
Data exportDataExportLoggingExport from Browser
Change valueChangeValueLoggingSpontaneous changes of values.
PostMortemDataPostMortemDataLoggingSpecial communication data.

To set parameters to write events of a given category into the log database:

  1. Click the required category of events.
  2. Using Log, History depth, Use device and Device placed bellow the table, set parameters for the given category of events.
  3. Click the Save button to confirm the log database configuration.