List of objects connected to the picture

Process D2000 GrEditor allows a user to display information about all objects that are connected to the picture either to control or to view.


To display information about connected objects

  1. Click the button List of connections Connection lists in the Main toolbar.
  2. It opens the dialog box containing information about objects in the picture.
  3. Click the button Connected.

List of objects connected to the picture

Information about connected objects is displayed in the table containing the following columns.

Syst. objectLine number and the name of the D2000 system object that is connected to given graphic object.
TypeObject value type.
GOGraphic object ID.
TypeConnection type:
  • Z - connection to view
  • O - connection to control
  • R - connected reference variable
  • P - palette's control object
RepaintMethod to repaint the graphic objects after changing the connected object value.
CategoryLocal variable category.
PaletteName of used display palette or bitmap palette.
Ext. paletteName of used extended palette.
ControlControl parameters - for more info see the article below "Information on control".
Descr. GOGraphic object name.
TextText used in graphic object.

Note: For the graphic object of Tab control type, the tab name is displayed.

Colors in the list:

According to the selected category, local variables in the list differ by appropriate colors:

Black text represents the unfiltered (visible) objects and red text filtered objects (invisible). If the object belongs to some group, the text is written in a lighter color.


Information on control

The column Control contains information on graphic object parameters relating to control - connection to control.

[action on] - [control mode]

[action on] - controlling of the connected object can be a reaction to any user's action performed on given graphic object in the D2000 HI process:

[control mode] - mode to control connected object.

If the connected object is a graphic information window (picture, graph) or a composition, the column Control can contain one of the following information:

For more information on the position of graphic information window on the D2000 HI desktop, see the topic Modes to control connected object.

If the option Set directly (quick value setting of D2000 system objects of Integer type) is selected to control the connected object, the column Control contains the string small ctrl. window.

If the option Open window (control by means of dialog window) is selected to control connected object, the column Control contains the string ctrl. window.

If the option Set value is selected, the column Control contains one of the following information:


To disconnect all connections

The button Disconnect all is used to disconnect all connections of graphic objects and object connected to the picture. Clicking the button opens the dialog box to confirm disconnecting - the button Yes. If you change your mind, click the button No.

List of objects in the picture
List of graphic objects used in the picture
Connecting graphic objects