AMiT ATOUCH32 DB-Net communication protocol

Supported device types and versions
Communication line configuration
Communication station configuration
DB-Net initialization
I/O tag configuration
Errors and problems
Literature
Changes and modifications
Document revisions

Supported device types and versions


The protocol supports data acquisition using device from the AMiT company (ADiS modular control system and ART267, ART4000, AMiRiS and AMAP compatible control systems and others) via a DB-Net communication network. Communication requires installation of ATOUCH32 driver to communicate in a DB-Net ATOUCH32 network (you can download it at http://www.amit.cz). Communication was tested and tuned for the ATOUCH32 driver of V2.10, V2.30, V2.40, V2.60, V2.90 and V3.30 versions.

Limitations: The protocol does not support database variables of "own station", i.e. on the computer with ATOUCH32 driver running but allows to read/write variables on process stations. The DB-Net driver can be used by just one application (in our case the process D2000 KOM) at the same time.

When using the older versions of ATOUCH32 V2.x, there must be configured just one communication line for DB-Net communication. ATOUCH32 V3.x versions enable so-called multithreading. It means, you may connect more lines, which will communicate in parallel, to ATOUCH32 and speed up the communication. The driver must be initialized only by one line (see "Init File" parameter, note 2). There is still the rule that all lines must be configured within one KOM process in one computer. This may be used in D2000 V9.00.021 rel.021 and higher.

Communication line configuration



Communication line parameters

Communication line - configuration dialog box - the Protocol parameter tab.
Parameters defined in the field have effect on some optional protocol parameters. There can be defined the following line protocol parameters:

Table 1

Full name Description Units / size Default value
HW Init File Full path to the file containing the DB-Net configuration.

Note 1:
If the line protocol parameter INIFILE is not specified (empty string), then the station protocol parameters described below must be configured correctly for all stations. The parameters of DB-Net IP can be configured only by "Init File".

Note 2: If you do not want so that the line initialized ATOUCH32 in the multithread mode, use "---", i.e. 3x "minus" character. One line within KOM process must contain the path to the existing init file. It, then, executes the initialization for all other lines.
-

Communication station configuration



Communication station parameters

Communication station - configuration dialog box - tab Protocol parameter.
Parameters defined in the field have effect on some optional protocol parameters. There can be defined the following station protocol parameters:

Table 2

Full name Meaning Unit/ size Default value
My Station Address of "own station" (PC with ATOUCH32 driver running) - 31
COM Port COM port used for the communication - 1
COM Speed Communication baud rate. - 19200
Max. Transactions Error Maximum number of consecutive read commands that failed to label the communication with station as failed. The status of station is set on StCOMERR. If the number of failed readings of I/O tags exceeds the double of this value the reading of next I/O tags will be stopped. The purpose is to make fast the communication (the station is considered to be completely inaccessible). - 10
Full Debug High level of line debug messages - trace messages contain details about received values of I/O tags. - False
Enable Matrix Read Reading of matrix variables will be optimised for slow networks (e.g. GPRS). Reading of variables with matrix types (INT MATRIX, LONG MATRIX, FLOAT MATRIX a DBNETTIME MATRIX) will be optimised. If multiple I/O tags share the same WID and type, only a single read request is generated and it incorporates a range of rows and columns of all these I/O tags. - False

DB-Net initialization


When starting, the DB-Net driver requires to get the configuration file or string containing the DB-Net network configuration in particular application. If you use the communication via standard COM port, it is possible to avoid creating the configuration file on disk using the My Station, COM Port and COM Speed station protocol parameters which must be configured for one of the stations.

If the Init File line protocol parameter is specified for a line (at least one), then the My Station, COM Port and COM Speed the protocol parameters will be ignored on all the stations. There will be used the configuration file on the disk which path is defined by the Init File line protocol parameter.
For further information on the file contents see the ATOUCH32 online help.

Example: configuration file contents:

[General]
MyStation=0
UDP.MyPort=222
UDP.MyPassword=111222333

[COM]
Com=2
Speed=38400
Station=1
Station=2
Station=4
Station=13

[COM]
Com=3
Speed=9600
OfsNet=32
Station=33
Station=34
Station=36
Station=45 

[UDP]
Address=192.168.168.1
Password=444555666
Offset=10
Station=10
Station=20
Station=30

[UDP]
Address="segment100.firmaXY.cz"
Password=777888999
Port=333
Offset=100
Timeout=5000
Station=105
Station=106
Station=107

I/O tag configuration


Possible I/O tag types: Ai, Ao, Ci, Co, Di, Do, TxtI, TxtO, TiA, ToA, TiR, ToR.

I/O tag address consists of:

Errors and problems


When starting or during the communication, there could be occurred the following error reports. To make the problem identification easier, set the communication tracking at least to the level Monitor (the best is to temporary set Monitor & Disk). When you set the option Monitor & Disk, there will create the file "line_name.LOG" in the application subdirectory TRACE, that will contain all debug and error logs. If the problems still persist, please contact the IPESOFT's technical support.

Error: DB-Net Station Address Error - 'StationName', Address : 'StationAddress'
Solution: Invalid station address - check the Address tab in the communication station configuration dialog box (in the process D2000 CNF) and eventually save the station configuration and restart the process D2000 KOM.
Error: DB-Net Point Address Error - 'PointName', Address : 'PointAddress'
Solution: Invalid I/O tag address - check the Address tab in the I/O tag configuration dialog box (in the process D2000 CNF) and eventually save the I/O tag configuration.
Error: DB-Net ATOUCH32 ERROR - 0xXY - AtchInitFromStringA
Solution: Error when calling the ATOUCH32 function AtchInitFromStringA - check the station configuration and protocol parameters. During start, the process D2000 KOM shows the configuration string pattern (the communication tracing level at least Monitor must be enabled) and check if meet required state.
Error: DB-Net ERROR - CreateSemaphore - ErrNr - Error description
Solution: System error of Windows API call. Restart the operating system.
Error: DB-Net ATOUCH32 ERROR - 0xXY - AtchReqGetVariable
DB-Net ATOUCH32 ERROR - 0xXY - AtchReqPutVariable
Solution: Error when calling the ATOUCH32 functions AtchReqGetVariable or AtchReqGetVariable for reading /writing a DB-Net database variable value. Previous communication tracing logs allow to detect which I/O tag is in troubles and then check its configuration.
Error: DB-Net ERROR - Reading 'PointName' - TNRES=0 !
DB-Net ERROR - Reading 'PointName' - TNRES=1 (reading on progress) !
DB-Net ERROR - Reading 'PointName' - TNRES=Invalid !
DB-Net ERROR - Writing 'PointName' - TNRES=0 !
DB-Net ERROR - Writing 'PointName' - TNRES=1 (reading on progress) !
DB-Net ERROR - Writing 'PointName' - TNRES=Invalid !
Solution: Transaction errors of reading/writing the DB-Net database variable. They couldn't occur.
Error: DB-Net ERROR - Reading 'PointName' - TNRES=4 (station not responded) !
DB-Net ERROR - Writing 'PointName' - TNRES=4 (station not responded) !
Solution: Transaction errors of reading/writing the DB-Net database variable. Station doesn't response because it is switched off, a problem with the communication wire or an configuration error (e.g. wrong baud rate, address or port). The error could occur sporadically, especially at reading.
Error: DB-Net ERROR - Reading 'PointName' - TNRES=4 (station responded) !
DB-Net ERROR - Writing 'PointName' - TNRES=4 (station responded) !
Solution: Transaction errors of reading/writing the DB-Net database variable. The station responded with an error. Probably it is an attempt to read or write the variable, which has no mirror in given device. Check the configuration of corresponding I/O tag and compare it with the log from the AMiT PSP3 software tool.
Error: DB-Net ATOUCH32 ERROR - 0xXY - AtchInitFromFileA
Solution: Error when calling the ATOUCH32 function AtchInitFromFileA. Check if the protocol parameter INIFILE is configured just for one station and is pointed to existing file on disk.

Literature


Changes and modifications


Document revisions


Communication protocols