The protocol LGPROFIBUS implements a communication with Landis&Gyr devices on the basis of ProfiBus communication protocol.
This communication supports (is verified) these Landis&Gyr devices:
Table 1
Device | Version of software on device | Version of protocol |
---|---|---|
PRU10.64 |
The card KMFB02 (Incos a.s. Žilina) is used as physical communication interface with the firmware IpeSoft s.r.o. Žilina (stored in EPROM). The communication runs on baud rate 93.75 kBd. A firmware in card provides all basic tasks for access to ProfiBus network. The card needs a driver KMFB02.SYS.
The parameters are configured in a dialog box – Communication station - configuration dialog box.
They influenced a behavior of the access to the communication medium. You can define the following parameters:
Table 2
Key word | Full name | Meaning | Unit | Default value |
---|---|---|---|---|
WT | WR_TIME | Delay before the message is sent. | ms | 80 |
RT | RD_TIME | Delay which is inserted into the executing of transaction when there is exceeded their maximum count. | ms | 100 |
MTR | MAX_TRANSACTION_NUMBER | Maximum transactions that are unfinished. | - | 5 |
MWR | MAX_WR_RETRY | Maximum retries during one record. | - | 5 |
MTT | MAX_TRANSACTION_TIME | Maximum waiting time for the response to end the transaction. | sec | 6 |
MMT | MAX_MESSAGE_TIME | Maximum time to complete at least one of unfinished transactions. After this timeout elapses, a communication error occurs in station. | sec | 10 |
The communication runs in the transaction way (Request/Response) for both data reading and writing. Data are read one point after another, always as a separate transaction.
String containing the protocol parameters is being defined as follows:
Key_word=value;Key_word=value; ...
Example:
WT=90;RT=200;MTR=7;
If there is used a keyword with an invalid value in the initialization string, there will be used corresponding default value according the table 1.
I/O tags: Ai, Ao, Ci, Co, Di, Do, TiR, ToR, TxtI, TxtO
I/O tag types correspond to the following „Profibus_Type“:
Table 3
D2000 type | Profibus_Type |
---|---|
Ci, Co | Unsigned16 |
Ai, Ao | FloatingPoint |
TxtI, TxtO | Bit_String |
TiR, ToR | TimeDiff32, TimeDiff48 |
Di, Do | Unsigned16 |
The address is a number in the range of 0 up to 65535.
Note:
You can use the software RefGen for easy configuration and servicing the
addresses of I/O tags when changing software in PLC. L&G utility „pointrep“
enables to generate a file „*.adr”, which is an input for RefGen. RefGen uses
the columns
“ProfiBus_Type” (Table 3), “OV_Index” (the address) and “Access_Right” (input/output).
-
-