Remia KME communication protocol

Supported device types and versions
Communication line configuration
Communication station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions

Supported device types and versions


The protocol supports reading data from the Remia KME concentrator. Internal number of REMIA protocol is 206.

The protocol supports reading of instant values as well as 1 and 15 minute archives of measurements from electrometers, which KME obtains:

The protocol also supports reading of instant values of binary data and values of 16-bit counters.

Communication line configuration


Communication station configuration



Station protocol parameters

Configuration dialog box of station - the tab "Protocol parameters".

Table 1

Key wordFull nameMeaningUnitDefault value

WT

Wait TimeoutTimeout to receive a response or one of its fragments.s.ms1.5 s

FA

Fragmented answer is expectedThe response may consist of several UDP packets (fragments).-False

ADOI

Actual Data Object ID

The address of the object (16-bit number) that contains information about the current values (analogs). A value of 0 disables reading of the current values as well as their 1 and 15-minute archives.

-8

A15OI

15min Archive Data Object ID

The address of the object (a 16-bit number) that contains information about 15-minute values. A value of 0 disables reading of 15-minute values.

-5

A1OI

1min Archive Data Object IDThe address of the object (a 16-bit number) that contains information about 1-minute values. A value of 0 disables reading of 1-minute values.-9

ABII

Binary data Object ID

The address of the object (a 16-bit number) that contains information about binary values. A value of 0 disables reading of binary values.

-0

EMNR

Number of EMs

The number of electrometers (1-255) whose instant data from impulse measurement (instant counter value, instant power, average power since the start of the current time interval, validity of the meter's data) are in response to reading the Actual Data Object ID, and whose historical data 1 and The 15-minute minutes (end-of-period counter value,, average power per period) are in response to reading 1min Archive Data Object ID and 15min Archive Data Object ID.

-41

EINR

Number of EIs

The number of meters (1-255) whose instant data from IEC communication (instant counter value, numbers of last 3 accumulations, counter values for the last 3 accumulations) are in response to reading the Actual Data Object ID, and historical data (last accumulation number, counter value for the last accumulation) are in response to reading 1min Archive Data Object ID and 15min Archive Data Object ID objects.

-6

EIVR

Number of values in EI

The number of measurements (1-255) in the EI section (data from IEC communication) in response to reading the Actual Data Object ID1min Archive Data Object ID15min Archive Data Object ID objects.

-16

WCNR

Number of word counters

The number of 16-bit counters (0-255) whose values are in response to reading the Actual Data Object ID object.

-0

PBD

Debug Packet Binary Contents

Activates advanced debugging with listing of binary data being sent and received.


YES/NOYES

FULL_DEBUG

Debug Values

Activates advanced debugging with listing of I/O tag values.

YES/NONO


I/O tag configuration


I/O tag types: Ai, Ci, Qi, Di, TiA.

The address of I/O tag can have different forms.

For electrometers in the EI structure - i.e. electrometers obtained by IEC communication - it has the form EI.EiNr.EiInd.EiParam where:

Examples of addresses:

EI.1.1.AV
EI.3.13.N1


For electrometers in the EM structure - i.e. electrometers obtained by measurement of impulses - it has the form EM.EmNr.EmParam  where:

Examples of addresses:

EM.2.CA15
EM.1.OV
EM.4.CA1
EM.5.CA
EM.40.PV
EM.40.PV1


For binary data - read from the object with address Binary data Object ID - it has the form DI.WrNr.BitNr.DiParam  where:

Examples of addresses:

DI.2.10.INP
DI.1.0.INP
DI.3.14.PPO


For instant values of 16-bit counters - read from the object with address Actual Data Object ID - it has the form EW.EwNr  where:

Examples of addresses:

EW.1
EW.47

Literature


-

Changes and modifications


-

Document revisions



Communication protocols