Communication line of LonWorks category

Supported types and device versions


A communication with LonWorks networks executes by an interface of Echelon devices (SLTA, PCLTA, iLON-10, ...) and the system Windows driver. Driver is installed together with "Echelon OpenLDV Installer" available on http://www.echelon.com/. The communication was tested on following interfaces:

Communication line configuration


Device

Set a device name (e.g. LON1, LON2 up to LONx according to the driver configuration (older devices as SLTA etc.)) or the interface name configured in "Control Panel" -> "LonWorks Interfaces" in case of the new devices as iLON-10 driver, which is installed through the Echelon OpenLDV Installer.

The file ldv32.dll had to be copied into an installation directory of D2000 System in case of older interfaces. OpenLDV Installer does not requires this file.

Node address parameters configuration


Click on the button Node parameters in the tab LonWorks and the following dialog box opens. It allows editing the node address parameters.

Check Configure parameters if you want to configure the node, otherwise all the address parameters will not change.


Change of domain address parameters

The node will belong to the domain according to the parameters in the domain table. Choose Domain 0 or Domain 1. The domain will deactivate if you do not choose any option.

Domain table parameters:

Note: An utility Echelon NodeUtil always manipulates with the Domain 1 table to receive the broadcast messages.


Change of Group Address parameters

After checking the check box from 0 to 14, the node will belong to selected groups (Group Address).

Group address parameters:

Table 1

Encoding of Timer Field Values (ms)

Value rpt_timer rcv_timer tx_timer
0 16 128 16
1 24 192 24
2 32 256 32
3 48 384 48
4 64 512 64
5 96 768 96
6 128 1024 128
7 192 1536 192
8 256 2048 256
9 384 3072 384
10 512 4096 512
11 768 6144 768
12 1024 8192 1024
13 1536 12288 1536
14 2048 16384 2048
15 3072 24576 3072