CALCARCHEXPR archExprIdent_Txt, btIdent_TimA, etIdent_TimA, stepIdent_Int, _ignoreInvalid_Bool, _locVarColValueIdent_Rec, statusIdent_Int |
| archExprIdent_Txt | in | Value identifier of Text type containing the expression. |
| btIdent_TimA | in | Identifier of AbsTime type - interval beginning. |
| etIdent_TimA | in | Identifier of AbsTime type - interval end. |
| stepIdent_Int | in | Identifier of Int type - time step [s]. |
| _ignoreInvalid_Bool | in | Identifier of Bool type - invalid values in expression will be replaced by 0. |
| _locVarColValueIdent_Rec | out | Reference to local variable column of RECORD type - final values. |
| statusIdent_Int | out | Identifier of Int type - success of calculation. |
TIME _bt, _et
INT _step
INT _retCode
TEXT _expr
TEXT _err
BOOL _bIgnoreInvalid
RECORD NOALIAS (SD.Data) _data
_bt := %StrToTime("00:00:00 01-01-2008")
_et := %StrToTime("00:00:00 02-01-2008")
_step := 1
_bIgnoreInvalid := @TRUE
_expr := "H.a + H.GetArchRowCol_Ref[2]^I2 + H.GetArchRowCol_Ref_Col_I1[2]"
CALCARCHEXPR _expr, _bt, _et, _step, _bIgnoreInvalid, _data^Value, _retCode
IF _retCode = _ERR_NO_ERROR THEN
; processing of result
ELSE
_err := _ERR_MSG ; extended error description
ENDIF |
Owing to the expression parsing works during system running (not during configuration) and if any errors occur, it is possible to obtain their detailed description as value of predefined local variable of Text type _ERR_MSG.