This protocol supports data reading and writing to the dataloggers INMAT 66 and INMAT 51 produced by ZPA Nová Paka (Czech republic).
Note:
When testing, we found out that there was a short period between sending the
request and receiving the response (less than 10 ms). You should enter the
similar values (1 to 10 ms) into the parameter "Receive delay" in line mode. If
there are several devices on one line (RS485), you should set such value which
is suitable for all devices to ensure 100% success of data transfer.
Communication station - configuration dialog box -
tab Protocol parameters.
They influence some of the optional parameters. You can set the following
station protocol parameters:
Table 1
Parameter | Meaning | Unit | Default value |
---|---|---|---|
Wait Timeout | Delay between reading the response until it is completed. | ms | 200 millisec. |
Wait First Timeout | First waiting for response after sending the request. | ms | 200 millisec. |
Retry Timeout | Delay between the response retry if some error in communication occurs. | ms | 500 millisec. |
Max Wait Retry | Maximum retries of reading the response until it is completed. | - | 4 |
Retry Count | Number of response retries if some error in communication occurs. | - | 2 |
Local Source Address | Local source address of D2000 KOM process. | - | 0 |
Full Debug | Communication monitoring high level, information about reading I/O tags and received values are displayed. | NO |
I/O tags: Ai
For address, you must set two parameters:
INX and IY
These address parameters are provided by the producer (ZPA Nová Paka) when buying the device.
The values are in hexadecimal format:
-