Supported device types and versions


This protocol supports the communication with KPX-02 devices and radio modems RMMBX that are used for the autonomous data acquisition by TOCCATA protocol.

UNIP2 protocol is used as a transport configuration and data protocol.

Communication line configuration


Communication station configuration



Station protocol parameters

Communication station - configuration dialog box - "Protocol parameters" tab.
These parameters influence some optional parameters of protocol. You can set the following station parameters:

Table 1

Parameters used for UNIP2 communication with KPX-02 (locally).
Key word Full name Meaning Unit Default value
ROUTE Routing Address The original address of the station for which the data was received by routing. - 0
RC Retry Count Number of repeat calls if the communication error occurs. - 2
RT Retry Timeout Delay between repeating the call if the communication error occurs. ms 100
WFT Wait First Timeout First waiting for the response after sending the call. ms 100
WT Wait Timeout Delay between reading the response until it is completed. ms 100
MTU MTU For Sending MTU (maximum transmission unit) for sending data. bytes 240
MRTU MTU For Receiving MTU (maximum transmission unit) for receiving data. bytes 240
MWR Max. Wait Retry Number of retry response reading until it is completed. - 20
WRD Wait Response Delay The period, after writing, during which D2000 KOM keeps communicating with the station to obtain the confirmation of successful write. sec 0
Parameters that configures data acquisition by TOCCATA protocol in KPX-02 device (transported).
Key word Full name Meaning Unit Default value
MPI Max PA Items Maximum PA data in one data block. 2 to 12 10
KLRD KL Read Delay Delay between the reading of KL points. min 2
MAXERR Max Errors Maximum errors in communication with L&G device. When this value is exceeded, all data will become invalid. - 4
RETRY Retry Number of retries of one call for data from L&G device. - 2
TIMEOUT Timeout Absolute time necessary to read the response form L&G device. ms 3000
TXDELAY Tx Delay Delay of sending the response from the communication device after receiving the call. Useful only for RMMBX radio modems. x10 ms 15 (150 ms)
PRUV PRU Version Version of TOCCATA protocol. It is the same as in L&G TOCCATA protocol. 0, 1, 2, 33 0

String containing the protocol parameters is defined as follows:

Key_word=value;Key_word=value; ...

Example:

WT=100;MWR=20;

If there is used a keyword with an invalid value in the initialization string, there will be used corresponding default value according the table 1.

I/O tag configuration


The rules are the same as in TOCCATA protocol (see L&G TOCCATA protocol).

Literature


-

Changes and modifications


-