This protocol supports data reading from / writing to Johnson Controls devices, DX9100 unit, that are equipped by a serial port for N2 Bus. The implementation currently does not support N2 Open standard.
Note: on TCP-IP/TCP line, multiple host names or IP addresses separated by comma/semicolon can be defined, to connect to multiple devices in round-robin fashion.
The configuration dialog box - Parameters tab.
The parameters influence some optional parameters of protocol. There can be defined the following parameters of station protocol:
Table 1
Parameter | Meaning | Unit | Default value |
---|---|---|---|
Delay between reading the responses until it is completed. | millisec | 100 millisec | |
The first waiting for a response after sending a call. | millisec | 200 millisec | |
Delay between retry calls if a communication error occurs. | millisec | 500 millisec | |
Number of retry response reading until it is completed. | - | 10 | |
Number of retry calls when error in communication occurs. | 1 .. 32 | 2 | |
| Maximum number of consecutive errors in one station reading cycle after which the next I/O tags are no longer read. A value of 0 causes all I/O tags to be read. The parameter is implemented to prevent one non-communicating station from causing excessive reading delay for other stations on the line. | - | 0 |
| Enables the detailed debug information about values of I/O tags that were obtained by polling. | YES/NO | NO |
Used I/O tags: Ai, Ao, Ci, Co, Di, Dout.
The address of I/O tag can define in two formats:
1. Predefined items DX9100 has format:
Modul.Tag
Where Modul is a name of module and Tag is name of tag within a module. List of items is based on the documentation DX-9100 Configuration Guide, Appendix B. Since this is a large list of the static items, there is prepared "Object Browser" dialog window, where you may find the particular object. In the "Item Address" section click the button next to the "Item" field.
The following window opens:
The left part of window contains the list of modules. After clicking the particular module, the list of tags that belong to this module are displayed in the right part of window.
Parameters of items:
Tag: Name of tag.
Description: Short description of item.
Access: Access level (R - read-only, R/W - read and write, CNF - read and write, the configuration parameter is recorded into EEPROM).
Type: Value type of item (see also here).
Address: Physical address of item that is used for reading/writing. It is calculated from the starting address of module and offset tag (in hexadecimal format). The bit number (1 up to 32) of the addresses of binary items is placed after dot.
After double-click the particular tag, the dialog window is closed and name of item occurs in the "Item" field in the "Item Address" section.
2. User format:
#Typ.Addr[.Bit]
Where:
Type is a value type of item. There are supported these types:
Value type | Range, value interpretation |
---|---|
U8 | 8 bits unsigned (JC tagging 1 Byte) |
U16 | 16 bits unsigned (JC tagging 2 Byte) |
U32 | 32 bits unsigned (JC tagging 4 Bytes) |
I8 | 8 bits signed (JC tagging 1 Byte Int) |
I16 | 16 bits signed (JC tagging 2 Byte Int) |
FP16 alebo N | 16 bits floating point in Johnson Controls format (JC tagging Number) |
CONN | Connection - interpreted as 16 bits unsigned |
DST | Destination - interpreted as 16 bits unsigned |
Address is the address of item in decimal format.
Bit is a bit number. Optional parameter, it is important only for binary items, when the particular bit is extracted form the value of whole item (for U8, U16 or U32 items).
Examples:
N.1232
U8.765.1
U32.4078
This user format is advisable to use when the required item is not in the list of predefined items.
Starting with D2000 version 10.1.37 (patches from 12.4.2016 and newer) it is possible to configure Time Schedules. In "Object Browser" new modules TS1cfg, TS2cfg .. TS8cfg have been added, each of them repesents a configuration of one Time Schedule.
Every time schedule has several general parameters and a set of eight begin times (BETIME1..8), end times (EETIME1..8) and days when a time schedule is active (EEDAYS1..8).
A time interval is configured by writing values to begin time and end time. Writing is supported for relative time (e.g. 01:05:00) and for Ao/Co (value in seconds, i.e. 01:05:00 equals to 3 900). Times are sent to device as hours:minutes (i.e. seconds are ignored). Invalidation of time is possible by writing invalid value or value 24:00:00 or greater (86400 seconds or more).
By writing value to days (EEDAYS1..8) it is possible to specify during which days a time schedule is active. Value is a number (0-255) interpreted as a bit mask:
-